Page 1 of DL06 I/O Specifications: D0-06DD1 (DL05 / DL06 PLCs)

Spec sheet · Koyo

DL06 I/O Specifications: D0-06DD1 (DL05 / DL06 PLCs)

Spec sheet11 pagesPDF 3.6 MB

Catalog specification pages for the DL06 micro PLC D0-06DD1: I/O specifications, CPU features, installation, networking and power budgeting.

Download the PDF3.6 MB

Covers · 1 model

The models it covers

Summary

What is in it

AutomationDirect catalog pages for the DL05 / DL06 micro PLCs, opening with the D0-06DD1 I/O specifications and wiring diagrams (AC powered, DC inputs, sinking DC outputs). Further pages give CPU features at a glance, dimensions and environmental specifications, the DL06 base unit I/O table and option modules, networking and protocols, port pinouts, status indicators and mode switch, ASCII and Modbus instructions, power budgeting with a D0-06DD1 example, and the optional D0-06LCD display.

Its parts

  1. D0-06DD1
  2. Features
  3. Dimensions, Installation
  4. Networking
  5. Ports, Status Indicators, Modes
  6. ASCII, Modbus Instructions
  7. DL06 Power Budgeting
  8. DL06 LCD Display

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Catalog pages from the DL05 / DL06 PLCs section, opening with the wiring and specifications of the DL06 D0-06DD1 base unit. The other pages cover features shared by the DL05 and DL06 families: ports, networking, mode switch, ASCII and Modbus instructions, power budgeting and the D0-06LCD display. A reader can use them to wire the D0-06DD1 and check a DL06 option module power budget.

What it is
DL06 micro PLC base unit with 20 DC inputs (sink/source) and 16 DC sinking outputs, CPU and power supply in one housing p. 1, 2, 6
Power supply
100–240 VAC, 50–60 Hz, 40VA maximum p. 1
Inputs
20 inputs, sink/source, 5 isolated commons, 12–24 VDC p. 1
Outputs
16 sinking outputs, 6–27 VDC; 0.5 A per point on Y0-Y1, 1.0 A per point on Y2-Y17 p. 1, 6
Output supply
External 20–28 VDC: 150mA max. (Y0-Y1), 280 mA max. (Y2-Y17) p. 1
Input impedance
X0-X3: 1.8K @ 12–24 VDC; X4-X23: 2.8K @ 12–24 VDC p. 1
Output fuses
None (external recommended) p. 1
Port 1
6-pin RS-232, fixed 9600 baud; slave only for K-sequence, DirectNET and Modbus RTU p. 7, 8
Port 2
DL06: 15-pin HD-sub, RS-232, RS-422 or RS-485, 300 to 38,400 baud; DirectNET and Modbus master or slave p. 7, 8
Power budget
Four option slots; D0-06DD1 supplies 1500mA at 5 VDC with 300mA at 24 VDC, or 2000mA with 200mA; the base unit itself uses 600mA at 5 VDC p. 10
Programming
DirectSOFT (full versions before v6.0 need v4.0 or later for the DL06); D2-HPP handheld programmer p. 3
LCD option
D0-06LCD: 16 x 2 backlit display with seven function keys, snaps onto the face of any DL06; uses 50mA at 5 VDC p. 10, 11
Cables and adapters
D0-CBL 12 ft crossover cable (50 ft max); D0-06ADPTR low profile 15-pin adapter p. 7, 8
Ethernet option
H0-ECOM100 100Base-T module, Modbus TCP p. 7

What this sheet walks you through

  • Wiring the D0-06DD1 power, inputs and outputs p. 1
  • Mounting and panel clearances for the DL05 and DL06 p. 4, 5
  • Networking the PLC point-to-point or multi-drop p. 7
  • Port pin-outs, status indicators and mode switch positions p. 8
  • Using ASCII and Modbus RTU instructions on port 2 p. 9
  • Calculating a DL06 power budget with option modules p. 10
  • Installing and using the D0-06LCD display p. 11

Good to know

  • Outputs Y2-Y17 must be derated to 0.6 A for EN61131-2 compliance. p. 1
  • On the DL06, RS-485 on port 2 is for Modbus or ASCII only. p. 7
  • The DL06 needs at least 1.5 in (38 mm) between the panel door and the nearest component. p. 4
  • The D2-HPP handheld cannot configure the DL06 LCD, and power must be off to fit or remove the LCD. p. 11
  • The 280mA at 24 VDC applies only if auxiliary 24VDC power is connected to the V+ terminal. p. 10

Questions this sheet answers

What power does the D0-06DD1 need?

100–240 VAC at 50–60 Hz, 40VA maximum. The outputs also need an external 20–28 VDC supply. p. 1

How many inputs and outputs does the D0-06DD1 have?

20 DC inputs (sink/source) and 16 sinking DC outputs. p. 1, 6

What cable connects a DL06 to a PC or panel?

The optional D0-CBL 12 ft crossover cable, for point-to-point links up to 50 ft (15 m). p. 7

Can the D2-HPP handheld set up the D0-06LCD?

No. The LCD is configured with one ladder instruction in DirectSOFT version 4.0 or later. p. 11

How many option modules does the DL06 take?

It has four option module slots, and a power budget check is needed for the modules chosen. p. 10

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. D0-06DD11
  2. Features2
  3. Dimensions, Installation4
  4. Networking7
  5. Ports, Status Indicators, Modes8
  6. ASCII, Modbus Instructions9
  7. DL06 Power Budgeting10
  8. DL06 LCD Display11

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Pages 7 to 117-11

The file

Size and text

PublisherAutomationDirect
Pages11
PDF3.6 MB
TextText from the PDF itself.