The text of a manual · part 3 of 9
MC1000 Series Installation and Operation Manual, pages 21 to 30
Pages 21 to 30 of 82
The original document is the PDF (297 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AC Tech M1420B and Lenze M1420B
Page 21
Minimum voltage rating of the protection device should be 250 Vac for 240/120 Vac and 240/200 Vac rated drives, and 600 Vac for 480/400 Vac and 590/480 Vac drives. Use Class CC or Class T current-limiting fuses with low I2T values, rated at 200,000 AIC. Recommended fuses are Bussman type KTK-R, JJN, and JJS, or equivalent.
9.0
VOLTAGE SELECTION
9.1
INPUT VOLTAGE RATINGS M1100 Series drives are rated for 240/120 Vac, 50-60 Hz input. The drive will function with input voltage of 120 Vac (+ 10%, -15%) at 48 to 62 Hz when wired for 120 Vac input, or with input voltage of 240 Vac (+ 10%, - 15%), at 48 to 62 Hz, when wired for 240 Vac input. M1200 Series drives are rated for 240/200 Vac, 50-60 Hz input. The drive will function with input voltages of 200 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz. M1400 Series drives are rated for 480/400 Vac, 50-60 Hz input. The drive will function with input voltages of 400 to 480 Vac (+ 10%, - 15%), at 48 to 62 Hz. M1500 Series drives are rated for 590/480 Vac, 50-60 Hz input. The drive will function with input voltages of 480 to 590 Vac (+ 10%, - 15%), at 48 to 62 Hz.
19
Page 22
10.0
POWER WIRING WARNING! Hazard of electrical shock! Disconnect incoming power and wait three minutes before servicing the drive. Capacitors retain charge after power is removed.
Note drive input and output current ratings and check applicable electrical codes for required wire type and size, grounding requirements, overcurrent protection, and incoming power disconnect, before wiring the drive. Size conservatively to minimize voltage drop. Input fusing and a power disconnect switch or contactor MUST be wired in series with terminals L1, L2, and L3 (L1 and L2 if input is single phase). If one has not been supplied by AC Technology Corporation, a disconnect means must be wired during installation. This disconnect must be used to power down the drive when servicing, or when the drive is not to be operated for a long period of time, but should not be used to start and stop the motor. Repetitive cycling of a disconnect or input contactor (more than once every two minutes) may cause damage to the drive.
10.1
WIRING FOR SINGLE PHASE OR THREE PHASE INPUT If the drive is nameplated for 240/120 Vac single phase input, wire the input to terminals L1 and N and jumper terminals L1 to L2 for 120 Vac input voltage, or wire to terminals L1 and L2 (do not wire to N) for 240 Vac input voltage. Refer to Section 11.0 - MC1000 POWER WIRING DIAGRAM. If the drive is nameplated for three phase input only, wire the input to terminals L1, L2, and L3. All three power output wires, from terminals T1, T2, and T3 to the motor, must be kept tightly bundled and run in a separate conduit away from all other power and control wiring. It is not recommended to install contactors or disconnect switches between the drive and motor. Operating such devices while the drive is running can potentially cause damage to the drive's power components. If such a device is required, it should only be operated when the drive is in a STOP state. If there is potential for the device to be opened while the drive is running, the drive must be programmed for COAST TO STOP (see Parameter 26 - STOP), and an auxiliary contact on the device must be interlocked with the drive's run circuit. This will give the drive a stop command at the same time the device opens, and will not allow the drive to start again until the device is closed.
20
Page 23
11.0
MC1000 POWER WIRING DIAGRAM L1 L2 N
T1 T2 T3
L1 L2 L3 120 Vac SINGLE PHASE INPUT WIRING DIAGRAM
GND GND
L1 L2 N
THREE PHASE AC MOTOR
DISCONNECT MEANS (REQUIRED)
240 Vac SINGLE PHASE INPUT WIRING DIAGRAM
GND FUSED INPUT VOLTAGE
WARNING! Do not connect incoming AC power to output terminals T1, T2, or T3! Severe damage to the drive will result.
