Page 41

15.3

THREE-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentary contacts (such as pushbuttons) for START and STOP commands. Also shown is the wiring for a 0-10 VDC or 4-20 mA speed reference signal. The TB-2 terminals are internally tied together

1 2 5A 5B 6 10A 10B 2 12A 13A 13B 13C 13D 14 15 2 RXA TXB

START REVERSE

CIRCUIT COMMON

START FORWARD

4-20 mA INPUT 0-10 VDC INPUT CIRCUIT COMMON STOP

FWD

MOMENTARY STOP CONTACT

16 17 18

0-10 VDC or 4-20 mA SELECT (see Note 3)

REV (see Note 2)

MOMENTARY START CONTACT

NOTES: 1. Momentarily close TB-12A to TB-2 to START, and momentarily open TB-1 to TB-2 to STOP. 2. If REVERSE direction is required, ROTATION must be set to FWD&REV, and TB-13C must be set to START REVERSE (refer to Parameters: 27 ROTATION, and 49 - TB13C). 3. Program TB-13A, 13B, or 13C to select the appropriate speed reference signal that will control the drive speed (refer to Parameters 47, 48, and 49). When that TB-13 terminal is closed to TB-2, the drive will respond to the selected speed reference signal. In the diagram above, TB-13A is programmed to select either a 0-10 VDC or 4-20 mA signal. 4. If the contact closure is not made between TB-13A and TB-2 to select a speed reference, the drive will default to MANUAL speed control, which is determined by Parameter 29 - MANUAL.

39

Page 42

15.4

SPEED POT AND PRESET SPEED CONTROL Shown below is the wiring diagram for a control scheme that utilizes a speed pot and PRESET SPEEDS for speed control, and either a two-wire or three-wire START/STOP circuit: The TB-2 terminals are internally tied together

1 2 5A 5B 6 10A 10B 2 12A 13A 13B 13C 13D 14 15 2 RXA TXB

16 17 18

CIRCUIT COMMON

PRESET SPEED #3

PRESET SPEED #2

PRESET SPEED #1

START

CIRCUIT COMMON

10 VDC SUPPLY

0-10 VDC INPUT CIRCUIT COMMON STOP

SPEED POT (10 K)

NOTES: 1. Program the PRESET SPEEDS (Parameters 1-4) to the desired values. 2. Program TB-13A to select SPEED #1, TB-13B to select SPEED #2, and TB13C to select SPEED #3 (refer to Parameters 47, 48, and 49). 3. To select a preset speed, close the appropriate terminal to TB-2. To select SPEED #4, close any two of the preset speed terminals to TB-2. 4. Speed pot control can be selected by one of two methods. If none of the preset speeds are selected (all TB-13 terminals are open), the drive will default to speed pot control if Parameter 29 - MANUAL is set to 0-10 VDC. The speed pot can also be selected if one of the TB-13 terminals is programmed to select 0-10 VDC and that terminal is closed to TB-2. 5. If REVERSE rotation is required, TB-13C cannot be used to select SPEED #3. TB-13C must be programmed to select RUN REVERSE or START REVERSE, leaving only TB-13A and TB-13B to select preset speeds.

40

Page 43

16.0

PROGRAMMING THE MC1000 DRIVE

16.1

PROGRAMMING THE PARAMETERS The MC1000 keypad serves two purposes: operating the drive when in the LOCAL mode, and programming the parameters for particular applications. The keypad is shown below, along with the display that should appear when the drive is first powered up:

STOP

> 20.00 HZ

PROG RUN

AUTO MAN

START

ENTER

FWD REV

STOP

To program the drive, the PROGRAM mode must be entered by pressing the PROG/RUN button. If the password protection is disabled, pressing the PROG/ RUN button will result in direct entry into the PROGRAM mode. If the password protection is enabled, the PASSWORD prompt will appear when an attempt is made to enter the PROGRAM mode. The PASSWORD prompt appears as follows:

PASSWORD

0000 CURSOR

To enter the password, use the UP and DOWN arrow keys to scroll to the password value, and then press the ENTER key. NOTE: The factory default password is 0019.

