Page 31
The table below shows the possible SPEED REFERENCE SOURCE indications for the auxiliary mode display:
SPEED REFERENCE SOURCE TABLE DISPLAY
DESCRIPTION
KEY
KEYPAD - Change speed using the UP and DOWN arrow keys.
VDC
0 - 10 VDC analog input at TB-5A.
IDC
4 - 20 mA analog input at TB-5B.
SP#1
PRESET SPEED #1
SP#2
PRESET SPEED #2
SP#3
PRESET SPEED #3
SP#4
PRESET SPEED #4
JOG
JOG SPEED - In JOG mode, JOG SPEED = PRESET SPEED #2.
MOP
MOTOR OPERATED POT - Change speed using contact closures at TB-13A (DEC FREQ) and TB-13B (INC FREQ).
29
Page 32
14.0
CONTROL WIRING
14.1
GENERAL
14.1.1
KEYPAD CONTROL The drive can be controlled by the keypad or by control devices wired to the terminal strip. The drive will run from the keypad “out of the box”, requiring no connections to the terminal strip. Refer to Section 13.0 - KEYPAD CONTROL.
14.1.2
CONTROL WIRING VS. POWER WIRING External control wiring MUST be run in a separate conduit away from all other input and output power wiring. If control wiring is not kept separate from power wiring, electrical noise may be generated on the control wiring that will cause erratic drive behavior. Use twisted wires or shielded cable grounded at the drive chassis ONLY. Recommended control wire is Belden 8760 (2-wire) or 8770 (3wire), or equivalent. Torque the control terminals to 2 lb-in (0.2 Nm). Be careful not to overtorque the control terminals, as this will cause damage to the terminal strip. This is not covered under warranty and can only be repaired by replacing the control board.
14.1.3
TB-2: CIRCUIT COMMON The TB-2 terminals are used as circuit common for the start/stop, forward/reverse, input select, local/remote, analog input, and analog output functions. There are three TB-2 terminals available on the terminal strip, and they are all internally connected to each other on the main control board. If necessary TB-2 may be connected to chassis ground. NOTE: TB-2 MUST be connected to chassis ground when using serial communications.
14.1.4
SURGE SUPPRESSION ON RELAYS Current and voltage surges and spikes in the coils of contactors, relays, solenoids, etc, near or connected to the drive, can cause erratic drive operation. Therefore, a snubber circuit should be used on coils associated with the drive. For AC coils, snubbers should consist of a resistor and a capacitor in series across the coil. For DC coils, a free-wheeling or flyback diode should be placed across the coil. Snubbers are typically available from the manufacturer of the device.
30
Page 33
14.2
START/STOP AND SPEED CONTROL
14.2.1
REMOTE MODE SELECTION The REMOTE mode can be selected by one of two methods: 1. Program Parameter 30 - CONTROL to REMOTE, or: 2. Program CONTROL to BOTH, set the TB-13A or TB-13C function (see Parameter 47 or 49) to LOCAL SELECT, and DO NOT make a contact closure between TB-13A or TB-13C and TB-2 (making the contact closure will select LOCAL mode).
WARNING! If CONTROL is set to LOCAL, TB-1 is disabled and CANNOT be used as a STOP switch! Incorrect use of TB-1 may result in damage to equipment and/or injury to personnel! See Parameter 30 - CONTROL.
WARNING! STOP (TB-1) and EXTERNAL FAULT (TB-13D) circuitry may be disabled if parameters are reset to factory defaults! The drive must be reprogrammed after a RESET in order to insure proper operation (see Parameter 65 - PROGRAM). FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT AND/OR INJURY TO PERSONNEL!
14.2.2
TWO-WIRE START/STOP CONTROL A two-wire start/stop circuit can be accomplished by one of three methods on the MC Series drive. Follow the appropriate procedure listed below: FORWARD ROTATION ONLY 1.
Select REMOTE mode (see above).
2.
Connect a jumper between TB-12A and TB-2 to provide a permanent START command to the drive.
3.
Wire a normally open maintained contact between TB-1 and TB-2. Closing this contact will RUN the drive and opening this contact will STOP the drive.
31
Page 34
FORWARD and REVERSE ROTATION
14.2.3
1.
Select REMOTE mode (see above).
2.
