Page 31
2. SYSTEM CONFIGURATION
Item
Model
A77GOT-S5
Graphic operation terminal
A850GOT
MELSEC-A
Description
Large graphic operation terminal monitor screen included model (black and white LCD, color LCD, EL) 250 monitor screens, 255 parts
Mid-size graphic operation terminal monitor included model (black and white LCD, STN color LCD) Base/window screen : 1024 pixels
Number of inputs/outputs
Current consumption
[I/O allocation module type]
5 V DC, - 24 V DC, - - 0.5 (when connecting MELSECNET: 0.7)
A851GOT A870GOT
A810GOT
Main base unit
Extension base unit
0.5 Large graphic operation terminal monitor screen included model (STN/TFT color EL) Base/window screen : 1024 pixels Large graphic operation terminal CRT connection model for monitor Base/window screen : 1024 pixels
A1S32B A1S33B A1S35B
Up to two I/O modules can be loaded. Up to three I/O modules can be loaded. Up to five I/O modules can be loaded.
A1S38B
Up to eight I/O modules can be loaded.
A1S52B(S1) A1S55B(S1)
Up to two I/O modules can be loaded. Up to five I/O modules can be loaded.
A1S58B(S1)
Up to eight I/O modules can be loaded.
A1S65B(S1)
Up to five I/O modules can be loaded.
A1S68B(S1)
Up to eight I/O modules can be loaded.
A1SC01B
0.055 m (2.17 in.) long flat cable, - A1SC03B A1SC07B Extension A1SC12B cable A1SC30B A1SC60B A1SC05NB A1SC07NB A1SC30NB A1SC07NB
0.33 m (11.8 in.) long 0.7 m (27.6 in.) long 1.2 m (47.24 in.) long 3 m (118.11 in.) long 6 m (236.22 in.) long 0.45 m (17.72 in.) long 0.7 m (27.6 in.) long 4.3 m (118.11 in.) long 5 m (196.85 in.) long, - - - - - - When connected via bus, 32 special points are occupied. When connected via bus, 32 special points are occupied. Consumed power: 100 VA Equipped with two extension connectors: one is on the right; the other on the left side Power supply module cannot be loaded (power is supplied from the main base unit)., - - - - - For extension on the right side Extension base unit connection cable, - - - - - - - - - - - * Approved standard
When connected via bus, 32 special points are occupied. Consumed power : 100 VA
Needs a power supply module.
* : Class 2 power supply recognized by the UL/cUL Standard is required for 5-12-24 V DC modules.
2 - 15
Remarks
A[ ]N, A[ ]A extension base cable
UL/cUL
Page 32
2. SYSTEM CONFIGURATION
Item
Model
MELSEC-A
Description
Applicable model
A1SMCA8KP A1SNMCA8KP A1SMCA2KE A1SMCA8KE A1SNMCA2KE A1SNMCA8KE
8 k steps, equipped with EPROM (directly) 8 k steps, equipped with EPROM (directly) 2 2 k steps, equipped with E PROM (directly) 2 8 k steps, equipped with E PROM (directly) 2 2 k steps, equipped with E PROM (directly) 2 8 k steps, equipped with E PROM (directly)
A2SNMCA30KE
14 k steps, equipped with E PROM (directly)
Memory write adapter
A6WA-28P
Used for memory cassette connector/EPROM 28-pin
Battery
A6BAT
EPROM
Memory cassette 2
E PROM
2
For A1SJHCPU : A6WA-28P required For A1SJH/A1SHCPU : A6WA-28P required For A1SJHCPU Writing/reading directly from the peripheral device is possible UL/cUL For A1SJH/A1SHCPU Writing/reading directly from the peripheral device is possible For A2SHCPU Writing/reading directly from the peripheral device is possible For A1SMCA-8KP Used to partition ROM in A1SMCA8KP Mounted in A1SCPU/A2SCPU body
Cable for connector/terminal block conversion module
AC05TB AC10TB AC20TB AC30TB AC50TB AC05TB-E AC10TB-E AC20TB-E AC30TB-E AC50TB-E
IC-RAM battery backup For sink type input module and sink type output module (standard type) For sink type input module and sink type output module (2-wire type) For sink type input module (3-wire type) For source type input module (standard type) For source type output module (standard type) For source type input module (2-wire type) For source type output module (2-wire type) For source type input module (3-wire type) 0.5 m (1.64 ft) for source module 1 m (3.28 ft) for source module 2 m (6.56 ft) for source module 3 m (9.84 ft) for source module 5 m (16.4 ft) for source module 0.5 m (1.64 ft) for source module 1 m (3.28 ft) for source module 2 m (6.56 ft) for source module 3 m (9.84 ft) for source module 5 m (16.4 ft) for source module
