DL06 I/O Specifications: D0-06DD1 (DL05 / DL06 PLCs), pages 1 to 6
Pages 1 to 6 of 11
The original document is the PDF (3.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Koyo DL06 D0-06DD1
Page 1
For the latest prices, please check AutomationDirect.com.
DL06 I/O Specifications D0-06DD1 $251.00
Note: Refer to Power Budgeting for Auxillary 24VDC current available.
Wiring diagram and specifications Power input wiring
D0-06DD1 Specifications AC Power Supply Voltage Range Specifications Number of Input Pts.
100–240 VAC/ 50–60 Hz, 40VA maximum 20 (sink/source)
Number of Commons
5 (isolated)
Input Voltage Range
12–24 VDC
Input Impedance
(X0-X3) 1.8K @ 12–24 VDC (X4-X23) 2.8K @ 12–24 VDC
On Current/ Voltage Level OFF Current/ Voltage Level Response Time OFF to ON Response ON to OFF Response Fuses Number of Output Points Number of Commons Output Voltage Range Peak Voltage Max.Frequency (Y0,Y1) ON Voltage Drop
DC Input Specifications
6-27 VDC 95-240 VAC
>5mA/10VDC <0.5mA/<2VDC X0-X3
X4-X23
<100µs
<8ms
<100µs
<8ms
None 16 (sinking) 4 isolated 6–27 VDC 50VDC 7kHz 0.3VDC @ 1A
12-24 VDC
Source
Sink
Input point wiring
Equivalent input circuit, Standard inputs (X4-X23)
0.5 A / pt (Y0-Y1)* 1.0 A pt (Y2-Y17)**
Maximum Current
Maximum Leakage Current 15µA @ 30VDC Maximum Inrush Current 2A for 100ms <10µs OFF to ON Response
DC Output Specifications
20-28 VDC
Output point wiring
ON to OFF Response
<20µs (Y0-Y1) <60µs (Y2-Y17)
External DC Power Required
20–28 VDC 150mA max. (Y0-Y1) 280 mA max. (Y2-Y17)
Status Indicators
Logic side
Fuses
None (external recommended)
9'& 6RXUFH
6LQN
Equivalent input circuit, High-speed inputs (X0-X3)
9'& 6RXUFH
* When Y0-Y1 are not used for pulse outputs, maximum current output is 1.0 A**.
6LQN
** These outputs must be derated to 0.6A for EN61131-2 compliance. Equivalent output circuit Pulse output (Y0-Y1)
Derating chart for DC outputs
Points 16
0.75A
Y0 - Y17
12
1.0 A
9'&
Equivalent output circuit Standard output (Y2-Y17)
9'&
8 4 0 0 32
10 50
20 68
30 86
40 104
50 55˚C 122 131˚F
Ambient Temperature ( ˚C/ ˚F)
tDL5-27
DL05 / DL06 PLCs
1-800-633-0405
Page 2
For the latest prices, please check AutomationDirect.com.
Features at a Glance The DL05 and DL06 micro PLCs are complete self-contained systems. The CPU, power supply, and I/O are all included inside the same housing. Option modules are available to expand the capability of each PLC family for more demanding applications. The standard features of these PLCs are extraordinary and compare favorably with larger and more expensive PLCs. The specification tables to the right are meant for quick reference only. Detailed specifications and wiring information for each model of the DL05 and DL06 PLCs can be found in those specific sections.
Program capacity Most boolean ladder instructions require a single word of program memory. Other instructions, such as timers, counters, etc., require two or more words. Data is stored in V‑memory in 16-bit registers.
Performance The performance characteristics shown in the tables represent the amount of time required to read the inputs, solve the Relay Ladder Logic program and update the outputs.
Instructions A complete list of instructions is available at the end of this section.
Communications The DL05 and DL06 offer powerful communication features normally found only on more expensive PLCs.
Special features The DC input and DC output PLCs offer high-speed counting or pulse output. Option module slots allow for discrete I/O expansion, analog I/O, or additional communication options.
DL05 CPU Specifications System capacity
Total memory available (words)………………… 14.8K Ladder memory (words)………………………… 7680 V-memory (words)………………………………7616 User V-memory………………………………7488 Non-volatile user V-memory…………………… 128 Built-in battery backup (D2-BAT-1)…………………Yes Total I/O………………………………………… 36 Inputs………………………………………… 20 Outputs……………………………………… 16 I/O expansion………………………………… Yes1
Performance
Contact execution (Boolean)…………………… 0.6µs Typical scan (1K Boolean)2 …………………… 1-2ms.
Contact execution (Boolean)…………………… 0.7µs Typical scan (1K Boolean)2………………… 1.5-3ms.