Program Parameter 27 - ROTATION to FWD & REV to allow rotation in both directions.
3.
Program Parameter 49 - TB13C to START REVERSE. This will force TB12A to act as START FORWARD.
4.
Select the desired rotation by closing the appropriate terminal (TB-12A for forward, or TB-13C for reverse) to TB-2. This can be done with a toggle switch or equivalent circuit.
5.
Wire a normally open maintained contact between TB-1 and TB-2. Close this contact to RUN the drive, and open this contact to STOP the drive.
ALTERNATE TWO-WIRE START/STOP CONTROL METHOD WARNING! This method requires TB-13C to be set for RUN REVERSE, which will disable TB-1 as a STOP switch! Incorrect use of TB-1 may result in damage to equipment and/or injury to personnel! Refer to Parameter 49 - TB13C.
FORWARD ROTATION ONLY 1.
Select REMOTE mode (see above).
2.
Program Parameter 27 - ROTATION to FWD & REV.
3.
Program Parameter 49 - TB13C to RUN REVERSE. This will force TB12A to act as RUN FORWARD.
4.
Wire a normally open maintained contact between TB-12A and TB-2. Close this contact to RUN the drive in FORWARD, and open this contact to STOP the drive.
FORWARD and REVERSE ROTATION with TWO RUN CONTACTS 1.
Follow 1-4 above and also wire a normally open maintained contact between TB-13C and TB-2. Close this contact to RUN the drive in REVERSE, and open this contact to STOP the drive.
32
Page 35
FORWARD and REVERSE ROTATION with ONE RUN CONTACT 1.
14.2.4
Follow 1-3 above and wire a normally open maintained contact between TB-2 and the common of a single-pole, double-throw toggle switch. Wire the poles of the toggle switch to TB-12A and TB-13C. Select the desired rotation with the toggle switch. Close the maintained contact to RUN, and open to STOP.
THREE-WIRE START/STOP CONTROL A three-wire start/stop circuit can be accomplished by one of two methods on the MC Series drive. Follow the appropriate procedure listed below: FORWARD ROTATION ONLY 1.
Select REMOTE mode (see above).
2.
Wire a normally closed momentary STOP contact between TB-1 and TB-2. Momentarily open this contact to STOP the drive.
3.
Wire a normally open momentary START contact between TB-12A and TB2. Momentarily close this contact to START the drive.
FORWARD and REVERSE ROTATION with TWO START CONTACTS 1.
Select REMOTE mode (see above).
2.
Program Parameter 27 - ROTATION to FWD & REV.
3.
Program Parameter 49 - TB13C to START REVERSE.
4.
Wire a normally closed momentary STOP contact between TB-1 and TB-2. Momentarily open this contact to STOP the drive.
5.
Wire a normally open momentary START FORWARD contact between TB12A and TB-2. Momentarily close this contact to START the drive in FORWARD.
6.
Wire a normally open momentary START REVERSE contact between TB13C and TB-2. Momentarily close this contact to START the drive in REVERSE.
NOTE: If the drive is operating in one direction, and is given the START command for the opposite direction, the drive will decelerate to 0 Hz and then accelerate back to the speed setpoint in the opposite direction.
33
Page 36
FORWARD and REVERSE ROTATION with ONE START CONTACT 1.
14.2.5
Follow 1-4 above and wire a normally open momentary contact between TB-2 and the common of a single-pole, double-throw toggle switch. Wire the poles of the toggle switch to TB-12A and TB-13C. See the wiring diagram in Section 15.3.
SPEED REFERENCE SIGNALS The drive allows for three analog speed reference inputs: a speed potentiometer (10,000 Ohm), 0-10 VDC, or 4-20 mA.
14.2.6
SPEED POT
Connect the wiper to terminal TB-5A, and connect the high and low end leads to terminals TB-6 and TB-2, respectively.
0-10 VDC
Wire the positive to terminal TB-5A and the negative to terminal TB-2. TB-5A input impedance is 200 kilohms.
4-20 mA
Wire the positive to terminal TB-5B and the negative to terminal TB-2. TB-5B input impedance is 100 ohms.