41

Page 44

Once the correct password is entered, the PROGRAM mode will be entered and the first parameter will be displayed, which is Parameter 0 - LINE VOLTS. This is shown below:

PARAMETER NAME

LINE VOLTS

PARAMETER VALUE

AUTO

CURSOR

To scroll through the parameters, use the UP and DOWN arrow buttons on the keypad. When the desired parameter is found, press the ENTER key to shift the cursor from the parameter name to the parameter value. In this example, the cursor shifts from LINE VOLTS to AUTO:

PARAMETER NAME

LINE VOLTS

PARAMETER VALUE

AUTO CURSOR

The parameter value can then be changed using the UP and DOWN arrow buttons. If the parameter has a numerical value, the UP arrow will increase the value and the DOWN arrow will decrease the value. If the parameter has specific choices that can be selected, the UP and DOWN arrow keys will scroll through the list of possible settings. When the desired value or option is selected, press the ENTER key to store the new setting. If the new setting is not ENTERED, it will not take effect and the old setting will still be valid. If the PROG/RUN key is pushed while the cursor is highlighting the parameter value, the value will change back to the original setting (if it had been changed, but not ENTERED), and the cursor will shift back to the parameter name. Pressing PROG/RUN again will exit the PROGRAM mode. If the PROGRAM mode is entered again within two minutes, the last parameter that was viewed, or changed, will come up on the display. After two minutes has elapsed, the password will have to be entered again when attempting to access the PROGRAM mode.

42

Page 45

16.2

PARAMETER ACCESS USING SPEED DIAL SPEED DIAL is used to access parameters quickly using the parameter number. Once accessed, the parameter can be programmed as described in Section 16.1. SPEED DIAL is accessed by pressing the AUTO/MAN key while in the PROGRAM mode. This will activate the SPEED DIAL display as shown below:

- SPEED DIAL -

Once in SPEED DIAL, the UP and DOWN arrow keys will allow the operator to scroll through the parameter numbers. The display will continue to show SPEED DIAL while scrolling through the parameter numbers, as shown below:

#11

SPEED DIAL

When the desired parameter is reached, the SPEED DIAL display will be replaced by the parameter name:

#11

MAX FRQ

Once the desired parameter is displayed on the screen, press the ENTER key to display the parameter name and present setting. The parameter setting can now be changed by the method described in Section 16.1. Press the AUTO/MAN key to return to SPEED DIAL.

43

Page 46

17.0

PARAMETER MENU PARAMETER MENU PARAM. NUMBER

PARAMETER NAME

RANGE OF ADJUSTMENT

FACTORY DEFAULT

0

LINE VOLTS

HIGH, LOW, AUTO

AUTO

1

SPEED #1

MIN FRQ - MAX FRQ

20.00 Hz

2

SPEED #2

MIN FRQ - MAX FRQ

20.00 Hz

3

SPEED #3

MIN FRQ - MAX FRQ

20.00 Hz

4

SPEED #4

MIN FRQ - MAX FRQ

20.00 Hz

5

SKIP #1

.00 Hz - MAX FRQ

.00 Hz

6

SKIP #2

.00 Hz - MAX FRQ

.00 Hz

7

BAND WID

.00 - 10.00 Hz

1.00 Hz

8

ACCEL

(NOTE 1)

30.0 SEC

9

DECEL

(NOTE 1)

30.0 SEC

10

MIN FRQ

.00 - MAX FRQ

.50 Hz

11

MAX FRQ

MIN FRQ - 120.0 Hz (NOTE 2)

60.00 Hz

12

DC BRAKE

(NOTE 1)

.0 VDC

13

DC TIME

.0 - 999.9 SEC

.0 SEC

14

DYN BRAKE

OFF, ON

OFF

16

CURRENT

25 - 180 % (NOTE 3)

180%

17

MOTOR OL

25 - 100 %

100%

18

BASE

20.00 - 360.0 Hz (NOTE 2)

60.00 Hz

19

FX BOOST

.0 - 30.0 %

(NOTE 1)

20

AC BOOST

.0 - 20.0 %

0.00%

21

SLIP CMP

.0 - 5.0 %

0.00%

NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS. NOTE 2: MAX LIMIT IS 650 Hz ON UNITS WITH HIGH FREQUENCY SOFTWARE. NOTE 3: IF LINE VOLTS IS SET TO "LOW" (OR SET TO "AUTO" AND THE INPUT VOLTAGE IS LOW), THE RANGE IS 25 - 150%.