INSTALL, WIRE, AND GROUND IN ACCORDANCE WITH ALL APPLICABLE CODES. NOTES: 1. Wire the motor for the proper voltage per the output rating of the drive. Motor wires MUST be run in a separate steel conduit away from control wiring and incoming AC power wiring. 2. Do not install contactors between the drive and the motor without consulting AC Technology for more information. Failure to do so may result in drive damage. 3. Remove any existing, and do not install, power factor correction capacitors between the drive and the motor. Failure to do so will result in drive damage. 4. Use only UL and CSA listed and approved wire. 5. Minimum wire voltage ratings: 300 V for 120, 200 and 240 Vac systems, and 600 V for 400, 480, and 590 Vac systems. 6. Wire guage must be based on a minimum of 150% of the rated output current of the drive, and a minimum 75°C insulation rating. Use copper wire only. 7. Wire and ground in accordance with NEC or CEC, and all applicable local codes.
21
Page 24
12.0
INITIAL POWER UP WARNING! Hazard of electrical shock! Wait three minutes after disconnecting incoming power before servicing drive. Capacitors retain charge after power is removed.
Before attempting to operate the drive, motor, and driven equipment be sure all procedures pertaining to installation and wiring have been properly followed.
WARNING! Severe damage to the drive can result if it is operated after a long period of storage or inactivity without reforming the DC bus capacitors!
If input power has not been applied to the drive for a period of time exceeding three years (due to storage, etc), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive leakage current. This can result in premature failure of the capacitors if the drive is operated after such a long period of inactivity or storage. In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply input power to the drive for 8 hours prior to actually operating the drive/motor system. Disconnect the driven load from the motor. Verify that the drive input terminals (L1, L2, and L3) are wired to the proper input voltage per the nameplate rating of the drive.
WARNING! DO NOT connect incoming AC power to output terminals T1, T2, and T3! Do not cycle input power to the drive more than once every two minutes. Damage to the drive will result.
Energize the incoming power line. The LCD display should light and flash “TESTING” and then show the voltage and horsepower rating of the drive. The display should then show “STOP > 20.00 HZ” which indicates that the drive is in a STOP condition, and the speed setpoint is 20.00 Hz:
STOP
>
22
20.00 HZ
Page 25
If the display does not appear, remove the incoming power, wait three minutes for the bus capacitors to discharge, and verify correct installation and wiring. If the wiring is correct, re-apply incoming power and note the display for drive status. If the display still does not appear contact the factory for assistance. NOTE 1: If the drive's display is blank after power up, and it is a model equipped with heatsink fans, check to make sure the fans are operating (they should be spinning anytime power is applied to the drive). If they are not spinning, the drive's display will be blank and the drive cannot be operated. If the fans are clogged or jammed, disconnect power from the drive and remove any obstructions from the fans. Re-apply power to the drive and check the fans. If they are spinning, the drive's display should appear and the drive should operate properly. If there are no obstructions, the fan itself may be defective. Please contact the factory for assistance. If the drive powers up correctly, follow the procedure given below to check the motor rotation: 1. Use the ! key to decrease the speed setpoint to the minimum value allowed (.50 Hz if Parameter 10 - MIN FRQ has not been changed). 2. Press the START key. The drive should indicate RUN, but if the speed setpoint is .50 Hz, the motor may not rotate. Press the " key to increase the speed setpoint until the motor starts to rotate. 3. If the motor is rotating in the wrong direction, press the STOP key and remove power from the drive. Wait three minutes for the bus capacitors to discharge, and swap any two of the motor wires connected to T1, T2, and T3. NOTE 2: The drive is phase insensitive with respect to incoming line voltage. Therefore, to change the motor rotation, the phases must be swapped at the drive output terminals or at the motor.
23
Page 26
13.0
KEYPAD CONTROL The drive can be operated in a number of different ways: keypad (LOCAL), control devices wired to the terminal strip (REMOTE), serial communications (SERIAL), or a combination of each. The drive should first be operated from the keypad during initial start-up. Refer to Sections 14.0 - CONTROL WIRING, and 18.0 - DESCRIPTION OF PARAMETERS for information on remote operation.
13.1
KEYPAD FUNCTIONS (IN LOCAL MODE) START/STOP
To start the drive, press the START key. To stop the drive, press the STOP key. NOTE: The STOP key is active in both LOCAL and REMOTE modes.
SPEED SETPOINT
To increase the speed setpoint, press the " key. To decrease the speed setpoint, press the ! key. NOTE: The " and ! keys will only function if another speed reference source is not selected.
FORWARD/REVERSE
To change rotation direction, press the FWD/REV key to select the desired direction, and then press the ENTER key within three seconds to confirm the change. NOTE: Parameter 27 - ROTATION must be set to FWD & REV for this key to be active.
