Page 71
54
RELAY
(RELAY FUNCTION)
The control board has one set of FORM C relay contacts at TB-16, 17, and 18 that can be programmed for the same indications as the open-collector outputs described above. The FORM C contacts at TB-16, 17, and 18 are rated 2 amps at 28 VDC or 120 Vac. Control wiring diagrams show relays in the rest state (coils NOT energized).
57
SERIAL
(SERIAL COMMUNICATIONS)
This parameter is used to activate serial communications. When using this feature, the drive can communicate with a personal computer (PC), programmable logic controller (PLC), or other external device that utilizes RS-485 serial communications for control. The serial interface may be used to read present parameter settings (uploading to the control device), write new parameter settings (downloading from the control device), monitor present drive activity, and control drive activity. The following settings are available: DISABLE
Serial communication function is disabled.
W / TIMER
Enables serial communications with a watchdog timer. If there is no serial activity (read or write) for more than 10 seconds, serial control will turn off and the drive will stop.
W / O TIMR
Enables serial communications without a watchdog timer. However, after 10 seconds of no serial activity, serial control can be turned off by issuing a STOP command from any source (keypad, terminal strip) other than the serial link.
NOTE 1: The keypad STOP button is always active, regardless of what method (LOCAL, REMOTE, or SERIAL) is being used to control the drive. The remote STOP input (TB-1) may also be active, depending on how the drive is programmed. NOTE 2: If a RESET command (Parameter 65 - PROGRAM) is issued through the serial link, this parameter will not default back to DISABLE. However, explicitly setting this parameter to DISABLE through the serial link will cut off communication with the drive. If developing an application for serial communications, refer to the RS-232/RS485 Modbus Communications Protocol Specification.
58
ADDRESS
(SERIAL ADDRESS)
This parameter is used with the serial communications feature, and is intended for use in a multiple drive network (RS-485). The serial link will support drives with addresses from 1 up to 247.
69
Page 72
61
PASSWORD
(PASSWORD NUMBER)
This feature limits access to the programmable parameters for added security. The correct password must be entered in order to change the parameters. Pressing the PROG/RUN button on the keypad will activate the PASSWORD prompt. If the correct password is entered, the PROGRAM MODE is entered and parameters can be changed. If the wrong password is entered, the drive will flash ERROR: INCORRECT and then return to the PASSWORD prompt to allow another attempt at entering the correct password. If the ENTER key is pressed while PASSWORD reads 0000, the MONITOR MODE will be entered (if Parameter 64 - MONITOR, is set to ON), which will allow the parameters to be viewed (except for PASSWORD), but not changed. NOTE 1: The factory default value is 0019. NOTE 2: If PASSWORD is set to 0000, the function is disabled. Pressing the PROG/RUN key will result in direct entry into the PROGRAM mode without having to enter a password.
63
SOFTWARE
(SOFTWARE VERSION)
This parameter displays the software code and revision number of the control board software. This information is useful when contacting the factory for programming or troubleshooting assistance. This is a “view-only” parameter, and cannot be changed.
64
MONITOR
(MONITOR MODE)
This parameter is used to enable (ON) or disable (OFF) the MONITOR MODE function. The functionality is explained below: ON
Pressing the PROG/RUN key will call up the PASSWORD prompt. If the ENTER key is pressed while the password value reads 0000, the MONITOR MODE is entered and parameters can be viewed (except for PASSWORD), but not changed.
OFF
Pressing the PROG/RUN key will call up the PASSWORD prompt. If the ENTER key is pressed while the password value reads 0000 (or any other incorrect value), it will be treated as in incorrect password and the display will flash ERROR: INCORRECT, and then return to the PASSWORD prompt to allow another attempt at entering the correct password.
70
Page 73
65
PROGRAM
(PROGRAM FACTORY DEFAULTS) WARNING!
STOP (TB-1) and EXTERNAL FAULT (TB-13D) circuitry may be disabled if parameters are reset to factory defaults! The drive must be reprogrammed after a RESET in order to insure proper operation. FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT AND/OR INJURY TO PERSONNEL! This parameter is used to reset the programmable parameters back to the factory default settings. This parameter has four possible settings: MAINTAIN
Maintain parameter settings as they are.
