Page 78
7. ERROR CODES
MELSEC-A Table 7.2 Error Code List (Continued)
Error Message
Detailed Error Code (D9091)
Error and Cause
(1) Reset CPU If error persists, possible hardware fault, consult Mitsubishi representative.
24
241
The entire stored program has been executed without executing the END instruction. (1) The END instruction has been missed (e.g. memory cassette removed during program execution). (2) The END instruction has been corrupted.
26, - The main CPU is malfunctioning or broken.
Possible hardware fault, consult Mitsubishi representative.
Verified data is different from the I/O data at power on. (1) An I/O module (including special function module) has been removed or the base unit while the PC power is switched ON, or wrong module is loaded.
Read the detailed error code by peripheral device, check and replace the module corresponding to that numeric value (I/O head number) or monitor special registers D9116 to D9123 by peripheral device, check and replace the module where that data bit is “1".
Output module fuse blown.
(1) Check the fuse blown LED indicator of the output module and replace the fuse of the lit module. (2) Read the detailed error code by peripheral device and replace the fuse of the output module corresponding to that numeric value (I/O head number), or monitor special registers D9100 to D9107 by peripheral device and replace the fuse of the output module where that data bit is “1".
401
Incorrect FROM/TO instruction execution.
402
Parameter I/O assignment, special function modules cannot be accessed at initial communication. At error occurrence, the head I/O number (the upper 2 digits of a 3 digit expression) of the special function module causing the error is stored in D9011.
Hardware fault (CPU, special function module and/or base unit). Consult Mitsubishi representative.
411
No response from special function unit after execution of FROM/TO instruction.
412
During parameter I/O assignment, at initial communication, responses from special function modules have not been returned. At error occurrence, the head I/O number (the upper 2 digits of a 3digit expression) of the special function module causing the error is stored in D9011.
Error Code (D9008)
“END NOT EXECUTE”
(Checked at end of program) “MAIN CPU DOWN” “UNIT VERIFY ERR.”
31, - (Checked continuously) “FUSE BREAK OFF”
32, - (Checked continuously) “CONTROL-BUS ERR.”
40
“SP. UNIT DOWN”
41
“LINK UNIT ERROR” 42, - A1SJ71AP21/R21, A1SJ71AT21B, AJ71AP21/R21 or AJ71AT21B located in master station.
7–9
Corrective Action
Hardware error of the accessed special function module. Consult Mitsubishi representative.
When using A1SJ71AP21/R21, A1SJ71AT21B, AJ71AP21/R21, or AJ71AT21B modules, set one as the master station and the other as a local station..
Page 79
7. ERROR CODES
MELSEC-A Table 7.2 Error Code List (Continued)
Error Message
Error Code (D9008)
Detailed Error Code (D9091)
“I/O INT. ERROR” 43
Error and Cause
Corrective Action
Interrupt signal received with no interrupt module present.
Since a hardware error has occurred in one of the modules, replace the modules one by one to find the faulty module. Consult Mitsubishi representative.
441
I/O modules allocated in parameter settings by peripheral device have been allocated by special function modules. Or, the opposite settings have been executed.
Reset I/O assignments in parameters by peripheral device according to the loading status of the special function modules.
442
More than 11 special function modules [except for the AI61 (S1)] which can start interrupts to the CPU have been loaded.
Load less than 10 special function modules [except for the AI61 (S1)] which can start interrupts to the CPU.
443
More than 1 AJ71AP21/R21s A1SJ71AT21Bs, AJ71AP21/R21s or AJ71AT21Bs has been loaded.
Load only AJ71AP21/R21s, A1SJ71AT21Bs, AJ71AP21/R21s or AJ71AT21Bs.
444
More than 6 computer link modules, etc., have been loaded to 1 CPU module.
Load no more than 6 computer link modules.
445
More than 1 AI61 (S1)/A1SI61 has been loaded.
Load only 1 AI61/A1SI61.
446
The modules MNET/MINI automatic refresh allocated in parameter settings by peripheral device and the names of the modules of actually linked station numbers are incorrect.
Reset the module assignments of the MNET/MINI automatic refresh in parameter settings by peripheral device according to the modules of station numbers actually linked.
The number special function modules which can use dedicated instructions, registered by I/O assignment per one CPU module (number of modules to be loaded) is larger than the specified limit. (The total of computers shown below is 1344 or more.)