Instructions and diagnostics
RLL ladder style………………………………… Yes RLLPLUS/flowchart style (Stages)………………Yes/256 Run-time editing………………………………… Yes Supports Overrides……………………………… Yes Scan……………………………………Variable/fixed Number of Instructions……………………………133 Types of Instructions: Control relays………………………………… 512 Timers……………………………………… 128 Counters…………………………………… 128 Immediate I/O…………………………………Yes Subroutines……………………………………Yes For/next loops…………………………………Yes Timed interrupt……………………………… Yes Integer math………………………………… Yes Floating-point math…………………………… No PID………………………………………… Yes Drum sequencers………………………………Yes Bit of word…………………………………… Yes ASCII print…………………………………… Yes Real-time clock/calendar………………………… Yes1 Internal diagnostics……………………………… Yes Password security……………………………… Yes System and user error log………………………… No
Communications
Built-in ports……………………………Two RS-232C Protocols supported: K-sequence (proprietary protocol)……………… Yes DirectNet master/slave………………………… Yes Modbus RTU master/slave………………………Yes ASCII out…………………………………… Yes Baud rate Port 1………………………… 9,600 baud (fixed) Port 2…………………selectable 300-38,400 baud …………………………………… (default 9,600)
Specialty Features
Filtered inputs……………………………………Yes3 Interrupt input……………………………………Yes3 High speed counter…………………………Yes, 5kHz3 Pulse output……………………………… Yes, 7kHz3 Pulse catch input…………………………………Yes3
2- 1K program includes contacts, coils, and scan overhead. If you compare our products to others, make sure you include their scan overhead. 3- features only available on units with DC inputs and output features only available on units with DC outputs.
DL05 / DL06 PLCs
System capacity
Total memory available (words)…………………… 6K Ladder memory (words)…………………………2,048 V-memory (words)…………………………… 4,096 User V-memory………………………………3,968 Non-volatile user V-memory…………………… 128 Battery backup………………………………… Yes1 Total built-in I/O………………………………… 14 Inputs………………………………………… 8 Outputs………………………………………… 6 I/O expansion……………………………………Yes1
1- features are available with use of certain option modules. Option module specifications are located later in this section.
tDL5-3
DL06 CPU Specifications
Performance
Instructions and diagnostics
RLL ladder style………………………………… Yes RLLPLUS/flowchart style (Stages)…………… Yes/1024 Run-time editing………………………………… Yes Supports Overrides……………………………… Yes Scan……………………………………Variable/fixed Number of Instructions……………………………229 Types of Instructions: Control relays……………………………… 1024 Timers……………………………………… 256 Counters…………………………………… 128 Immediate I/O…………………………………Yes Subroutines……………………………………Yes For/next loops…………………………………Yes Table functions……………………………… Yes Timed interrupt……………………………… Yes Integer math………………………………… Yes Trigonometric functions…………………………Yes Floating-point math…………………………… Yes PID………………………………………… Yes Drum sequencers………………………………Yes Bit of word…………………………………… Yes Number type conversion……………………… Yes ASCII in, out, print…………………………… Yes LCD instruction……………………………… Yes Real-time clock/calendar………………………… Yes Internal diagnostics……………………………… Yes Password security……………………………… Yes System and user error log………………………… No
Communications
Built-in ports:………………………… One RS-232C …………One multi-function RS232C/RS422/RS485 NOTE: RS485 is for MODBUS RTU only.
Protocols supported: K-sequence (proprietary protocol)……………… Yes DirectNet master/slave………………………… Yes Modbus RTU master/slave………………………Yes ASCII in/out………………………………… Yes Baud rate Port 1………………………… 9,600 baud (fixed) Port 2…………………selectable 300-38,400 baud …………………………………… (default 9,600)
Specialty Features
Filtered inputs……………………………………Yes3 Interrupt input……………………………………Yes3 High speed counter…………………………Yes, 7kHz3 Pulse output………………………………Yes, 10kHz3 Pulse catch input…………………………………Yes3 1- features are available with use of certain option module. Option module specifications are located later in this section. 2- 1K program includes contacts, coils, and scan overhead. If you compare our products to others, make sure you include their scan overhead. 3- features only available on units with DC inputs and output features only available on units with DC outputs.
1-800-633-0405
Page 3
For the latest prices, please check AutomationDirect.com.
Features at a Glance DirectSOFT software The DL05 and DL06 PLCs use the same familiar DirectSOFT programming software that our larger PLCs use. A FREE version of DirectSOFT gives you all the great features of the full version, but with a 100-word PLC program download limitation. For programs larger than 100 words, the full package is required. The FREE PC-DS100 software may be sufficient to program the DL05 and DL06. If you are programming with a full package version prior to v6.0, you will need v2.4 or later for the DL05 PLCs and v4.0 or later for the DL06. We always recommend the latest version for the most robust features. See the DirectLOGIC Overview section DL in this catalog for a complete description of DirectSOFT including features, part numbers of programming packages and upgrades.
