Spec sheet · AutomationDirect
AutomationDirect T1K-08B, Konnect-It T1K-08B and Koyo T1K-08B Spec Sheet
Spec sheet2 pagesPDF 884 KB
Both pages are below, each with its text.
Covers · 3 models
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Two AutomationDirect catalog pages on Terminator I/O terminal bases, field device wiring and power options, and dimensions and installation. They list the T1K-08B together with the T1K-08B-1, T1K-16B and T1K-16B-1 bases. They give terminal wire and torque specifications, 24VDC wiring options, hot-swap cautions and the system's environmental specifications.
- Device
- Terminator I/O terminal base; the bases come in screw clamp and spring clamp versions for half-size and full-size modules p. 1
- Labeling
- Hot stamp silkscreen numbering of I/O points, commons and power terminals p. 1
- Operating temperature
- 32°F to 131°F (0°C to 55°C) p. 2
- Storage temperature
- -4°F to 158°F (-20°C to 70°C) p. 2
- Humidity
- 5% to 95%, non-condensing p. 2
- Dielectric withstand
- 1500VAC, 1 minute p. 2
- Screw-type terminals
- Screw-type bases: torque 1.77–3.54 lb·in (0.2–0.4 N·m); solid 25–12 AWG, stranded 26–12 AWG p. 1
- Spring clamp terminals
- Spring clamp bases: solid 25–14 AWG, stranded 26–14 AWG p. 1
- Bussed 24VDC
- T1K-08ND3 and T1K-16ND3 DC input modules have jumpers to select the internal 24VDC supply for 2- and 3-wire devices p. 1
- External 24VDC
- User-supplied 24VDC or T1K-01AC auxiliary 24VDC applied to one end of the terminal rows and jumpered across each base p. 1
- Vibration and shock
- MIL STD 810C, Method 514.2 (vibration) and Method 516.2 (shock) p. 2
- Noise immunity
- NEMA ICS3-304; impulse noise 1µs, 1000V p. 2
What this sheet walks you through
- Powering 2- and 3-wire DC input devices from the bussed 24VDC p. 1
- Feeding external 24VDC across the terminal bases p. 1
- Replacing modules with power on (hot swap) p. 1
- Checking unit dimensions and mounting orientation p. 2
Good to know
- Modules are not to be jumpered together into a 24VDC bus when the hot-swap feature is used. p. 1
- Before hot-swapping analog or DC output modules, each module's 24VDC and 0 VDC base terminals are wired directly to the external supply. p. 1
- Terminator I/O units mount horizontally and not upside-down, for cooling airflow. p. 2
- The catalog is not a replacement for the technical data sheet or the T1K-INST-M Installation and I/O Manual. p. 2
Questions this sheet answers
What wire sizes fit Terminator I/O terminal bases?
Screw-type bases take 25–12 AWG solid or 26–12 AWG stranded; spring clamp bases take 25–14 AWG solid or 26–14 AWG stranded. p. 1
What is the operating temperature of Terminator I/O?
32°F to 131°F (0°C to 55°C), with 5% to 95% non-condensing humidity. p. 2
Can Terminator I/O modules be replaced with power on?
Yes, the hot-swap feature allows it, but the terminals must not be touched, and power is best removed when equally convenient. p. 1
Which manual covers Terminator I/O installation?
The T1K-INST-M Installation and I/O Manual, along with the technical data sheet that comes with the products. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
For the latest prices, please check AutomationDirect.com.
Field Device Wiring and Power Options Terminal base specifications
T1K-08B $55.00
T1K-08B-1 $55.00
Terminator I/O terminal bases are available in screw clamp and spring clamp versions for both half-size and full-size modules. Hot stamp silkscreen labeling is used for numbering I/O points, commons, and all power terminals. Screw clamp, half-size
Terminal Base Specifications Terminal Type
Screw type
Recommended 1.77–3.54 lb·in (0.2–0.4 N·m) Torque Wire Gauge
Solid: 25–12 AWG Stranded: 26–12 AWG
T1K-16B $69.00
Spring clamp, half-size
T1K-16B-1 $69.00
Spring clamp N/A Solid: 25–14 AWG Stranded: 26–14 AWG Screw clamp, full-size
Spring clamp, full-size
Field device wiring options Power your DC input devices from the integrated 24VDC power supply bus. T1K-08ND3 and T1K-16ND3 DC input modules include jumpers for selecting the internal 24VDC power supply available for 2- and 3-wire field devices. Clearly labeled triple stack terminals make it easy to wire 2- and 3-wire devices ensuring clean wiring with only one wire per termination.
2 and 3-wire DC input devices using bussed 24VDC power
External user supplied 24VDC power, or auxiliary 24VDC terminals from T1K-01AC, can be easily applied directly to one end of the terminal rows and jumpered across each base in the system. This is a convenient solution for powering analog I/O and discrete DC output devices whose modules do not have direct access to the internal bussed 24VDC. If current consumption increases, simply add additional T1K-01AC power supplies into the system.
Use externally supplied 24VDC power or 24VDC auxiliary power from T1K-01AC
Do not jumper modules together to create a 24VDC bus when using the “hot swap” feature. See Note below.
Hot-swap feature The hot-swap feature allows Terminator I/O modules to be replaced while system power is on. Be careful not to touch the terminals with your hands or other conductive material to avoid the risk of personal injury or equipment damage. Always remove power if it is equally convenient to do so.
tFED-52
Universal Field I/O
Note: Before hot-swapping analog or DC output modules in a Terminator I/O system, make sure that each of the analog and DC output module’s 24VDC and 0 VDC base terminals are wired directly to the external power supply individually. If the external 24VDC and 0 VDC is jumpered from base to base in a daisy chain
fashion, and an analog or DC output module is removed from its base, the risk of disconnecting the external 24VDC and 0 VDC to the subsequent I/O modules exists.
1-800-633-0405
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
For the latest prices, please check AutomationDirect.com.
Dimensions and Installation It is important to understand the installation requirements for your Terminator I/O system. This will ensure that the Terminator I/O products work within their environmental and electrical limits.
See the Enclosures section for an enclosure that may be suitable for your application
Plan for safety This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Unit dimensions and mounting orientation Use the following diagrams to decide if the Terminator I/O system can be installed in your application. Terminator I/O units should be mounted horizontally. To ensure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2” depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.
48mm (1.89in)
tFED-48
Ambient Operating Temperature
32°F to 131°F (0°C to 55°C)
Storage Temperature
-4°F to 158°F (-20°C to 70°C)
Ambient Humidity
5% to 95% (Non-condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand (Dielectric)
1500VAC, 1 minuteInsulation Resistance500 VDC, 10 MqNoise Immunity
NEMA ICS3-304 Impulse noise 1µs, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)
Agency Approvals
UL, CE, FCC class A, NEC Class 1 Division 2
48mm (1.89in)80mm (3.15in)Power Supply
Terminator I/O Environmental Specifications
48mm (1.89in)
80mm (3.15in)
Network Interface Module
Universal Field I/O89mm (3.5in)80mm (3.15in)
Half-size I/O Module with Base
83.3mm (3.28in)
80mm (3.15in)
Full-size I/O Module with Base
System Depth
1-800-633-0405