Decrease the number of loaded special function modules., - “SP. UNIT LAY. ERR.”
44
(Number of loaded AD59 x 5)
447
(Number of loaded AD57(S1)/AD58 x 8) (Number of loaded A1SJ71C24-R2(PRF/R4) x 10) (Number of loaded AJ71C24(S3/S6/S8) x 10) (Number of loaded AJ71UC24 x 10) (Number of loaded AJ71C21(S1) x 29) (Number of loaded A1SJ71PT32-S3 x 125) +
(Number of loaded AJ71PT32(S3) x 125) Total
448
> 1344
(1) Load no more than 4 modules. (1) More than 4 AJ71LP21/ AJ71BR11 modules are installed. (2) Load a total of 4 or less of the modules. (2) A total of five or more of the following modules is installed: A1SJ71AP21/R21, A1SJ71AT21B, AJ71AP21/R21, AJ71AT21B, AJ71LP21, AJ71BR11.
7 – 10
Page 80
7. ERROR CODES
MELSEC-A Table 7.2 Error Code List (Continued)
Error Massage
Error Code (D9008)
Detailed Error Code (D9091)
“SP. UNIT ERROR” 461 (Checked when FROM/TO instruction, or special function module dedicated instruction is specified.)
There is no special function module in the area specified by the FROM/TO instruction.
Corrective Action
Read the error step by peripheral device, check and correct the content of the FROM/TO instruction of that step.
462
(1) The model name of the module (1) Match the model name specified by I/O allocation specified in the CC-Link parameter with that specified in dedicated instruction is different the CC-Link dedicated from that specified by I/O instruction. allocation parameter. (2) Read the error step by (2) There is no special function peripheral device, check and module in the area specified by correct the content of the the FROM/TO instruction or special function module there is no corresponding dedicated instruction of that special function module. step.
(1) Re-write link parameters from (1) The link range is set in peripheral programming module parameter settings by to PC. peripheral device, and for some (2) Check station number setting. reason, the content written to (3) Persistent error occurrence the link parameter area differs may be an indication of from the link parameter content hardware fault. Consult read by the CPU or link Mitsubishi representative. parameter is not written. (2) 0 slave stations set.
470
NET/10 network refresh parameter error.
471
NET/10 transfer parameter for data link error
472
NET/10 routing parameter error
473
NET/10 network parameter error (first module)
474
NET/10 network parameter error (second module)
475
NET/10 network parameter error (third module)
476
NET/10 network parameter error (fourth module)
46
“LINK PARA. ERROR”
47
Error and Cause
7 – 11
Page 81
7. ERROR CODES
MELSEC-A Table 7.2 Error Code List (Continued)
Error Message
Error Code (D9008)
Detailed Error Code (D9091)
Error and Cause
Corrective Action
Read the error step by peripheral device, check and correct the program of that step.
501
(1) When using file register (R), operations have been executed exceeding the specified range for the device number and block number of file register (R). (2) The file register is used in the program without executing file register capacity settings.
502
The combination of devices specified by instruction is incorrect.
503
The storage data of specified devices or the constants are not within the usable range.
504
The quality of settings used for handled data has exceeded the usable range.
“OPERATION ERROR”
50
505 (Checked during execution of instruction)
(1) The station number specified by instruction [LEDA/B|LRDP], [LEDA/B|LWTP], [LRDP] or [LWTP] is not a local station. (2) The head I/O number specified by instruction [LEDA/B|RFRP], [LEDA/B|RTOP], [RFRP] or [RTOP] is not a remote station.
7 – 12
Page 82
7. ERROR CODES
MELSEC-A Table 7.2 Error Code List (Continued)
Error Message
Error Code (D9008)
Detailed Error Code (D9091)
Error and Cause
Corrective Action
506
The head I/O number specified by instruction [LEDA/B|RFRP], [LEDA/B|RTOP], [RFRP] or [RTOP] is not a special function module.
Read the error step by peripheral device, check and correct the program of that step.
(1) While the AD57 (S1) or the AD58 is executing instructions by partial processing, other instruction have been output to the same module. (2) While the AD57 (S1) or the AD58 is executing instructions by partial processing, instructions have been output to other AD57 (S1) or AD58 by partial processing.
