AC Tech Variable Speed AC Motor Drives SCN Series Installation and Operation Manual, pages 41 to 47

Pages 41 to 47 of 47

The original document is the PDF (269 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AC Tech SN103S and Lenze SN103S

Page 41

The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please contact the factory for more information on troubleshooting faults.

FAULT MESSAGES FAULT

DESCRIPTION & POSSIBLE CAUSES

AF

High Temperature Fault: Ambient temperature is too high; Cooling fan has failed (if equipped).

CF

Control Fault: A blank EPM, or an EPM with corrupted data has been installed. Perform a factory reset using Parameter 48 - PROGRAM SELECTION. Incompatibility Fault: An EPM with an incompatible parameter version has been installed. Either remove the EPM or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the parameter version of the drive. Dynamic Braking Fault: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors. External Fault: One of the TB-13 terminals is set as an External Fault input and that terminal is open with respect to TB-11. Refer to Parameters 10, 11 and 12.

cF dF EF GF

Data Fault: User data and OEM defaults in the EPM are corrupted.

HF

High DC Bus Voltage Fault: Line voltage is too high; Deceleration rate is too fast; Overhauling load. For fast deceleration or overhauling loads, dynamic braking may be required. Remote Keypad Fault: The communication between the SCN drive and the optional Remote Keypad has been lost. Check for proper wiring and/or noise.

JF LF

Low DC Bus Voltage Fault: Line voltage is too low.

OF

Output Transistor Fault: Phase to phase or phase to ground short circuit on the output; Boost settings are too high; Acceleration rate is too fast; Failed output transistor. Current Overload Fault: VFD is undersized for the application; Mechanical problem with the driven equipment.

PF SF

Single-phase Fault: Single-phase input power has been applied to a three-phase drive.

UF

Start Fault: Start command was present when the drive was powered up. Must wait 2 seconds after power-up to apply Start command if START METHOD is set to NORMAL.

F1

EPM Fault: The EPM is missing or damaged.

F2 - F9, Fo

Internal Faults: The control board has sensed a problem - consult factory.

To clear a fault, issue a STOP command on the terminal strip. The fault will only clear if the condition that caused the fault has passed. For example, if the drive trips on a LOW DC BUS VOLTAGE FAULT (LF) due to low input voltage, the fault cannot be cleared until the input voltage returns to a normal level. If the drive is programmed to automatically restart after a fault (see Parameter 03), the drive will attempt to restart three times after a fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or Fo faults). If all three restart attempts are unsuccessful, the drive will trip into FAULT LOCKOUT (LC), which requires a manual reset as described above. 38

Page 42

17.0

SCN DISPLAY MESSAGES

The following describes the various displays and messages that can appear on the SCN drive. 17.1

SPEED DISPLAY

If the drive is in a STOP state (indicated by "- -" on the display), and the keypad speed command is changed, the display will show the commanded speed, and the upper left decimal point will turn on solid. About five seconds after a change is made, the display will begin to alternate between the commanded speed value and the "- -" display. If the Mode button is pressed, the display will stop alternating and show the "- -" display only. When the drive is given a START command, the displayed speed will start increasing as the drive accelerates up to the commanded speed. If the keypad speed command is changed while the drive is running, the display will show the commanded speed rather than the actual speed, until the actual speed reaches the commanded speed. If the keypad speed command is changed faster than the drive can accelerate or decelerate, the upper left decimal point will blink to indicate that the the drive is accelerating or decelerating to the new speed. Once the actual speed reaches the commanded speed, the upper left decimal point will turn on solid for 5 seconds and then turn off to indicate that the commanded speed has been reached, and that the display is now showing the actual speed. 17.2

CHANGING THE SPEED REFERENCE SOURCE

When the speed source is changed while the drive is running, the display will flash the message for the new speed source to indicate that the new speed source is active. Also, if the drive is being controlled from a speed source other than the ! and " buttons (speed pot, preset speed, etc), and one of the ! or " buttons is pressed, the display will flash the present speed source message to indicate that the ! and " buttons are invalid. Example 1: The drive is running and the present speed source is the keypad. TB-13A is programmed to select a speed pot signal as the speed source. When TB-13A is closed to TB-11, the display will flash “EU” to indicate that the speed source has changed to the speed pot signal. If the contact between TB-13A and TB-11 is opened, the display will flash “CP” to indicate that the speed source has changed back to the ! and " buttons. Example 2: The speed source is a speed pot. If the ! or " button is pushed, the display will flash “EU” to indicate that the present speed source is the speed pot and that the ! and " buttons are invalid. Refer to the table below for the possible speed reference source displays:

39

Page 43

SPEED SOURCE DISPLAYS DISPLAY

DESCRIPTION

CP

CONTROL PAD: Speed is set using the ! and " buttons on the front of the drive.

EU

EXTERNAL VOLTAGE: Speed is controlled by a speed pot.

JG

JOG: The drive is in Jog mode, and the speed is set by Preset Speed #2 (Parameter 32).

OP

MOP (Motor Operated Pot): Contacts wired to two of the TB-13 terminals are used to increase and decrease the drive speed. See Parameters 10, 11, and 12.

P1 - P7

PRESET SPEEDS #1-7: Speed is set by the indicated Preset Speed (Parameters 31-37).

NOTE: The speed source displays will flash when the speed reference source is changed while the drive is running to indicate that the new speed reference source is active.