RESET 60
Resets parameters to factory defaults for 60 Hz base frequency.
RESET 50
Resets parameters to factory defaults for 50 Hz base frequency.
RST HIGH
Resets parameters to factory defaults for 650 Hz base frequency. This option will only appear if the drive is equipped with the High Frequency Output option.
When a factory reset is performed, the following terminals are affected: TB-1 will be disabled as a STOP input because Parameter 30 - CONTROL will default to LOCAL. TB-13A, 13B, and 13C will be disabled because Parameters 47, 48, and 49 will default to NONE. If TB-13C was set to RUN REVERSE, TB-12A will default to a momentary START contact. TB-13D will default to a normally open EXTERNAL FAULT contact because Parameter 50 - TB13D will be reset to EXT FAULT. NOTE: This parameter will display RESET 60, RESET 50 or RST HIGH until a change is made to one or more of the parameter settings. Once a parameter is changed, the display will change to MAINTAIN.
66
HISTORY
(CLEAR FAULT HISTORY)
This parameter is used to clear the previous faults in the FAULT HISTORY. When set to CLEAR and the ENTER key is pushed, the display will change to MAINTAIN, and the FAULT HISTORY will display NO FAULT for each of the eight fault histories.
71
Page 74
69
LANGUAGE
(LANGUAGE SELECTION)
The MC Series drive can support other languages with the addition of an optional LANGUAGE EEPROM chip installed in socket U11 on the control board of the drive. If the EEPROM is not present, the default language will be ENGLISH. Also, this parameter is not affected when the parameters are reset using Parameter 65 - PROGRAM. Therefore, if a language other than ENGLISH is selected, it will remain in effect after a RESET.
70
FAULT HISTORY
The FAULT HISTORY stores the previous eight fault conditions that caused the drive to trip. The information stored here is view-only, it cannot be altered. The FAULT HISTORY can be used to determine if there is a pattern, or trend, to the faults, which may indicate a problem in the system. Refer to Section 19.0 TROUBLESHOOTING for more information on faults. The FAULT HISTORY indicates the number of the fault (number 1 is the most recent fault), the fault message, and the status of the drive at the time of the fault. An example is shown below: FAULT NUMBER
FAULT MESSAGE
3 OVERLOAD
DRIVE STATUS
RUN
In the example above, the third fault log is being viewed, which is an OVERLOAD fault that occurred while the drive was in a RUN state.
72
Page 75
19.0
TROUBLESHOOTING The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please contact the factory for more information on troubleshooting faults. NOTE: The drive will not automatically restart after a PWR SAG or a CONTROL fault. Also, if an OUTPUT fault occurs below 1.5 Hz, the drive will only attempt one restart, after a four minute delay. If unsuccessful, it will then trip into FAULT LOCKOUT, which will require a manual reset. This is done to protect the drive in case of a shorted motor.
FAULT MESSAGES FAULT
DESCRIPTION
POSSIBLE CAUSES
OUTPUT
Output transistor fault: Output
Phase to ground short.
current exceeded 200% of drive
Phase to phase short.
rating.
FX or AC BOOST set too high. Bad transistor module (IPM).
LO VOLTS
Low DC Bus Voltage fault: DC
Low line voltage.
bus voltage below 60% of normal. HI VOLTS
HI TEMP
OVERLOAD
High DC Bus Voltage fault: DC
High line voltage.
bus voltage above 120% of
Overhauling load.
normal.
DECEL rate is set too fast.
Temperature fault: Internal
Ambient temperature too high.
drive temperature too high.
Fan failure (if equipped).
Current Overload fault: Output
Drive undersized for the current rating exceeded for too application.
long.
Problem with motor and/or driven equipment.
PWR TRAN
Power Transient fault: Low line voltage.
73
AC line dipped or sagged.