AUTO/MANUAL
To toggle between AUTOMATIC (terminal strip) and MANUAL (keypad) speed control, press the AUTO/MAN key to select the desired mode, and then press the ENTER key within three seconds to confirm the change. NOTE: Parameter 28 - AUTO/MAN must be set to BOTH for this key to be active. See Section 14.0 - CONTROL WIRING for information on automatic speed references.
FAULT RESET
Use the STOP key to reset a fault. If the fault condition has passed, pressing the STOP key will reset the fault and return the drive to a STOP condition. NOTE: If an OUTPUT fault occurs, there will be a 30 second delay before the fault can be cleared using the STOP key.
24
Page 27
13.2
MC1000 DISPLAY The following describes the possible display configurations for the MC1000 Series drive.
13.2.1
MC1000 DISPLAY IN STOP MODE When the drive is in the STOP mode, there are three possible displays. The first is the SPEED display, which looks like this: DRIVE STATUS
SPEED SETPOINT
STOP
> 60.00 HZ SPEED UNITS
DIRECTION (FORWARD)
NOTE: See Parameter 31 - UNITS for the SPEED UNITS display options. Pressing the ENTER key will change the display from the SPEED indication to the % LOAD indication: DRIVE STATUS
PERCENT LOAD
STOP
> 0% LOAD
DIRECTION (FORWARD)
Pressing the ENTER key again will change the display from the % LOAD indication to the VAC (motor voltage) indication: DRIVE STATUS
MOTOR VOLTAGE
STOP
>
0 VAC
DIRECTION (FORWARD)
Pressing ENTER again will change the display back to the SPEED indication.
25
Page 28
The following table shows the possible DRIVE STATUS indications that can appear on the drive display:
DRIVE STATUS TABLE DISPLAY
DESCRIPTION
STOP
Drive is in STOP mode - No output to the motor.
RUN
Drive is in RUN mode and is within + 3 Hz of the speed setpoint.
FAULT
Drive has shut down due to a FAULT condition. If the fault condition has passed, pressing the STOP key will clear the fault and return the drive to the STOP mode.
LOCK
Drive is in FAULT LOCKOUT after five unsuccessful restart attempts.
BRAKE
DC BRAKE is energized.
LIMIT
Drive is in CURRENT LIMIT due to an overloaded motor, or ACCEL is set too fast.
F DEC
Drive is in DECEL FREEZE because DECEL rate is too fast.
26
Page 29
13.2.2
MC1000 DISPLAY IN RUN MODE When the drive is in the RUN mode, the default display will look like this:
DRIVE STATUS
RUN
SPEED SETPOINT
>
60.00 HZ
DIRECTION (FORWARD)
SPEED UNITS
As in the STOP mode, the ENTER key can be used to toggle the display from SPEED to % LOAD to VAC (motor voltage):
DRIVE STATUS
RUN
PERCENT LOAD
> 85% LOAD
DIRECTION (FORWARD)
DRIVE STATUS
RUN
MOTOR VOLTAGE
>
460 VAC
DIRECTION (FORWARD)
NOTE: During acceleration and deceleration to the SPEED SETPOINT, the DRIVE STATUS will show the actual drive speed. When the SPEED SETPOINT is reached, the DRIVE STATUS will change to RUN (or STOP if the drive is decelerating to a STOP).
27
Page 30
13.2.3
MC1000 DISPLAY IN FAULT MODE When the drive trips into a fault, the display will automatically change to the FAULT display, which indicates the FAULT MESSAGE: DRIVE STATUS
FAULT MESSAGE
FAULT: OVERLOAD
In FAULT mode, the ENTER key will toggle the display between four screens: FAULT, SPEED, % LOAD and VAC. The DRIVE STATUS for these displays will be FAULT. An example is shown below of the drive in the FAULT mode displaying SPEED. DRIVE STATUS
SPEED SETPOINT
FAULT > 60.00 HZ DIRECTION (FORWARD)
SPEED UNITS
NOTE: To clear a FAULT, press the STOP key, issue a remote STOP command at TB-1, or use TB-13D (refer to Parameter 50 - TB13D).
13.2.4
MC1000 DISPLAY IN AUXILIARY MODE If the ENTER key is held down, the display will enter the auxiliary mode, which indicates the control source (LOCAL, REMOTE, or SERIAL), AUTO or MANUAL mode, and the speed reference source. When the ENTER key is released, the display will return to the previous screen. An example of the auxiliary mode display is shown below:
CONTROL SOURCE
AUTO/MAN MODE
SPEED REFERENCE SOURCE
LOCAL -- AUTO -- IDC
28