17.3

STATUS AND WARNING MESSAGES

STATUS AND WARNING MESSAGES DISPLAY

DESCRIPTION br

DC BRAKING: The DC braking circuit is activated.

cE

COMPATIBLE EPM: An EPM with a previous parameter version has been installed, and an attempt was made to change the programming. The drive will operate with the EPM installed, but the parameters cannot be changed. Refer to setting 06 (TRANSLATE) in Parameter 48.

CL

CURRENT LIMIT: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current. If the drive remains in CURRENT LIMIT for too long, it can trip into a CURRENT OVERLOAD fault (PF).

Er GE

ERROR: Invalid data has been entered or an invalid command was attempted. "GE" will be displayed if an attempt is made to change the OEM default settings when the drive is operating in the OEM mode (see Parameter 48).

GF

If "GF" is displayed when a RESET OEM is attempted, it indicates that the OEM defaults in the EPM are corrupted. If "GF" is displayed upon power-up, it indicates that the OEM defaults and the user settings in the EPM are corrupted. Refer to Section 13.2.

LC SP

FAULT LOCKOUT: The drive has failed three restart attempts and now requires a manual reset. START PENDING: "SP" blinks during the interval between restart attempts. DECEL OVERRIDE (both upper decimal points blinking): The drive has stopped decelerating to avoid tripping into an HF fault due to regenerative energy from the motor.

40

Page 44

18.0

USER SETTING RECORD

NO.

PARAMETER NAME

FACTORY DEFAULT

01

LINE VOLTAGE

HIGH (01)

02

CARRIER FREQUENCY

6 kHz (02)

03

START METHOD

NORMAL (01)

04

STOP METHOD

COAST (01)

05

STANDARD SPEED SOURCE

KEYPAD (01)

06

TB-14 OUTPUT

NONE (01)

10

TB-13A FUNCTION SELECT

NONE (01)

11

TB-13B FUNCTION SELECT

NONE (01)

12

TB-13C FUNCTION SELECT

NONE (01)

14

CONTROL

TERMINAL STRIP ONLY (01)

17

ROTATION

FORWARD ONLY (01)

18

TIME RANGE SELECT x1.0 (02)

19

ACCELERATION TIME

20 SEC

20

DECELERATION TIME

20 SEC

21

DC BRAKE TIME

0 SEC

22

DC BRAKE VOLTAGE

0%

23

MINIMUM FREQUENCY

0 Hz

24

MAXIMUM FREQUENCY

60 Hz

41

USER SETTING

Page 45

NO.

PARAMETER NAME

FACTORY DEFAULT

25

CURRENT LIMIT

180%

26

MOTOR OVERLOAD

100%

27

BASE FREQUENCY

60 Hz

28

FIXED BOOST

1%

29

ACCEL BOOST

0%

30

SLIP COMPENSATION

0%

31-37

PRESET SPEEDS

0 Hz

38

SKIP BANDWIDTH

0 Hz

42

ACCEL / DECEL #2

20 SEC

44

PASSWORD

25

47

CLEAR HISTORY

MAINTAIN (01)

48

PROGRAM SELECTION

USER SETTINGS (01)

50

FAULT HISTORY

(N/A)

51

SOFTWARE CODE

(N/A)

52

DC BUS VOLTAGE

(N/A)

53

MOTOR VOLTAGE

(N/A)

54

LOAD

(N/A)

55

SPEED POT INPUT

(N/A)

57

TB STRIP STATUS

(N/A)

58

KEYPAD STATUS

(N/A)

42

USER SETTING

Page 46

AC Tech Variable Speed AC Motor Drives

EC DECLARATION OF CONFORMITY In accordance with EN45014:1998

Applied Council Directive(s): EMC Directive 89/336/EEC, as amended: 92/31/EEC and Low Voltage Directive 73/23/EEC, as amended: 93/68/EEC

We, Manufacturer: AC Technology Corporation 660 Douglas Street Uxbridge, MA 01569 U.S.A.

Authorized Representative: AC Technology Europe Unit 8, Denington Industrial Estate 16 Everitt Close Wellingborough, Northants. NN8.2QF U.K.

declare under our sole responsibility that the products to which this Declaration relates, are in conformity with the relevant provisions of the following standards, provided that installations are carried out in accordance with manufacturer’s instructions.

PRODUCTS RELEATED TO DECLARATION SCN Series AC Variable Frequency Motor Drives Models: SN103S SN115S SN210S SN230S SN215 SN105S SN203S SN215S SN205 SN220 SN110S SN205S SN220S SN210 SN230

RELEVANT EUROPEAN STANDARDS EN 50081-2* Electromagnetic compatibility – Generic emission standard – Part 2: Industrial environment EN 50082-2* Electromagnetic compatibility – Generic immunity standard – Part 2: Industrial environment EN 50178:1998 Electronic equipment for use in power installations * with suitable line filters that are properly installed.

YEAR OF CE Marking (Low Voltage Directive): 2000 Signature: Jim Reinwald, Compliance Manager Date:

19 April 2000

Page 47

AC Technology Corporation 660 Douglas Street, Uxbridge MA 01569 Sales: 800-217-9100, FAX: 508-278-7873 Service: 508-278-9100 ext 125, FAX: 508-278-6620 www.actechdrives.com