Programming
Handheld programmer....D2-HPP. . . . . . . . . . . . . . . $321.00 DirectSOFT Programming for Windows PC-DSOFT6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $395.00 PC-DS100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Free PC-R60-U (upgrade) . . . . . . . . . . . . . . . . . . . . . . . . . $179.00
External power inputs
Mounting tab
Input status indicators
Mode switch
Communication ports
Output status indicators
Mode status indicators Communication status indicators Removable terminal block
External power inputs
Discrete output terminals
Discrete input terminals
Discrete output terminals
Option module slot
Hardware features diagrams Removable terminal block
Option module slots
Mode status indicators
Output status indicators Input status indicators
Communication status indicators
Mode switch
Discrete input terminals www.automationdirect.com
Removable terminal block
Communication ports
Mounting tab
DL05 / DL06 PLCs tDL5-4
Page 4
For the latest prices, please check AutomationDirect.com.
Product Dimensions and Installation It is important to understand the installation requirements for your DL05 or DL06 system. Your knowledge of these requirements will help ensure that your system operates within its environmental and electrical limits.
Note: here is a minimum clearance requirement of 2” (51mm) between the panel door (or any devices mounted in the panel door) and the nearest DL05 component.
Plan for safety This catalog should never be used as a replacement for the user manual. You can purchase, download free, or view online the user manuals for these products. The D0-USER-M is the publication for the DL05 PLCs, and the D0-06USER-M is the publication for the DL06 PLCs. The D0-OPTIONS-M is the user manual for the option modules. These user manuals contain important safety information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Temperature probe
2" 50mm min
Power source 2" 50mm min 2" 50mm min
Panel ground terminal Bus b ar
Panel
Star washers
Earth ground
Ground braid copper lugs
Star washers
Panel or single point ground
See the Enclosure section to find an enclosure that fits your application
Temperature probe
1.5" 38mm min
Environmental Specifications for DL05 and DL06
Power source 1.5" 38mm min
Ambient Operating Temperature
Panel ground terminal Bus b ar
Earth ground
Note: is a minimum clearance requirement of 1.5” (38mm) between the panel door (or any devices mounted in the panel door) and the nearest DL06 component.
tDL5-5
DL05 / DL06 PLCs
Storage Temperature
1.5" 38mm min
-4º F-158ºF (-20ºC to 70ºC) 32ºF-131ºF (0º to 55ºC)
Ambient Humidity
5 to 95% relative humidity (non-condensing)
Vibration Resistance
MIL STD 810C Method 514.2
Shock Resistance
MIL STD 810C Method 516.2
Noise Immunity
NEMA (ICS3-304)
Atmosphere
No corrosive gases
1-800-633-0405
Page 5
For the latest prices, please check AutomationDirect.com.
Product Dimensions and Installation Unit dimensions and mounting orientation DL05 and DL06 PLCs must be mounted properly to ensure ample airflow for cooling purposes. It is important to follow the unit orientation requirements and to verify that the PLC’s dimensions are compatible with your application. Notice particularly the grounding requirements and the recommended cabinet clearances. Mounting orientation
Mounting orientation www.automationdirect.com
DL05 / DL06 PLCs tDL5-6
Page 6
For the latest prices, please check AutomationDirect.com.
Choosing the I/O Type Analog I/O
DL06 Base Unit I/O Table Inputs
Outputs
Part Number I/O Type/ Sink or Voltage I/O Type/ Sink or Voltage/Current Commons source Ranges Commons Source Ratings D0-06AA
AC/5
N/A
90–120 VAC AC/4
D0-06AR
AC/5
N/A
90–120 VAC Relay/4
D0-06DA
DC/5
Sink or 12–24 VDC AC/4 source
D0-06DD1
DC/5
Sink or 12–24 VDC DC/4 source
D0-06DD2
DC/5
Sink or 12–24 VDC DC/4 source
D0-06DR
DC/5
Sink or 12–24 VDC Relay/4 source
Price
17–240 VAC, 0.5 A $314.00 50/60 Hz 6–27 VDC, 2A N/A $293.00 6–240 VAC, 2A 17–240 VAC, 0.5 A N/A $293.00 50–60 Hz 6–27 VDC, 0.5 A (Y0-Y1) Sink 6–27 VDC, 1.0 A (Y2$251.00 Y17)* 12–24 VDC, 0.5 A (Y0-Y1) Source 12–24 VDC, 1.0 A (Y2$251.00 Y17) 6–27 VDC, 2A N/A $272.00 6–240 VAC, 2A 6–27 VDC, 0.5 A (Y0-Y1) Sink 6–27 VDC, 1.0 A (Y2$251.00 Y17)* 12–24 VDC, 0.5 A (Y0-Y1) Source 12–24 VDC, 1.0 A (Y2$251.00 Y17) 6–27 VDC, 2A N/A $272.00 6–240 VAC, 2A N/A
D0-06DD1-D DC/5
Sink or 12–24 VDC DC/4 source
D0-06DD2-D DC/5
Sink or 12–24 VDC DC/4 source
D0-06DR-D DC/5
Sink or 12–24 VDC Relay/4 source
* outputs must be derated to 0.6 A for EN61131-2 compliance.