Page 76
FAULT MESSAGES FAULT
DESCRIPTION
PWR SAG
Power Sag fault: Control board
POSSIBLE CAUSES Erratic AC line.
voltage is below tolerance. A new control board has been
Perform a factory reset using installed that is different from the Parameter 65-PROGRAM. previous version.
This will update the software and allow the fault to be reset.
LANGUAGE
Language fault: Selected
Defective language EEPROM.
language not present
Language EEPROM (U11) removed after programming.
EXTERNAL
External fault: TB-13D is open
Check setting of Parameter or closed to TB-2, depending on
50-TB13D.
setting of Parameter 50 - TB13D. Check devices wired between TB13D and TB-2. DB ERROR
Dynamic Brake fault: DB
The DB duty cycle is too high, circuit has sensed a resistor causing the resistors to overheat.
overload. CONTROL
Control Board fault: New
Perform a factory reset using software has been installed that
Parameter 65-PROGRAM.
is different from the previous
This will update the software and version.
allow the fault to be reset.
INTERNAL
Internal fault: The micro-
Electrical noise on control wiring.
INTERN (#)
processor has sensed a problem. Defective microprocessor.
Blank Display
The power supply has shut down. Check heatsink fans (if equipped).
(drive will not run) This can be the result of clogged Clear any obstructions. If they or failed heatsink fans.
are not clogged, contact the AC Tech Service Department.
74
Page 77
20.0
USER SETTING RECORD PARAMETER MENU: USER SETTING RECORD PARAM. NUMBER
PARAMETER NAME
FACTORY DEFAULT
0
LINE VOLTS
AUTO
1
SPEED #1
20.00 Hz
2
SPEED #2
20.00 Hz
3
SPEED #3
20.00 Hz
4
SPEED #4
20.00 Hz
5
SKIP #1
.00 Hz
6
SKIP #2
.00 Hz
7
BAND WID
1.00 Hz
8
ACCEL
30.0 SEC
9
DECEL
30.0 SEC
10
MIN FRQ
.50 Hz
11
MAX FRQ
60.00 Hz
12
DC BRAKE
.0 VDC
13
DC TIME
.0 SEC
14
DYN BRAKE
OFF
16
CURRENT
180 %
17
MOTOR OL
100%
18
BASE
60.00 Hz
19
FX BOOST
(NOTE 1)
20
AC BOOST
0.00%
USER SETTING
NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.
75
Page 78
PARAMETER MENU: USER SETTING RECORD PARAM. NUMBER
PARAMETER NAME
FACTORY DEFAULT
21
SLIP CMP
.0 %
22
TORQUE
CONSTANT
23
CARRIER
2.5 kHz
25
START
NORMAL
26
STOP
COAST
27
ROTATION
FORWARD
28
AUTO/MAN
BOTH
29
MANUAL
KEYPAD
30
CONTROL
LOCAL
31
UNITS
HERTZ
32
HZ MULT
1.00
33
SPEED DP
XXXXX
34
LOAD MLT
100%
35
CONTRAST
MED
36
SLEEP TH
.00 Hz
37
SLEEP DL
30.0 SEC
39
TB5 MIN
.00 Hz
40
TB5 MAX
60.00 Hz
41
AIN FLTR
0.02 SEC
42
TB10A OUT
NONE
43
@TB10A
60.00 Hz
76
USER SETTING
Page 79
PARAMETER MENU: USER SETTING RECORD PARAM. NUMBER
PARAMETER NAME
FACTORY DEFAULT
44
TB10B OUT
NONE
45
@TB10B
125%
47
TB13A
NONE
48
TB13B
NONE
49
TB13C
NONE
50
TB13D
EXT FAULT
52
TB14 OUT
NONE
53
TB15 OUT
NONE
54
RELAY
NONE
57
SERIAL
DISABLE
58
ADDRESS
30
61
PASSWORD
0019
63
SOFTWARE
(N/A)
64
MONITOR
ON
65
PROGRAM
RESET 60
66
HISTORY
MAINTAIN
69
LANGUAGE
ENGLISH
70
FAULT HISTORY
(N/A)
77
USER SETTING
Page 80
NOTES
78