44

Page 47

PARAMETER MENU CONT'D PARAM. NUMBER

PARAMETER NAME

22

TORQUE

RANGE OF ADJUSTMENT CONSTANT, VARIABLE,

FACTORY DEFAULT CONSTANT

CT / NOCMP 23

CARRIER

25

START

2.5, 6, 8, 10, 12, 14 kHz NORMAL, POWER-UP,

2.5 kHz NORMAL

AUTO RE-, RE-BRAKE 26

STOP

27

ROTATION

RAMP, COAST FORWARD, REVERSE,

COAST FORWARD

FWD&REV, FWD@LOC 28

AUTO/MAN

AUTO, MANUAL, BOTH

BOTH

29

MANUAL

KEYPAD, 0-10 VDC

KEYPAD

30

CONTROL

LOCAL, REMOTE, BOTH

LOCAL

31

UNITS

HERTZ, RPM, % HZ,

HERTZ

/SEC, /MIN, /HR, GPH, NONE 32

HZ MULT

33

SPEED DP

.10 - 650.0 XXXXX, XXX.X, XX.XX,

1.00 XXXXX

X.XXX, .XXXX 34

LOAD MLT

95 - 139 %

100%

35

CONTRAST

LOW, MED, HIGH

MED

36

SLEEP TH

.00 - 360.0 Hz

.00 Hz

37

SLEEP DL

0.0 - 300.0 SEC

30.0 SEC

39

TB5 MIN

.00 - 360.0 Hz (NOTE 2)

.00 Hz

40

TB5 MAX

.00 - 360.0 Hz (NOTE 2)

60.00 Hz

41

AIN FLTR

0.01 - 10.0 SEC

0.02 SEC

42

TB10A OUT

NONE, 0-10V, 2-10V

NONE

43

@TB10A

3.00 - 360.0 HZ (NOTE 2)

60.00 Hz

44

TB10B OUT

NONE, 0-10V, 2-10V

NONE

NOTE 2: MAX LIMIT IS 650 Hz ON UNITS WITH HIGH FREQUENCY SOFTWARE.

45

Page 48

PARAMETER MENU CONT'D PARAM. NUMBER

PARAMETER NAME

RANGE OF ADJUSTMENT

FACTORY DEFAULT

45

@TB10B

10 - 200 %

125%

NONE, 0-10VDC, 4-20MA, 47

TB13A

SPEED#1, LOC SEL,

NONE

DEC FREQ NONE, 0-10VDC, 4-20MA, 48

TB13B

SPEED#2, INC FREQ,

NONE

JOG FWD, JOG REV NONE, 0-10VDC, 4-20MA, 49

TB13C

SPEED#3, LOC SEL,

NONE

RUN REV, STRT REV 50

TB13D

EXT FAULT, EXT /FAULT,

EXT FAULT

EXT CLEAR NONE, RUN, FAULT, 52 53 54

TB14 OUT TB15 OUT RELAY

/FAULT, LOCK, @ SPEED,

NONE

ABOVE#3, I LIMIT, AUT/MAN, FLWR PR, REVERSE

57

SERIAL

DISABLE, W/TIMER, W/O TIMR

DISABLE

58

ADDRESS

1 - 247

30

61

PASSWORD

0000 - 9999

0019

63

SOFTWARE

(VIEW - ONLY)

(N/A)

64

MONITOR

OFF, ON

ON

65

PROGRAM

MAINTAIN, RESET 60,

RESET 60

RESET 50 (NOTE 4) 66

HISTORY

MAINTAIN, CLEAR

MAINTAIN

69

LANGUAGE

(NOTE 1)

ENGLISH

70

FAULT HISTORY

(VIEW - ONLY)

(N/A)

NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS. NOTE 4: "RST HIGH" WILL APPEAR ON UNITS SET UP FOR HIGH FREQUENCY.