Read the error step by peripheral device and provide interlock by special relay M9066 or change the program structure and correct. This prevents the execution of other instructions to the same module while executing instructions to the AD57 (S1) or AD58 by partial processing and prevents the execution of instructions to other AD57(S1) or AD58 by partial processing.
(1) An instruction which cannot be executed by remote terminal module connected to the MNET/MINI-S3 was executed to the modules. (2) Another [PRC] instruction has been executed although the number registered in the memory and waiting to be processed has reached 32, and this has caused the mailbox (memory area for instructions waiting for execution) to overflow. (3) A [PIDCONT] instruction has been executed without executing a [PIDINIT] instruction. Or, a [PID57] instruction has been executed without executing a [PIDINIT] instruction or [PIDCONT] instruction.
(1) Read the error step by peripheral device and correct the program, meeting loaded conditions of remote terminal module. (2) Correct by using special register D9081 (number of mailbox vacancies) or special register M9081 (mailbox BUSY signal) to ensure that no registrations can be made in the mailbox (memory area for instructions waiting for execution), and therefore [PRC] instructions cannot be executed, when the mailbox is full. (3) Execute each instruciton, and then, execute the next instruction.
(1) CPU malfunction due to noise. (2) Hardware fault.
(1) Eliminate noise. (2) Hardware fault.
(1) Battery voltage low. (2) Battery not connected.
(1) Replace the battery. (2) When using RAM memory or the power failure compensation function, load the lead connectors.
“OPERATION ERROR”
507
50
509
(Checked during execution of instruction) “MAIN CPU DOWN”
60, - “BATTERY ERROR” 70, - (Checked at poweron)
7 – 13
Page 83
7. ERROR CODES 7.3
MELSEC-A
Error Code List Detected only with A1SHCPU and A2SHCPU(S1) The error codes, error messages, detailed error codes and corrective actions detected only with A1SHCPU and A2SHCPU(S1) are described. For errors other than above, refer to section 7.1. CC-Link is the abbreviation for Control & Communication Link. It will be referred to as CC-Link in this section. Table 7.3 Error Code List Error Message
Detailed Error Code (D9092)
“INSTRUCT CODE ERR.
Error and Cause
Corrective Action
An error code which the CPU cannot interpret exists in the program.
(1) Read out the steps where the error occurred using a peripheral device, and correct the program. (2) Check if the used ROM contains instruction codes that cannot be interpreted, and insert the correct ROM.
103
Wrong device was specified in the extension application instruction.
Read out the steps where the error occurred using a peripheral device, and correct the program.
104
The program structure of the extension application instruction was wrong.
105
Wrong command name was specified in the extension application instruction.
462
(1) The model name of the module specified in the CC-Link dedicated instruction is different from that specified by I/O allocation parameter. (2) The module specified by a CC-Link dedicated instruction is not a master module.
(1) Match the model name specified by I/O allocation parameter with that specified in the CC-Link dedicated instruction. (2) Read the error step with a peripheral device. Check and correct the CC-Link dedicated instruction in the step.
503
The stored data or constant in the specified device is not in the usable range.
Read out the steps where the error occurred using a peripheral device, and correct the program.
504
The specified number of data to use exceeded the allowed number.
101
“SP. UNIT ERROR”
“OPERATION ERROR”
509
The number of CC-Link dedicated instructions executed during a scan executed 64.
Reduce the number of CC-Link dedicated instructions executed during a scan to 64 or less.
A CC-Link dedicated instruction was issued to a master module for which parameters are not set.
Set parameters.
Point
MITSUBISHI
When using the CC-Link dedicated instructions, use a master module with the rating plate indicating “9707B” or later in its DATE column.
MODEL DATE
9707 B
MITUBISHI ELECTRIC
BD992D008H38 Function version Manufacture of year and month
7 – 14
Page 84
APPENDIX APPENDIX Appendix 1
Dissimilarities Between A1SHCPU and A1SCPU(S1)
Item
A1SHCPU
1
Processing speed *1
0.33µs
2
I/O points
2048 points *2
3
File register capacity (R)
Max. 8192 points (R0 to 8191)
Max. 4096 points (R0 to 4095)
4
Memory capacity
64k bytes
32k bytes
5
Comment points
Max. 3685 points
Max. 1600 points *3
6
CC-Link Dedicated Instruction
11 instructions
None
Conventional memory cassette 7
A1SCPU
A1SCPU-S1 1µs
256 points
512 points
× b b b b b
A1SMCA-2KE/8KE/8KP New memory cassette A1SNMCA-2KE/8KE/8KP *1 I/O processing: during refreshing or performing the LD instruction. *2 Each CPU has 2048 points (X/Y0 to 7FF) of I/O devices, while the actual I/O points are same as in the AnS series. The additional I/O devices can be used for MELSECNET (/B), MELSECNET/MINI, or CC-Link. *3 The CPU can store 1600 comment points, while the GPP function can create up to 3685 comment points.