SPEED REFERENCE SELECTION AUTO/MAN vs. LOCAL/REMOTE In the MC Series drive, AUTO/MAN refers to speed control, and LOCAL/ REMOTE refers to START/STOP control. AUTOMATIC or MANUAL speed control selection is affected by whether the drive is in LOCAL or REMOTE mode. In LOCAL mode (keypad start/stop control), AUTOMATIC and MANUAL speed control is selected using Parameter 28 - AUTO/MAN. When AUTO/MAN is set to BOTH, the AUTO/MAN button on the keypad is active and is used to toggle between MANUAL (keypad or speed pot) and AUTOMATIC (0-10 VDC, 4-20 mA, or preset speeds) speed control. When set to MANUAL, speed control is governed by Parameter 29 - MANUAL, which selects either KEYPAD or 0-10 VDC (speed pot). When set to AUTOMATIC, one of the TB-13 input selects must be set to the desired speed reference, and that terminal must be closed to TB2. The drive will then respond to the automatic speed reference. If one of the TB13 input selects is set for a speed reference, and the contact closure is not made to TB-2, speed control will remain in AUTO mode, but the drive will respond to the keypad or speed pot, depending on Parameter 29 - MANUAL. Therefore, if the Form C relay or open-collector outputs are set to indicate AUTO/MAN mode, they will still indicate AUTO mode.
34
Page 37
In REMOTE mode (terminal strip start/stop control), speed control is only selected using the TB-13 input selects. For AUTOMATIC speed control, one of the TB13 input selects must be set to the desired speed reference, and that terminal must be closed to TB-2. The drive will then respond to the automatic speed reference. If none of the TB-13 input selects are closed to TB-2, speed control will default to MANUAL mode, and the drive will respond to the keypad or speed pot, depending on Parameter 29 - MANUAL. This will cause the Form C relay or open-collector outputs to indicate MANUAL mode if set to indicate AUTO/MAN mode. 0 - 10 VDC and 4 - 20 mA INPUT SIGNALS TB-13A, TB-13B, and TB-13C can all be programmed to select 0-10 VDC or 420 mA input. PRESET SPEEDS TB-13A can be programmed to select SPEED #1, TB-13B to select SPEED #2, and TB-13C to select SPEED #3. Closing any two of these terminals to TB-2 will select SPEED #4. Refer to Parameters 1-4: SPEED #1 - #4 in Section 18.0 DESCRIPTION OF PARAMETERS. JOG The JOG function only works when the drive is in REMOTE mode, and only when the drive is in a STOP condition. TB-13B can be programmed to select either JOG FORWARD or JOG REVERSE. The jog speed is set by PRESET SPEED #2. Close TB-13B to TB-2 to JOG, and open the contact to STOP.
WARNING! When operating in JOG mode, the STOP key WILL NOT stop the drive. To stop the drive, the contact between TB-13B and TB-2 must be opened.
MOP - MOTOR OPERATED POT TB-13A and TB-13B are used for this function, which sets the speed of the drive using contacts wired to the terminal strip. Program TB-13A to select DEC FREQ, and program TB-13B to select INC FREQ. Closing TB-13A to TB-2 will activate the DEC FREQ function, and will cause the speed setpoint to decrease until the contact is opened. DEC FREQ will operate when the drive is in RUN mode or STOP mode. Closing TB-13B to TB-2 will activate the INC FREQ function, and will cause the speed setpoint to increase until the contact is opened. INC FREQ will only operate when the drive is in RUN mode.
35
Page 38
NOTE: If TB-13A, TB-13B, and TB-13C are all programmed to select speed references, and two or three of the terminals are closed to TB-2, the higher terminal has priority and will override the others. For example, if TB-13A is programmed to select 0-10VDC, and TB-13C is programmed to select PRESET SPEED #3, closing both terminals to TB-2 will cause the drive to respond to PRESET SPEED #3, because TB-13C overrides TB-13A.
14.2.7
ANALOG OUTPUT SIGNALS There are two terminals that can supply analog output signals proportional to output frequency or load. Terminal TB-10A can provide a 0-10 VDC or a 2-10 VDC signal proportional to output frequency, and TB-10B can provide the same signals proportional to load. The 2-10 VDC signals can be converted to a 4-20 mA signal using a resistor in series with the signal such that the total load resistance is 500 Ohms. See Parameters: 42 - TB10A OUT, 43 - @TB10A, 44 - TB10B OUT, and 45 - @TB10B in Section 18.0 - DESCRIPTION OF PARAMETERS. NOTE: These analog output signals cannot be used with “loop-powered” devices that derive power from a 4-20 mA signal.