Relay terminal module
A6TE2-16SR
For sink type output module
A1SY41, A1SY42, A1SH42, AY42, AY42-S1, AY42-S3, AY42-S4, AH42
Cable for connecting relay terminal module
AC06TE AC10TE AC30TE AC50TE AC100TE
0.6 m (1.97 ft) long 1 m (3.28 ft) long 3 m (9.84 ft) long 5 m (16.4 ft) long 10 m (32.8 ft) long
A6TE2-16SR
A6TBXY36 A6TBXY54 Connector/terminal block conversion module
A6TBX70 A6TBX36-E A6TBY36-E A6TBX54-E A6TBY54-E A6TBX70-E
AnS I/O module and special module terminal block cover
A1STEC-S
Slim-type terminal block cover for the AnS I/O module and special module (terminal block connector type)
A1SX41(S2), A1SX42(S2), A1SY41, A1SY42, A1SH42, AX42(S1), AY42(S1/S3/S4), AH42 A1SX41(S2), A1SX42(S2), A1SH42, AX42(S1), AH42 A1SX81(S2), AX82 A1SY81, AY82EP A1SX81(S2), AX82 A1SY81, AY82EP A1SX81(S2), AX82
A6TBXY36, A6TBXY54, A6TBX70
A6TBX36-E, A6TBY36-E, A6TBX54-E, A6TBY54-E, A6TBX70-E
A1SX10, A1SX10EU, A1SX20, A1SX20EU, A1SX30, A1SX40 (S1/S2), A1SX80 (S1/S2), A1SY10, A1SY10EU, A1SY14EU, A1SY18A, A1SY18AEU, A1SY22, A1SY28A, A1SY28EU, A1SY40, A1SY50, A1SY60 (E), A1SY68A, A1SY80, A1SX48Y18, A1SX48Y58, A1SI61, A1S64AD, A1S62DA,A1S63ADA, A1S62RD3/4, A1SD61, A1SP60
* : Class 2 power supply recognized by the UL/cUL Standard is required for 5-12-24 V DC modules.
2 - 16
* Approved standard
Page 33
2. SYSTEM CONFIGURATION
MELSEC-A
REMARK I/O cables with connectors for I/O modules with 40-pin connector specifications (A1SX41, A1SX42, A1SY41, A1SY42, etc.) or 37-pin D-sub connector specifications (A1SX81, A1SY81, A1SY81EP) are available. Consult your nearest Mitsubishi representative for I/O cables with connectors.
(2)
A[ ]NA[ ]A extension base unit The following table shows the modules that can be loaded to the A[ ]NA [ ]A extension base units : A65B; A68B; A55B; or A58B. For details on the specifications of each module see the appropriate module manual.
POINT (1)
All A[ ]NA[ ]A "building block type I/O modules" are compatible with the AnSHCPU.
Item
Model
Single-axis positioning module
AD70, AD70D
Positioning module
AD71, AD71S1, AD72
Position detection module
A61LS, A62LS
High speed counter module
AD61, AD61S1
A-D converter module
A68AD, A68ADS2, A616AD, A60MX, A60MXR, A68ADN
Temperature input module
A616TD, A60MXT
D-A converter module
A62DA, A62DAS1, A616DAI, A616DAV, A68DAV, A68DAI
A-D/D-A converter module
A84AD
CRT control/LCD control module
AD57, AD57S1, AD58
Graphic controller module
AD57G, AD57GS3
Memory card, parrallel interface module
AD59, AD59S1
Voice output module
A11VC
Computer link module
AJ71C24(S3/S6/S8), AJ71UC24
Intelligent communication module
AD51E, AD51ES3, AD51H(S3)
Terminal interface module
AJ71C21, AJ71C21S1
MELSECNET/MINI (S3) data link module
AJ71PT32, AJ71PT32-S3
Data link module
AJ71AP21, AJ71AR21, AJ71AT21B
SUMINET interface module
AJ71P41
Ethernet interface module
AJ71E71
2 - 17
Page 34
2. SYSTEM CONFIGURATION
MELSEC-A
Item
Model
Multidrop data link module
AJ71C22
Interrupt module
AI61
Power supply module
A61P, A62P, A63P, A65P, A66P, A67P, A68P, A61PEU, A62PEU
Extension base unite
A62B, A65B, A68B, A52B, A55B, A58B
(3)
Peripheral devices Item
Module
Plasma handy graphic programmer
A6PHP-SET
Intelligent GPP
A6GPP-SET
Composite video cable RS-422 cable
User disk
Cleaning disk
AC10MD
RS-422 cable
• Connects A6GPP and monitor display. (1 m (3.28 ft) long)
AC30R4
3 m (9.84 ft) long 30 m (98.4 ft) long
SW0-GPPU
2DD
SW0S-USER
2HD
SW0-FDC
Applicable to A6GPP/A6PHP
Connects CPU and A6GPP/A6PHP. Used for storing user program (3.5 in., formatted) Used for cleaning disk drive.