Appendix 2
Dissimilarities Between A2SHCPU(S1) and A2SCPU(S1)
Item
A2SHCPU
A2SHCPU-S1
A2SCPU(S1)
1
Processing speed *4
0.25µs
1µs
2
I/O points
2048 points *5
512 points (1024 points *6)
3
File register capacity (R)
Max. 8192 points (R0 to 8191)
Max. 4096 points (R0 to 4095 *6)
4
Memory capacity
5
CC-Link Dedicated Instruction Conventional memory cassette
6
64k bytes
192k bytes
32k bytes (192k bytes *6)
11 instructions
None
× b b b b b
A2SMCA-14KE/14KP New memory cassette A2SNMCA-30KE *4 I/O processing: during refreshing or performing the LD instruction. *5 Each CPU has 2048 points (X/Y0 to 7FF) of I/O devices, while the actual I/O points are same as in the AnS series. The additional I/O devices can be used for MELSECNET (/B), MELSECNET/MINI, or CC-Link. *6 When using A2SCPU-S1
A–1
Page 85
APPENDIX Appendix 3
1
Item
A2ASCPU-S30
A2ASCPU-S60
A2ASCPU(S1)
Memory capacity (built-in RAM)
256k bytes
256k bytes
64k bytes (256k bytes *7)
Main
Max. 30k steps
Max. 30k steps
Max. 14k steps
Sub
None
Max. 30k steps
None
Program capacity
2
Dissimilarities Between A2SCPU-S30/S60 and A2ASCPU(S1)
3
No. of input/output points
1024 points
1024 points
512 points (1024 points *7)
4
Max. block No. of expanded file register
Block No. 3
Block No. 16
Block No. 3 (No. 16 *7)
5
Command processing speed
0.20 ms/step
0.15 ms/step
0.20 ms/step
0.32A
0.35A
0.32A
6
Sequence command
Consumed current
*7 When using A2ASCPU-S1
Appendix 4
CE Marking Compatible Modules for Compact PC
Mode l
Specification s
A1SHCPU CPU module
256 actual I/O points, 64k byte memory
A2SHCPU(S1) 512 actual I/O points, 64k byte memory
Power supply module
A1S61PEU
200-240 VAC input, 5 VDC 5A output
A1S62PEU
200-240 VAC input, 5 VDC 2A 24VDC 0.6A output
A1S61PN
100-240 VAC input, 5 VDC 5A output
A1S62PN
100-240 VAC input, 5 VDC 3A 24VDC 0.6A output
A1SX10EU
16 points, 100-120 VAC input
A1SX20EU
16 points, 200-240VAC input
A1SY10EU
16 points, 120VAC output (relay)
A1SY14EU
12 points, 240VAC output (relay)
A1SY18AEU
8 points, 240VAC output, independent common (relay)
A1SY28EU
8 points, 100-240VAC output (Triac)
Input module
Output module
Appendix 5 CC-Link Dedicated Instructions List RLPA
Link parameter setting
RRPA
Refresh parameter setting
RIFR
Read from master station buffer memory
RITO
Write to master station buffer memory
RIRD
Read from buffer memory of intelligent remote station
RIWT
Write to buffer memory of intelligent remote station
RIRCV
Read from buffer memory of intelligent remote station (with handshaking)
RISEND
Write to buffer memory of intelligent remote station (with handshaking)
RDGET
Read from the word station link register
RDPUT
Write to the word station link register
RDMON
Monitor the word station link register * For detailed information and description of CC- Link dedicated instructions, refer to Appendix 1.1 “CC-Link Dedicated Instructions” in the A1SJHCPU/A1SHCPU/A2SHCPU(S1) User’s Manual(IB-66779).
A–2