14.2.8
DRIVE STATUS OUTPUT CONTACTS The control board has one Form C relay at terminals TB-16, TB-17, and TB-18. Contacts are rated 2 amps at 28 VDC or 120 Vac. There are also two open-collector outputs at terminals TB-14 and TB-15. The open-collector circuit is a current-sinking type rated at 30 VDC and 40 mA maximum. An external power supply (30 VDC max) must be used to power the open-collector outputs. The drive does not have a dedicated power supply for the open-collector outputs. The Form C relay and the open collector outputs can be programmed to indicate any of the following: RUN, FAULT, /FAULT (INVERSE FAULT), LOCK (FAULT LOCKOUT), AT SPEED, ABOVE #3, I LIMIT (CURRENT LIMIT), or AUTO/ MAN. See Parameters: 52 - TB14 OUT, 53 - TB15 OUT, and 54 - RELAY. Refer to Section 6.2.5 for a complete description of each of these status indications.
36
Page 39
15.0
MC1000 CONTROL WIRING DIAGRAMS
15.1
MC1000 TERMINAL STRIP Shown below is the terminal strip on the main control board, along with a brief description of the function of each terminal. Wiring shown above the terminal strip indicates internal wiring on the main control board.
FORM C RELAY The TB-2 terminals are internally tied together
1 2 5A 5B 6 10A 10B 2 12A 13A 13B 13C 13D 14 15 2 RXA TXB
16 17 18
RS-485 SERIAL COMMUNICATIONS
CIRCUIT COMMON OPEN-COLLECTOR OUTPUT OPEN-COLLECTOR OUTPUT
TB-13D FUNCTION SELECT
TB-13C FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13A FUNCTION SELECT
CIRCUIT COMMON
START
0-10 OR 2-10 VDC OUTPUT: LOAD
0-10 OR 2-10 VDC OUTPUT: FREQUENCY
10 VDC SUPPLY FOR SPEED POT 4-20 mA SPEED REFERENCE INPUT 0-10 VDC SPEED REFERENCE INPUT CIRCUIT COMMON STOP
NOTE: The function of terminals TB-10A, TB-10B, TB-13A, TB-13B, TB13C, TB-13D, TB-14, TB-15, TB-16, and TB-18 are dependent on the programming of certain parameters. In most cases, the name of the parameter matches the number of the terminal, allowing quick and easy programming of the terminals to suit the application. The exception is TB-16 and TB-18, which are governed by Parameter 54 - RELAY. A complete description of operating the drive in the REMOTE mode can be found in Section 14.2. The following diagrams provide a quick reference to wire the drive for the most common configurations.
37
Page 40
15.2
TWO-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintained contact (such as that from a PLC) for RUN and STOP commands. Close the contact to RUN, and open the contact to STOP. Also shown is the wiring for a 0-10 VDC or 4-20 mA speed reference signal. The TB-2 terminals are internally tied together
1 2 5A 5B 6 10A 10B 2 12A 13A 13B 13C 13D 14 15 2 RXA TXB
START REVERSE
START FORWARD
CIRCUIT COMMON
4-20 mA INPUT 0-10 VDC INPUT CIRCUIT COMMON STOP
FWD
16 17 18
0-10 VDC or 4-20 mA SELECT (see Note 3)
REV (see Note 2)
MAINTAINED RUN/STOP CONTACT
NOTES: 1. Close TB-1 to TB-2 to RUN, and open to STOP. 2. If REVERSE direction is required, ROTATION must be set to FWD&REV, and TB-13C must be set to START REVERSE (refer to Parameters: 27 ROTATION, and 49 - TB13C). 3. Program TB-13A, 13B, or 13C to select the appropriate speed reference signal that will control the drive speed (refer to Parameters 47, 48, and 49). When that TB-13 terminal is closed to TB-2, the drive will respond to the selected speed reference signal. In the diagram above, TB-13A is programmed to select either a 0-10 VDC or 4-20 mA signal. 4. If the contact closure is not made between TB-13A and TB-2 to select a speed reference, the drive will default to MANUAL speed control, which is determined by Parameter 29 - MANUAL.
38