A7PU
• Connected directly to the CPU with an RS-422 cable (AC30R4, AC300R4) to read and write programs. Provided with an MT function. • The product package includes a cable used for connection to an audio cassette recorder.
A7PUS
Connected directly to the CPU with an RS-422 cable (AC30R4-PUS) to read and write programs.
A8PUE
Connected directly to the CPU with an RS-422 cable (AC30R4-PUS, AC20R4-A8PU) to read and write programs.
AC30R4, AC300R4,
P-ROM writer module
A6PHP SW[ ]GP-GPPAEE : A-series GPP function system disk SW[ ]GP-GPPKEE : K-series GPP function system disk SW0-GPPU : User disk (2DD) AC30R4 : RS-422 cable (3 m (9.84 ft) long) A6GPP SW[ ]GP-HGPAEE : A-series GPP function system disk SW[ ]GP-HGPKEE : K-series GPP function system disk SW0-GPPU : User disk (2DD) AC30R4 : RS-422 cable (3 m (9.84 ft) long)
AC300R4
Programming module
RS-422 cable
Remarks • • • • • • • • • •
Used to connect an A7PU to the CPU. Long : 3 m/30 m (9.84 ft./98.4 ft.)
AC30R4-PUS
Used to connect an A7PUS or A8PUE to the CPU. Long : 3 m (9.84 ft.)
AC20R4-A8PU
Used to connect an A8PUE to the CPU. Long : 2 m (6.56 ft.)
• Used for writing a program in the CPU/A6PHP to ROM, or for reading A6WU AC30R4, AC300R4 AC03WU
2 - 18 a CPU program from ROM.
• Connected to CPU/A6PHP using an AC30R4/AC03WU cable. Connects CPU and A6WU. 3 m/30 m (9.84 ft/98.4 ft) long Connects A6PHP and A6WU. 0.3 m (0.98 ft) long
Page 35
2. SYSTEM CONFIGURATION
MELSEC-A
POINTS (1)
Programming devices compatible with A1SHCPU A6WU P-ROM writer module cannot be used. All programming devices compatible with A1SHCPU can be used, excluding A6WU. (When A7PU, A7PUS, A8PU or A8PUE is used, the CPU type "A3" is displayed when started up.)
(2)
Software packages compatible with A1SHCPU All utility packages compatible with A1SHCPU can be used.
2 - 19
Page 36
2. SYSTEM CONFIGURATION 2.4 2.4.1
MELSEC-A
General Description of System Configuration AnSHCPU The following gives the system configuration, number of inputs/outputs, I/O number allocation, etc. when the AnSHCPU is used as an independent system.
1st extension stage UNIT 1 2 3
1 2 3
System configuration
UNIT 1 2 3
1 2 3
1 2 3
Slot number to to to to to to to to 0F 1F 2F 3F 4F 5F 6F 7F to to to to to to to
8F 9F AF BF CF DF EF FF Extension base unit (A1S55B-S1) 16 17 18 19 20 (21) (22) (23) 100 110 120 130 140 150 160 170 to to to to to to to
10F 11F 12F 13F 14F 15F 16F 17F
Extension base unit (A1S68B-S1) 24 25 26 27 28 29 30 31 Power supply module
UNIT 1 2 3
7
80 90 A0 B0 C0 D0 E0 F0 to 3rd extension stage
6
Extension base unit (A1S58B-S1) 8 9 10 11 12 13 14 15 to
2nd extension stage
5
00 10 20 30 40 50 60 70
CPU
Extension cable
Power supply module
Main base unit (A1S38B) 0 1 2 3 4
180 190 1A0 1B0 1C0 1D0 1E0 1F0 to to to to to to to to
18F 19F 1AF 1BF 1CF 1DF 1EF 1FF
Maximum number of extension stages
Three
Maximum number of input/output points
A1SHCPU : 256 points, A2SHCPU : 512 points, A2SHCPU-S1 : 1024 points
Main base units
A1S32B, A1S33B, A1S35B, A1S38B
Extension base units
A1S52B(S1), A1S55B(S1), A1S58B(S1), A1S65B(S1), A1S68B(S1), A52B, A55B, A58B, A62B, A65B, A68B
Extension cables
Notes
I/O number allocation
A1SC01B, A1SC03B, A1SC07B, A1SC12B, A1SC30B, A1SC60B, AC06B, AC12B, AC30B, A1SC05NB, A1SC07NB (1) Only the 1st extension base unit can be used when extension base units of types other than the AnS S1 are equipped. (The S1 type and other types must not be used together.) (2) To use the AnS S1 type extension base unit with an A[ ]N or A[ ]A type, the latter must be equipped with the last extension base unit. (The A[ ]N or A[ ]A extension base unit cannot be connected to the AnS S1 type.) (3) When an A1S52B (S1), A1S55B (S1), A1S58B (S1), A52B, A55B, or A58B is used, a voltage of 5 V DC is supplied from the power supply module. See Section 7.1.3, and consider the application. (4) The extension cable should be used for distances of up to 6 m (19.68 ft.). (5) The extension cable must not be bundled with or laid near the main circuit (high voltage, high current) lines. (1) Allocate I/O numbers to the extension base units in order of extension base unit number, not in extension cable connection order. (2) I/O numbers are allocated on the assumption that both the main base unit and the extension base units have eight slots. Sixteen input/output points will be allocated to each slot indicated by dotted lines in the above system configuration figure. (3) Allocate 16 input/output points to empty slots. (4) If the setting of an extension base unit has been omitted, make the allocation on the assumption that each of the eight slots of the relevant base unit occupies 16 input/output points. (5) Items (2) to (4) can be changed by performing "I/O allocation". For details, see the ACPU Programming Manual (Fundamentals).
2 - 20
Page 37
2. SYSTEM CONFIGURATION 2.4.2
MELSEC-A
A1SJHCPU This section describes the system configuration, numbers of I/O points, I/O allocations, etc., for a stand-alone A1SJHCPU system. 0
Extension cable
1st extension base unit UNIT 1 2 3
System configuration
1 2 3
1
2
3
4
5
6
7
Slot number
00 10 20 30 40 50 60 70 to to to to to to to to 0F 1F 2F 3F 4F 5F 6F 7F
A1SJHCPU
Extension base unit (A1S58B-S1) 8
9
10 11 12 13 14 15
80 90 A0 B0 C0 D0 E0 F0 to to to to to to to to 8F 9F AF BF CF DF EF FF
To 2nd and 3rd extension base units (Can be used by allocating I/O points.)
To 2nd and 3rd extension base units (Can be used by allocating I/O points.) *In this example, a 16-point module is installed at each slot.
Maximum number of extension stages
Three
Maximum number of input/output points
256
Extension base units
A1S52B(S1), A1S55B(S1), A1S58B(S1), A1S65B(S1), A1S68B(S1), A52B, A55B, A58B, A62B, A65B, A68B
Extension cables
Notes
I/O number allocation
A1SC03B, A1SC07B, A1SC12B, A1SC30B, A1SC60B, A1SC01B, AC06B, AC12B, AC30B, A1SC05NB, A1SC07NB (1) If using a type of extension base unit for A1S use other than the S1 type,, only one extension base unit can be installed. (Combined use of S1 type extension base units and extension base units other than the S1 type is not possible.) (2) When using one or more S1 type extension base units for A1S use in combination with one or more extension base units for A[ ]N or A[ ]A use, the final extension base unit must be one for A[ ]N or A[ ]A use. (An S1 type extension base for A1S use can not be connected from an extension base for A[ ]N or A[ ]A use.) (3) Extension base units A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B, A58B are supplied with a 5 V DC power supply from the power supply module on the main base unit; see Section 7.1.3 to determine whether or not these extension base units can be used. (4) The total length of extension cable used must not exceed 6 m (19.68 ft.). (1) I/O numbers are allocated in the order of the numbers set in extension base number setting, regardless of the order of connection of extension cables. (2) When allocating I/O points, all main bases and extension bases are regarded as having 8 slots of I/O points. Accordingly, 16 points per slot are allocated to the part of the system configuration drawing indicated using dotted lines. (3) 16 points are allocated to vacant slots. (4) If extension base number setting has not been performed at one or more modules, I/O points are allocated by regarding each slot in the total number of slots involvedobtained by multiplying the number of extension bases for which setting was skipped by 8 slots-as occupying 16 points per slot. (5) The allocations in (2) to (4) above can be changed by performing "I/O allocation". When using two or three extension base units, perform "I/O allocation" to allocate 0 points to vacant slots of the A1SJCPU and some slots of the first extension base unit, and allocate I/O points to the second and third extension base units. (The total number of I/O points for the A1SJCPU and 1st, 2nd, and 3rd extension base units is 256.) For details on "I/O allocation", see the ACPU Programming Manual(Fundamentals).
2 - 21