Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Liebert ACV Series AccuVar Surge Protection Technical Specification

Spec sheet · Liebert

Liebert ACV Series AccuVar Surge Protection Technical Specification

Spec sheet1 pagePDF 144 KB

The page is below, with its text.

Download the PDF144 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

One-page technical specification (SS-22033 Rev 6) for the Liebert ACV Series (Accuvar) facility-wide surge protection devices, including the AccuVar II (AII). It gives the general specifications, surge ratings and the part number scheme for voltage, source configuration, protection modes and monitoring options. A reader can use it to decode or build an AccuVar part number.

What it is
Facility-wide surge protection device, Liebert ACV Series (Accuvar) p. 1
Surge rating
ACV: 65kA per mode; ACCUVAR II (AII): 80kA per mode p. 1
Voltages
120, 208, 230, 240, 277, 346, 480 and 600 V (L-G voltage codes) p. 1
Monitoring options
R: red and green LEDs and audible alarm; RE: adds enhanced EMI/RFI filtering; RK: adds alarm relay contacts; RKE: adds both p. 1
Short circuit rating
200kAIC p. 1
Frequency range
47-63Hz p. 1
EMI/RFI noise rejection
63dB Max p. 1
Location type
Type 1 (R and RK models); Type 2 (RE and RKE models) p. 1
Enclosure
NEMA 4X p. 1
Weight
6.5 lbs (3 kgs) p. 1
Protection modes
Three digits for L-N or L-L, L-G and N-G: 1 = mode included, 0 = not; "111" = all modes p. 1
Example part number
ACV277Y111RKE: 130kA per phase, 277/480V, 3-phase wye, all modes, LEDs, audible alarm, enhanced EMI/RFI filtering, alarm relay contacts p. 1
Certifications
The manual states ANSI/UL 1449 Third Edition; UL 1283 (Type 2 locations); cUL; CE p. 1

What this sheet walks you through

  • Building an AccuVar part number from voltage, configuration, modes and options p. 1
  • Choosing a monitoring option p. 1

Good to know

  • Single-phase source configurations need a "-" in the part number. p. 1

Questions this sheet answers

What is the surge rating of the Liebert AccuVar ACV?

65kA per mode for the ACV, and 80kA per mode for the ACCUVAR II (AII). p. 1

What does RKE mean at the end of an AccuVar part number?

The standard LED and audible alarm options plus enhanced EMI/RFI filtering and alarm relay contacts. p. 1

What does the part number ACV277Y111RKE mean?

130kA per phase, 277/480V three-phase wye, all protection modes, with LEDs, audible alarm, enhanced EMI/RFI filtering and alarm relay contacts. p. 1

What enclosure does the Liebert ACV use?

A NEMA 4X enclosure; the unit weighs 6.5 lbs (3 kgs). p. 1

The file

Size and text

Pages1
PDF144 KB
TextText from the PDF itself.

Every page · 1

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Liebert ACV Series AccuVar Surge Protection Technical Specification

The text of page 1, from the PDF itself

Surge Protection For Business-Critical ContinuityTM

LiebertTM ACV Series (Accuvar) Technical Specification Facility Wide Surge Protection

General Specifications Maximum Continuous Operating Voltage Short Circuit Current Rating (SCCR) Operating Frequency Range EMI/RFI Noise Rejection Location Type Nominal Discharge Current (In) Standard Status Indication Certifications Standard Enclosure Weight Warranty UL 1449 Third Edition, Type 1 VPRs Configuration L-N L-G L-L 120S, 120Y 600 700 900 240D 1000 1200 230Y, 277Y 1000 1000 1800 346Y 1500 1500 2500 480D 1800 3000 600D 1800 4000

Model # __ __ __

Model / Surge Rating ACCUVAR ACV 65kA Per Mode ACCUVAR II AII 80kA Per Mode

__ __ __

Headquarters Surge Protection 100 Emerson Parkway Binghamton, NY 13905 P (607) 721 8840 P (800) 288 6169 F (607) 722 8713 E contactsurge@emerson.com

__ __ __

200kAIC 47-63Hz 63dB Max Type 1(R and RK models); Type 2 (RE and RKE models) 20kA LEDs, Audible Alarm ANSI/UL 1449 Third Edition; UL 1283 (Type 2 locations); cUL; CE NEMA 4X 6.5 lbs (3 kgs) 10 Years Replacement

N-G 600 900 1200

Unit ACV AII

Life Cycle Surge Testing (10kA, 20kV, IEEE Cat. C3) Per Mode Per Phase 6,000 12,000 8,000 16,000

__ __ __

Monitoring Options Standard Options – (Red & Green LED’s, R Audible Alarm with Enable/Disable Feature) Standard Options + Enhanced EMI/RFI RE Filtering Standard Options + RK Alarm Relay Contacts Standard Options + Enhanced EMI/RFI RKE Filtering, & Alarm Relay Contacts

L-G Voltage 120V 120 208V 208 230V 230 240V 240 277V 277 346V 346 480V 480 600V 600

Source Configuration 1 Phase L-N 2w + gnd (must put “-“ in part number) 1 Phase L-L 2w + gnd (must put “-“ in part number) Split Phase 3w + gnd 3 Phase Wye 4w + gnd 3 Phase Delta 3w + gnd 3 Phase Delta Hi-leg 4w+ gnd

SS-22033 Rev 6 1/10

__

120VAC 125%, all others 115%

S Y D H

Mode Required ? YES NO L-N OR L-L 1 0 L-G 1 0 N-G 1 0 Example: “111” = All Modes of Protection

Example Part Number
ACV277Y111RKE

130kA Per Phase, 277/480V, 3-Phase Wye, All Mode, LED’s, Audible Alarm with Enable/Disable feature, Enhanced EMI/RFI Filtering, Alarm Relay Contacts