Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

Spec sheet · Leuze

AS-Interface Safety at Work: Safety Monitors, ASM1, ASM1E

Spec sheet7 pagesPDF 416 KB

Catalog pages for the Leuze ASM1 and ASM1E AS-i Safety Monitors: functions, ordering data, wiring example and technical data.

Download the PDF416 KB

Names · 1 model

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Leuze catalog pages for the ASM1 and ASM1E AS-Interface Safety at Work safety monitors, which watch the safety-related AS-i bus participants (light curtains, safety switches, control devices) and drive one or two release circuits. The pages compare the ASM1, ASM1E and ASM1E-m (muting) variants, list article numbers, show an ASM1 connection example with a light curtain, and give technical data, safety ratings and dimensions.

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Leuze catalog pages (2010) for the ASM1 and ASM1E AS-i Safety Monitors, covering the versions ASM1/1, ASM1/2, ASM1E/1, ASM1E/2, ASM1E-m/1 and ASM1E-m/2. They give the functions of each version, article numbers, a connection example, technical data and dimensions. A reader can use them to identify a monitor, compare versions and wire it.

What it is
AS-i Safety Monitor that watches the safety-related AS-Interface bus participants assigned to it and switches release circuits p. 1
Versions
ASM1/1 (580020) and ASM1E/1 (580024): 1 release circuit; ASM1/2 (580021) and ASM1E/2 (580025): 2 release circuits; Muting versions ASM1E-m/1 (580055), ASM1E-m/2 (580056) p. 4
Supply
24 V DC, ±15%; 150 mA (ASM1/1, ASM1E/1), 200 mA (ASM1/2, ASM1E/2) p. 2, 6
Safety outputs
Up to 2 potential-free safety-related switching outputs (OSSDs); max. contact load 1 A with 24 V DC, 3 A with 230 V AC p. 7
AS-i network
Up to 31 safe AS-i slaves; 4 Safety Monitors per AS-Interface network p. 2, 6
Configuration interface
RS 232 at 9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits; asimon configuration and diagnostics software p. 2, 6
Function modules
ASM1/1 and ASM1/2: 32; ASM1E/1 and ASM1E/2: 48 p. 3
Dimensions
45 mm x 105 mm x 120 mm (W x H x D) p. 2, 6
Operating temperature
-20...+60°C p. 2
Housing and mounting
Polyamide PA 66 housing; snap-on fastening on DIN rails in accordance with EN 50022 p. 6
Inputs and signal output
Start and feedback inputs: opto-coupled, high-active, approx. 10 mA at 24 V DC; signal output: pnp transistor, 200 mA p. 7
Fuse
External, max. 4 A MT p. 7
Wire sizes
1x 0.5 to 4.0 mm2 and 2x 0.5 to 2.5 mm2 (single-wired); 2x 20 to 14 (AWG) p. 6
Safety ratings
The manual states SIL 3, PL e and Category 4 p. 2

What this sheet walks you through

  • Configuring and diagnosing the monitor from a PC over RS 232 p. 1, 2
  • Comparing the functions of the ASM1 and ASM1E versions p. 3
  • Ordering the right version by article number p. 4
  • Wiring an ASM1 with a COMPACTplus light curtain p. 5
  • Setting up Muting with the ASM1E-m versions p. 1, 2

Good to know

  • IP 20 means the unit belongs only in electrical rooms or cabinets rated at least IP 54. p. 6
  • The data sheet points to the connecting and operating instructions for further information. p. 7
  • Programmable Muting logic is available only on the ASM1E-m/1 and ASM1E-m/2. p. 2

Questions this sheet answers

What is the article number of the Leuze ASM1/2?

580021, the AS-i Safety Monitor with 2 release circuits. p. 4

What power supply does the ASM1 need?

24 V DC ±15%, drawing 150 mA (ASM1/1) or 200 mA (ASM1/2). p. 2, 6

How many safe AS-i slaves can one ASM1 monitor?

Up to 31 safe AS-i slaves can be connected. p. 2

What is the difference between the ASM1 and ASM1E?

The ASM1E has 48 configurable function modules instead of 32, plus extra logic, diagnostics and an activation/deactivation mode. p. 1, 3

How is the ASM1 configured?

From a PC through its RS 232 interface, using the asimon configuration and diagnostics software. p. 2

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 71-7

The file

Revision and size

Part no.09-01_ASM1_ASM1E
Revision2010
PublisherLeuze electronic GmbH + Co. KG
Pages7
PDF416 KB
TextText from the PDF itself.
09-01_ASM1_ASM1E