46

Page 49

18.0

DESCRIPTION OF PARAMETERS 0

LINE VOLTS

(LINE VOLTAGE)

This parameter calibrates the drive for the correct input voltage, and can be set to AUTO, HIGH, or LOW. When set to AUTO, the drive measures the DC bus voltage when power is applied and automatically calibrates itself according to the measured value (DC bus voltage is equal to input voltage multiplied by 1.4). This parameter can also be set “manually”, using the HIGH or LOW settings. For actual line voltages of 230/240 Vac (on 240/200 Vac models), 460/480 Vac (on 480/400 Vac models), or 575/590 Vac (on 590/480 Vac models), set this parameter to HIGH. Also use the HIGH setting for 240/120 Vac single-phase input models. Refer to the table below. For actual line voltages of 200/208 Vac (on 240/200 Vac models), 380/415 Vac (on 480/400 Vac models), or 460/480 Vac (on 590 Vac models), set this parameter to LOW. Refer to the table below.

INPUT LINE VOLTAGE SELECTION MODEL M1100S

M1200(S)

M1400 M1500

1-4

RATED INPUT

INPUT

ACTUAL INPUT

PARAM.

VOLTAGE

PHASE

VOLTAGE

SETTING

240 / 120 Vac

1

220 - 240 Vac

HIGH

240 / 120 Vac

1

110 - 120 Vac

HIGH

240 Vac

1

220 - 240 Vac

HIGH

240 / 200 Vac

3

220 - 240 Vac

HIGH

240 / 200 Vac

3

200 - 208 Vac

LOW

480 / 400 Vac

3

460 - 480 Vac

HIGH

480 / 400 Vac

3

380 - 415 Vac

LOW

590 / 480 Vac

3

575 - 600 Vac

HIGH

590 / 480 Vac

3

460 - 480 Vac

LOW

SPEED #1- #4

(PRESET SPEEDS #1, #2, #3, AND #4)

PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact closures between terminal TB-2 and terminals TB-13A, TB13B, and TB-13C. These terminals must be programmed as preset speed selects using Parameters 47 - 49: TB13A, TB13B, and TB13C.

47

Page 50

The preset speeds can only be set to values that are within the operating range defined by the minimum and maximum frequency (see Parameters: 10 - MIN FREQ, and 11 - MAX FREQ). The following table shows how each preset speed is selected using the TB-13 terminals. The terms OPEN and CLOSED refer to the state of the TB-13 terminal relative to TB-2.

PRESET SPEED ACTIVATION SPEED #

TB - 13A

TB - 13B

TB - 13C

1

CLOSED

OPEN

OPEN

2

OPEN

CLOSED

OPEN

3

OPEN

OPEN

CLOSED

CLOSED

CLOSED

OPEN

CLOSED

OPEN

CLOSED

OPEN

CLOSED

CLOSED

4

NOTE: SPEED #4 is selected if any two of the three TB-13 terminals are closed to TB-2.

5,6 SKIP #1 & #2 7 BAND WID

(SKIP SPEED #1 & #2) (SKIP BANDWIDTH)

These parameters are used to prevent the drive from operating continuously at critical speeds, or frequencies, that cause excessive mechanical vibration of the driven equipment. The SKIP SPEEDS (Parameters 5 and 6) and the SKIP BANDWIDTH (Parameter 7) are used to define up to two speed avoidance ranges. The SKIP SPEED settings define the starting point of the speed range that is to be avoided, and the SKIP BANDWIDTH setting defines how far the speed range extends beyond SKIP SPEED. Setting the SKIP SPEEDS to .00 Hz disables this function. Example: The critical frequency is 21 Hz, and a bandwidth of 2 Hz is desired. Therefore, set SKIP #1 to 20 Hz and set SKIP BANDWIDTH to 2 Hz. This results in a speed range from 20 Hz to 22 Hz that the drive will not operate within continuously. If the drive were operating at 25 Hz and then commanded to operate at a speed within the range of avoidance, the drive would decelerate to 22 Hz and remain at that frequency until commanded to 20 Hz or below. The drive would then decelerate through the range of avoidance to the new frequency. Likewise, if the drive were operating at 18 Hz, and then commanded to operate at a speed within the range of avoidance, the drive would accelerate to 20 Hz and remain at that frequency until commanded to a speed of 22 Hz or above. The drive would then accelerate through the range of avoidance to the new frequency.

48