Discrete I/O Option Moduless Inputs Outputs Part Number I/O Type/ Sink or Voltage I/O Type/ Sink or Number/ Number/ Commons source Ranges Commons Source
Price Voltage/Current Ratings
By using option modules, you can add analog inputs or outputs to your DL05 or DL06 PLC. The table below shows the input and output types at a glance. Detailed specifications are provided later in this section.
Analog I/O Option Modules Inputs Part Number
Outputs
No. Input Type No.
Output Type
Price
F0-04AD-1
4
0-20 mA or 0 4-20 mA
N/A
$83.00
F0-04AD-2
4
0-5 VDC or 0 0-10 VDC
N/A
$120.00
F0-08ADH-1
8
0-20 mA 0
N/A
$134.00
F0-08ADH-2
8
0-5 VDC or 0 0-10 VDC
N/A
$144.00
F0-04DAH-1
0
N/A
4
4-20 mA $144.00
F0-08DAH-1
0
N/A
8
4-20 mA $197.00
F0-04DAH-2
0
N/A
4
0-10 VDC $140.00
F0-08DAH-2
0
N/A
8
0-10 VDC $186.00
F0-4AD2DA-1 4
0-20 mA or 2 4-20 mA
0-20 mA or $192.00 4-20 mA
F0-2AD2DA-2 2
0-5 VDC or 2 0-10 VDC
0-5 VDC or $155.00 0-10 VDC
0-5 VDC or 2 0-10 VDC
0-5 VDC or $218.00 0-10 VDC
12–24 VDC
Relay/3/1
N/A
6–27 VDC, 1A 6–240 VAC, 1A
$64.00
DC/4/2
Sink or source Sink or source
12–24 VDC
DC/4/2
Sink
6–27 VDC, 0.3 A
$64.00
D0-08TR
N/A
N/A
N/A
Relay/8/2
N/A
6–27 VDC, 1A 6–240 VAC, 1A
$64.00
D0-10ND3
DC/10/2
12–24 VDC
N/A
N/A
N/A
$54.00
F0-4AD2DA-2 4
D0-10ND3F
DC/10/2
Sink or source Sink or source
12–24 VDC
N/A
N/A
N/A
$62.00
F0-04RTD
4
RTD
0
N/A
$207.00
D0-10TD1
N/A
N/A
N/A
DC/10/2
Sink
6–27 VDC, 0.3 A
$63.00
F0-04THM*
4
0
N/A
$207.00
D0-10TD2
N/A
N/A
N/A
DC/10/2
Source
12–24 VDC, 0.3 A
$63.00
Thermocouple / Voltage
D0-16ND3
DC/16/4
Sink or source
20–28 VDC
N/A
N/A
N/A
$58.00
D0-16TD1
N/A
N/A
N/A
DC/16/2
Sink
6–27 VDC, 0.1A
$64.00
D0-16TD2
N/A
N/A
N/A
DC/16/2
Source
12–24 VDC, 0.1A
$64.00
F0-04TRS
N/A
N/A
N/A
Relay/4/4
N/A
5–30 VDC, 3A 5–125 VAC, 3A
$41.00
F0-08NA-1
AC/8/2
N/A
80–132 VAC 90–150 VDC
N/A
N/A
N/A
$50.00
D0-07CDR
DC/4/1
D0-08CDD1
F0-08SIM
8-pt. Input simulator
$37.00
Communications and Specialty Option Modules Part Number H0-ECOM100 D0-DEVNETS H0-CTRIO H0-CTRIO2 H0-PSCM D0-DCM F0-CP128
Description Ethernet Communications Module 10/100 Mbit DeviceNET Slave Module High Speed Counter I/O Module Profibus Slave Communications Module Serial Communications Module ASCII CoProcessor Module www.automationdirect.com
Price $216.00 $100.00 Retired Retired $309.00 $146.00 $192.00
* module specifications page for thermocouple types and voltage input ranges supported
Power budgeting No power budgeting is necessary for the DL05. The built-in power supply is sufficient for powering the base unit, any of the option modules, the handheld programmer, and even a DV1000 operator interface. Power budgeting is necessary for the DL06. With four option module slots and an optional LCD display, it is necessary to verify that sufficient power is available for all optional devices. Power budgeting is described in detail on page 2-29 and in the DL06 User Manual. DL05 / DL06 PLCs tDL5-8