Manual · AC Tech
MC1000 Series Installation and Operation Manual
Manual82 pagesPDF 297 KB
Installation and operation manual for the AC Tech (Lenze) MC1000 Series variable frequency drives, including the M1420B.
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Installation and operation manual for the AC Tech MC1000 Series variable frequency drive, from AC Technology Corporation, a member of the Lenze Group. It gives specifications, the model designation code (which decodes models such as the M1420B), dimensions and input and output ratings, then covers AC motor and drive theory, installation, input power and power wiring, initial power up, keypad control, control wiring diagrams, programming, a full description of parameters, troubleshooting and a user setting record.
Its parts
- General
- MC1000 Specifications
- MC1000 Model Designation Code
- MC1000 Dimensions
- MC1000 Ratings
- Theory
- Installation
- Input AC Requirements
- Voltage Selection
- Power Wiring
- MC1000 Power Wiring Diagram
- Initial Power Up
- Keypad Control
- Control Wiring
- MC1000 Control Wiring Diagrams
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
The installation and operation manual for the AC Tech MC1000 Series variable frequency drives, covering the M1100, M1200, M1400 and M1500 models from 1/4 to 60 HP. It gives specifications, the model number code, ratings, power and control wiring, keypad operation, parameters and a fault table. By its code the M1420B is the 480/400 Vac, 2 HP model in a NEMA 1 enclosure.
- Model code
- M1420B: MC1000 Series drive, 480/400 Vac, 2 HP (1.5 kW), three phase input, NEMA 1 vented enclosure p. 5
- Input rating
- M1420: 3 phase, 4.7 / 4.1 A, 3.4 kVA p. 12
- Output rating
- M1420: 3.9 / 3.4 A, 2.7 kVA, 0 - 400 / 460 Vac p. 12
- Input voltage
- M1400 Series: 400 to 480 Vac (+ 10%, - 15%), 48 to 62 Hz p. 21
- Output frequency
- 0-120 Hz, optional up to 1000 Hz; sine coded PWM p. 4
- Overload capacity
- 150% for 60 seconds, 180% for 30 seconds p. 4
- Speed reference
- 0-10 VDC or 4-20 mA; 10 VDC supply for a speed pot p. 4, 39
- Outputs
- Form C relay 2 A at 28 VDC or 120 Vac; open-collector 40 mA at 30 VDC; 0-10 or 2-10 VDC analog for speed and load p. 4
- Serial port
- RS-485 serial communications on the terminal strip p. 39
- Carrier frequency
- 2.5 kHz to 14 kHz; above 8 kHz derate output current by 0.94 (10 kHz), 0.89 (12 kHz), 0.83 (14 kHz) p. 4, 10
- Input fuses
- Class CC or Class T, 200,000 AIC, sized 1.5 times input current, 10 amps minimum; Bussman KTK-R, JJN or JJS p. 20, 21
- Efficiency
- > 97% throughout speed range; power factor > 0.96 p. 4
- Environment
- Storage -20 to 70 C; humidity below 95% non-condensing; 3300 feet (1000 m) without derating p. 4
- Fault messages
- OUTPUT, LO VOLTS, HI VOLTS, HI TEMP, OVERLOAD, PWR TRAN, PWR SAG, LANGUAGE, EXTERNAL, DB ERROR, CONTROL, INTERNAL p. 75, 76
What this manual walks you through
- Reading the MC1000 model number code p. 5
- Choosing input fuses or a circuit breaker p. 20, 21
- Wiring single phase or three phase input power and the motor p. 22, 23
- Operating the drive from the keypad p. 26
- Reading the display in stop, run, fault and auxiliary modes p. 27, 28, 29, 30
- Functions of the control terminal strip p. 39
- Troubleshooting fault messages and their causes p. 75, 76
- Derating for carrier frequencies above 8 kHz p. 10
Good to know
- Disconnect power and wait three minutes before servicing; the capacitors keep their charge. p. 20
- Never connect incoming AC power to output terminals T1, T2 or T3. p. 23
- Cycling a disconnect or input contactor more than once every two minutes may damage the drive. p. 22
- Do not install power factor correction capacitors between the drive and the motor. p. 23
- The drive does not restart by itself after a PWR SAG or CONTROL fault. p. 75
Questions this manual answers
What does the M1420B model number mean?
MC1000 Series, 480/400 Vac input, 2 HP (1.5 kW), three phase, in a NEMA 1 general purpose vented enclosure. p. 5
How do I reset a fault on an MC1000 drive?
Once the fault condition has passed, press STOP; after an OUTPUT fault there is a 30 second delay first. p. 26
What causes a HI VOLTS fault?
DC bus voltage above 120% of normal, from high line voltage, an overhauling load, or a DECEL rate set too fast. p. 75
What fuses does the MC1000 need?
Class CC or Class T current-limiting fuses rated 1.5 times the drive input current, at least 10 amps, such as Bussman KTK-R, JJN or JJS. p. 20, 21
What input voltage does the M1420 accept?
M1400 Series drives take 400 to 480 Vac (+10%, -15%) at 48 to 62 Hz. p. 21
The whole text · 9 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file