Spec sheet · AutomationDirect
AutomationDirect T1K-01DC, Konnect-It T1K-01DC and Koyo T1K-01DC Spec Sheet
Spec sheet2 pagesPDF 684 KB
Both pages are below, each with its text.
Covers · 3 models
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A two-page catalog extract on Terminator I/O power supplies: the specifications of the T1K-01DC DC supply beside the T1K-01AC AC supply, the 5VDC and 24VDC power each Terminator I/O module draws, and a power budget example. The second page gives mounting guidance and the Terminator I/O environmental specifications.
- Device
- DC power supply for Terminator I/O; powers the network interface and I/O modules to its right p. 1
- Input voltage
- 12/24 VDC p. 1
- Maximum power
- 30 W p. 1
- Max inrush
- 10 A p. 1
- 5VDC output
- 5.25 VDC, 2000 mA max, 5% max ripple p. 1
- 24VDC output
- None (listed as N/A) p. 1
- Voltage withstand
- 1 min. @ 1500 VAC between primary, secondary and field ground p. 1
- Fuse
- 1 primary fuse, not replaceable p. 1
- Position
- Always to the left of the modules it supplies p. 1
- Humidity
- 5% to 95%, non-condensing (Terminator I/O system) p. 2
What this sheet walks you through
- Calculating the power budget for a Terminator I/O power supply p. 1
- Adding more power supplies to a Terminator I/O system p. 1
- Looking up the 5VDC and 24VDC current each Terminator I/O module draws p. 1
- Unit dimensions and mounting orientation p. 2
Good to know
- In a power budget, do not count modules to the right of an additional power supply. p. 1
- Mount Terminator I/O units horizontally and never upside-down, for cooling airflow. p. 2
- The catalog does not replace the technical data sheet that comes with the product or the T1K-INST-M manual. p. 2
Questions this sheet answers
What input voltage does the T1K-01DC take?
12/24 VDC, with a maximum power of 30 W. p. 1
How much 5V current does the T1K-01DC supply?
Up to 2000 mA at 5.25 VDC, with 5% maximum ripple. p. 1
Does the T1K-01DC provide 24VDC to the modules?
No: its 24VDC output is listed as N/A in the specification table. p. 1
Which modules does a Terminator I/O power supply feed?
Only the network interface and I/O modules to its right; a second supply closes the loop for the one to its left. p. 1
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Power Supplies and Power Requirements Power supplies
The Terminator I/O product line offers two power supply options: AC or DC. The power supplies are always positioned to the left of the modules to which they supply power. Consult the system configuration examples and the power budgeting example for more information on positioning power supplies.
Power requirements Module
5VDC 24VDCInterface ModulesDC Output ModulesT1K-01DC <--->
Input Voltage Range 110/220 VAC 12/24 VDC Input Frequency
50/60 HzN/AMaximum Power50 VA30 W
Max. Inrush Current 20 A
10 AInsulation Resistance> 10 M⏲ @ 500 VDCVoltage Withstand
1 min. @ 1500 VAC between primary, secondary and field ground
Voltage5VDC PWR5.25 VDC5.25 VDC
2000 mA max current Current Rating (see option note 2000 mA max below)
Ripple5% max.5% max.Voltage24 VDCN/A300 mA max.
24VDC Current Rating (see current option note PWR
N/Abelow)Ripple10% max.N/AModule5VDC 24VDCAnalog Input Modules3500T1H-08TDS2000T1F-08AD-17550*T1H-EBC1003000T1K-08TD1100200*T1F-08AD-27550*T1H-PBC5300T1K-16TD1200400*T1F-16AD-17550*T1K-DEVNETS25045T1K-08TD2-12000T1F-16AD-27550*T1K-RSSS2500T1K-16TD2-12000T1F-14THM6070*T1K-MODBUS3000AC Output ModulesT1F-16RTD1500T1K-08TA2500Analog Output ModulesT1K-08ND3350T1K-16TA4500T1F-08DA-17575*T1K-16ND3700T1K-08TAS300AC Input ModulesT1K-01AC <--->
Power Supply Specifications
5VDC 24VDCT1H-EBCDC Input Modules
Power supply specifications
Module0T1F-08DA-27575*Relay Output ModulesT1F-16DA-175150*75150*T1K-08NA-1350T1K-08TR3500T1F-16DA-2T1K-16NA-1700T1K-16TR7000
Combination Analog Modules
T1K-08TRS4000T1F-8AD4DA-17560*T1F-8AD4DA-27570*
Specialty Modules T1H-CTRIO
400
0
- Use either internal or external source for 24VDC
- Use either internal or external source for 24VDC
Calculating the power budget
To calculate the power budget, read the available power (current rating) from the Power Supply Specifications table and subtract the power consumed by each module to the right of the power supply. Do not include modules to the right of an additional power supply.
Adding additional power supplies
Each power supply furnishes power only to the network interface and I/O modules to its right. Inserting a second power supply closes the power loop for the power supply to the left, while also powering the modules to its right. Perform a power budget calculation for each power supply in the system.
Power Budget Example Module
5VDC24VDCT1K-01AC+2000 mA+300 mAT1H-EBC-350 mA-0 mAT1K-16ND3-70 mA-0 mAT1K-16TD2-200 mA-0 mAT1F-08AD-1-75 mA-50 mARemaining+1305 mA+250 mA
Accessories available for Terminator I/O are listed in the Terminator Field I/O section of the Price List
Fuse 1 (primary), not replaceable MVSTBW MVSTBW Replacement 2.5/4-ST-5.08 2.5/6-ST-5.08 Terminal Block BK BK (Phoenix Contact) Note: 500 mA @ 24 VDC can be achieved by lowering the 5VDC from 2000 mA to 1500 mA .
This power supply powers the network interface module and This power supply powers these three I/O the next two I/O modules modules
Volume 13e8-14Universal Field I/O1 - 80 0 - 633 - 0405
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Dimensions and Installation It is important to understand the installation requirements for your Terminator I/O system. This will ensure that the Terminator I/O products work within their environmental and electrical limits.
See the Enclosures section for an enclosure that may be suitable for your application
Plan for safety This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Unit dimensions and mounting orientation Use the following diagrams to make sure the Terminator I/O system can be installed in your application. Terminator I/O units should be mounted horizontally. To ensure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2” depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.
48mm (1.89in)
32°F to 131°F (0°C to 55°C)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance Shock Resistance Voltage Withstand (Dielectric) Insulation Resistance
MIL STD 810C, Method 514.2
5% to 95% (Non-condensing)
MIL STD 810C, Method 516.2 1500 VAC, 1 minute 500 VDC, 10
Noise Immunity Agency Approvals
UL, CE, FCC class A, NEC Class 1 Division 2
48mm (1.89in)
80mm (3.15in)
Network Interface Module
-4°F to 158°F (-20°C to 70°C)
NEMA ICS3-304 Impulse noise 1µs, 1000 V FCC class A RFI (144 MHz, 430 MHz 10 W, 10 cm)
48mm (1.89in)80mm (3.15in)Power Supply
Terminator I/O Environmental Specifications Ambient Operating Temperature Storage Temperature Ambient Humidity
89mm (3.5in)
80mm (3.15in)
Half-size I/O Module with Base
83.3mm (3.28in)
80mm (3.15in)
Full-size I/O Module with Base
System DepthVolume 13e8-12Universal Field I/O1 - 80 0 - 633 - 0405