Page 17

2. SYSTEM CONFIGURATION 2.

MELSEC-A

SYSTEM CONFIGURATION This chapter describes the applicable system configurations, cautions on configuring a system, and component devices of the AnSHCPU.

2.1 2.1.1

Overall Configuration AnSHCPU The figure below shows a system configuration when the AnSHCPU is used independently. (To peripheral device)

A1SHCPU

A2SHCPU (S1)

ROM cassette

ROM cassette

(A1SNMCA-8KP equipped with EPROM) (A1SNMCA-[ ]KE equipped with E2PROM)

(A2SNMCA-30KE equipped with E2PROM)

Main base (A1S3[ ]B)

Extension cable (A1SC0[ ]NB) [Building block type]

• Power supply module • Input module • Output module • Special function module

Battery (A6BAT)

• Power supply module • Input module • Output module • Special function module

Extension cable (A1SC[ ][ ]B)

Extension base

Extension base (A1S5[ ]B (S1)): Without a power supply module (A1S6[ ]B (S1)): Equipped with a power supply module

(A5[ ]B): Without a power supply module (A6[ ]B): Equipped with a power supply module

2-1

Page 18

2. SYSTEM CONFIGURATION

MELSEC-A

Memory write adapter dedicated to A1SNMCA-8KP (A6WA-28P) (To AnSHCPU) AC30R4/ AC300R4 cable

A6PHP plasma handy graphic programmer

AC03WU cable

A6WU P-ROM writer module

ROM cassette for A1SHCPU (A1SNMCA-8KP)

SW3GP-GPPAEE/ SW4GP-GPPAEE system FD

A6GPP Intelligent GPP

SW3GP-GPPAEE/ SW4GP-GPPAEE system FD

Memory write adapter dedicated to A1SNMCA-8KP (A6WA-28P)

ROM cassette for A1SHCPU (A1SNMCA-8KP)

*1 (RS-232C cable) (RS-232C converter)

RS-422

*1, *2 SW0IX-GPPAE MELSEC-MEDOC system FD

IBM PC/AT or 100 % compatible

(RS-422 cable)

AC20R4-A8PU cable

A8PUE Programming module

AC30R4-PUS cable

A7PUS Programming module

*1: Refer to SW0IX-GPPAE Software Package Operating Manual or the MELSEC-MEDOC Operating Manual for connectable cables and devices. *2: IBM is a registered trademark of the International Buisiness Machines Corporation.

POINT For applicable printers, cables, and ROM writers, see the operating manual for each peripheral device used.

2-2

Page 19

2. SYSTEM CONFIGURATION 2.1.2

MELSEC-A

A1SJHCPU The figure below shows a system configuration and peripheral device configuration when the A1SJHCPU is used independently.

(To peripheral device) Battery (A6BAT)

A1SJHCPU

Thin type I/O module (A1SJ-56

ROM cassette A1SMCA-8KP/ A1SNMCA-8KP equipped with EPROM A1SMCA- KE/ A1SNMCA- KE equipped with E2PROM

Input module (A1SX

Extension cable (A1SC

)

)

B) Output module (A1SY

Extension base (A1S5 B) : Without a power supply module (A1S6 B) : Equipped with a power supply module

)

Special function module

Power supply module (A1S6

P

Extension cable (A1SC05NB [Building block type]

Input module (AX

Extension base (A5 B) : Without a power supply module (A6 B) : Equipped with a power supply module

)

Power supply module (A6

2-3

Output module (AY

P)

)

Special function module

Fuse

Page 20

2. SYSTEM CONFIGURATION

(To A1SJHCPU)

MELSEC-A

AC30R4/ AC300R4 cable

A6PHP plasma handy graphic programmer

A6WU P-ROM writer module

AC03WU cable

EPROM write adapter (A6WA-28P)

ROM cassette (A1SNMCA-8KP, A1SMCA-8KP) A6GPP intelligent GPP

EPROM write adapter (A6WA-28P) A7PU programming module

Printer (A7NPR, A7PR, K7PR, K6PR, K6PR-K, K6PR-K-S1, GT-10, general purpose printer

AC30R2 cable

ROM cassette (A1SNMCA-8KP, A1SMCA-8KP)

Audio cassette cable (J-1)

Audio cassette recorder

A7PUS programming module AC30R4-PUS cable

AC20R4-A8PU cable

A8PUE programming module

*1 (RS-232C cable) (RS-232C converter)

RS422

*1, *2 IBM PC/AT or 100 % compatible

(RS-422 cable)

2-4

SW0IX-GPPAE MELSEC-MEDOC system FD

*1: See the SW0IX-GPPAE Software Package Operating Manual or the MELSEC-MEDOC Operating Manual for connectable cables and devices. *2: IBM is a registered trademark of the International Business Machines Corporation.

Page 21

2. SYSTEM CONFIGURATION 2.2

MELSEC-A

Cautions on Configuring a System This section describes the hardware and software that can be used with the AnSHCPU.

2.2.1

Hardware (1)

I/O module An A[ ]N or A[ ]A building-block type I/O module can be used by loading it to the A5[ ]B/A6[ ]B extension base.

(2)

Special function module (a)

An A[ ]N or A[ ]A special function module can be used by loading it to the A5[ ]B/A6[ ]B extension base.

(b)

Limits are imposed on the number of the following special function modules that can be loaded.

AD51(S3) AD51FD (S3) AJ71C24(S3/S6/S8) AJ71P41 AJ61BT11 *1

AD51H(S3) AD57G(S3) AJ71C22 AJ71UC24 AJ71E71

A1SD51S A1SJ71C24-R2(PRF/R4) A1SJ71UC24-R2(PRF/R4) A1SJ71E71-B2/B5

A1SJ61BT11 *1

Up to 2

AI61(S1)

Only 1

A1SI61 AJ71AP21(S3) AJ71AT21B AJ71BR11

AJ71AR21 AJ71LP21

A1SJ71AT21B A1SJ71AP21(S3) A1SJ71LP21

A1SJ71AR21 A1SJ71BR11

Only 1

*1

At intelligent mode

POINT When the dedicated instruction for the CC-Link is used, use the master module with ("9707 B" or later), shown right, inscribed in the DATE column of the rated plate.

CPU UNIT MODEL DATE

9707 B

MITSUBISHI ELECTRIC Function version Date of manufacture

(3)

Peripheral device (a)

Points to note when using an A6WU P-ROM writer

2-5

Page 22

2. SYSTEM CONFIGURATION 1)

MELSEC-A

When using an A1SHCPU Use an A6WU P-RPM writer module whose software version is "E" or later. [][][]()E

A6WU Label

(4)

DATE [ ] [ ] [ ] ( ) ( )

Date of manufacture

Software version Hardware version

(b)

The A6WU P-ROM writer module cannot be installed directly on the AnSHCPU (add-on installation impossible). Only handheld connection using cables is possible.

(c)

When writing to an A1SHCPU/A1SJHCPU using an A6WU series PROM writer module, SERIAL must be selected.

(d)

Among the programming modules (A7PU, A7PUS and A8PUE), only the A7PUS can be added on. The other models (A7PU and A8PUE) are available only as the handheld installation type which requires cables.

EPROM memory cassette ROM partition Partitioning the EPROM memory cassette with an A6GPP (SW4GPGPPA)/A6WU requires a memory write adapter (optional). The valid combinations of memory cassette and memory write adapter are as follows : CPU model

Memory cassette model

Memory write adapter model

A1SHCPU

A1SNMCA-8KP

A6WA-28P

A1SJHCPU, A1SHCPU

A1SMCA-8KP, A1SNMCA-8KP

A6WA-28P

(5)

2

Program write during operation with E PROM (a)

(b)

2

When an operation is executed using an E PROM, writing is not possible in the RUN status. If writing is attempted in this status, the following messages will be sent to the peripheral devices : • When the SW3GP-GPPA is used

:

• When SW0RX-GPPA is used

:

• When the A7PU is used

:

"PC COMMUNICATIONS ERROR : ERROR CODE = 17" is displayed. "PC COMMUNICATIONS ERROR : ERROR CODE = 17" is displayed. "PC NOT RESPOND" is displayed.

Programs cannot be written from peripheral devices which are connected to the computer link module or other stations of the MELSECNET. Write programs from peripheral devices connected to the AnSHCPU's RS-422.

2-6

Page 23

2. SYSTEM CONFIGURATION (c)

MELSEC-A

When writing a program to the A1SNMCA-2KE, set the parameter for main sequence program capacity to 2 k steps or less. Programs written with a main sequence program capacity setting of 3 k steps or over cannot work properly. Checking between the AnSHCPU and a peripheral device will result in a mismatch.

2-7