Manual · Mitsubishi
MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware)
Manual85 pagesPDF 773 KB
Hardware user's manual for Mitsubishi MELSEC AnS series compact PLCs: CPUs, power supplies and digital I/O modules.
Names · 14 models
The models it names
Filed with · 4 models
Also filed with these models on the old site
Summary
What is in it
Mitsubishi's hardware user's manual for the MELSEC AnS series compact programmable controllers (A1S, A1SC24-R2, A2S, A1SH, A2SH and A2AS CPUs). It gives general specifications and the specifications of the power supply and digital I/O modules, then covers installation and EMC and low-voltage compliance, base mounting, CPU part identification, wiring of power supply and I/O modules, fail-safe circuits, daily and periodic maintenance, battery replacement and CPU error code lists.
Its parts
- General Specifications
- Module Specifications
- Installation
- Wiring
- Fail-Safe Constructions
- Maintenance
- Error Codes
From the manual
Key facts from this manual
Each line names its page in the PDF.
Mitsubishi hardware user's manual for MELSEC A series compact PLCs: the A1S(S1), A1SCPUC24-R2, A2S(S1), A1SH, A2SH(S1) and A2AS(S1/S30/S60) CPUs, with their power supply modules and digital I/O modules such as the A1SX and A1SY series. It gives environmental and module specifications, installation and EMC rules, wiring, fail-safe circuits, maintenance and CPU error codes.
- Operating temperature
- 0 to 55°C (storage -20 to 75°C) p. 12
- Operating humidity
- 10 to 90% RH, non-condensing p. 12
- Installation location
- Control panel, no corrosive gases p. 12
- Elevation
- 2000m (6562 feet) max. p. 12
- Shock resistance
- 147m/s2 (15G), 3 times in each of X, Y, Z; JIS B3501, IEC 1131-2 p. 12
- Overvoltage category
- II max.; pollution level 2 max. p. 12
- A1SX81 input
- 32 points, 12/24 VDC, 3/7 mA; ON at 8 VDC or higher, OFF at 4 VDC or lower; 60% on at 26.4 VDC p. 15
- A1SX10 input
- 16 AC inputs, 100 to 120 VAC, 50/60 Hz p. 15
- A1SX42 input
- 64 points, 12/24 VDC, 2/5 mA; 50% on at 24 VDC (A1SX42-S2: 24 VDC, 5 mA) p. 15
- A1SY10 output
- 16 relay outputs, 240 VAC 50/60 Hz or 24 VDC, 2 A/pt, 8 A/com p. 17
- A1SY42 and A1SY81
- A1SY42: 64 points 12/24 VDC, 0.1 A/pt, 1.6 A/com; A1SY81: 32 points 12/24 VDC, 0.1 A/pt, 2 A/com p. 17
- A1S61PN power supply
- 100-240 VAC input, 5 VDC 5A output p. 85
- A1S63P power supply
- 24 VDC input (15.6 to 31.2VDC), 5 VDC 5A output p. 13
- A1SHCPU vs A1SCPU
- A1SHCPU: 256 actual I/O points, 64k bytes, 0.33µs; A1SCPU: 32k bytes, 1µs p. 84, 85
What this manual walks you through
- Power supply module specifications p. 13, 14
- Input module specifications p. 15, 16
- Output module specifications p. 17, 18
- Combined input/output module specifications p. 19, 20
- Installing to meet the EMC Directive p. 9
- CPU parts, LEDs and switches p. 39
- Clearing latched data with the RUN/STOP key switch p. 39
- Setting A1SCPUC24-R2 transmission and mode switches p. 40
- Replacing the CPU battery p. 69
- Reading CPU error codes and fixing their causes p. 70, 71
Good to know
- Power supply overcurrent protection shuts off the 5V and 24 VDC circuits and stops the system until the cause is removed. p. 13
- If the system will not boot after an overvoltage trip and the LED stays off, the power supply module must be replaced. p. 13
- Do not apply more than 400 V between AC and LG on the power supply. p. 14
Questions this manual answers
What are the specs of the Mitsubishi A1SX81?
A 32-point 12/24 VDC input module drawing 3/7 mA; ON at 8 VDC or higher, OFF at 4 VDC or lower, 60% simultaneously on at 26.4 VDC. p. 15
What input and output does the A1S61PN power supply have?
100-240 VAC input and a 5 VDC 5A output. p. 85
When should the battery in an A1S CPU be replaced?
As soon as possible after the low-battery signals M9006 and/or M9007 come on; the lithium battery keeps the program and data during power failures. p. 69
What does WDT ERROR (error code 22) mean?
The scan time exceeded the watchdog time; the manual says to reduce the scan time and check D9005 for line voltage dips. p. 71
What is the difference between the A1SHCPU and the A1SCPU?
The A1SHCPU processes at 0.33µs with 64k bytes of memory and CC-Link instructions; the A1SCPU runs at 1µs with 32k bytes. p. 84
Contents
Chapters and sections
Each line opens the PDF at its page.
- Cover1
- SAFETY PRECAUTIONS2
- REVISIONS6
- Notification of CE marking8
- 1. GENERAL SPECIFICATIONS12
- 2. MODULE SPECIFICATIONS13
- 3. INSTALLATION22
- 3.1 General Safety Requirements22
- 3.2 Requirements for Compliance to EMC Directive (89/336/EEC)23
- 3.3 Requirement to Conform to the Low-Voltage Instruction30
- 3.4 Module Handling34
- 3.5 Base Mounting35
- 3.6 Constructions to Reduce EMI Noise37
- 3.7 Precautions When Unfailure Power System (UPS) is Connected38
- 3.8 Part Identification of the CPU39
- 3.9 RS232C Interface (A1SCPUC24-R2 only)42
- 3.10 Self-Loopback Test (A1SCPUC24-R2 only)44
- 4. WIRING45
- 5. FAIL-SAFE CONSTRUCTIONS62
- 6. MAINTENANCE66
- 7. ERROR CODES70
- APPENDIX84
2 more lines, from page 85 on
The whole text · 13 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 51-5
- Pages 6 to 86-8
- CONTENTS9-11
- Pages 12 to 2112-21
- 3. INSTALLATION, pages 22 to 2922-29
- 3. INSTALLATION, pages 30 to 3730-37
- 3. INSTALLATION, pages 38 to 4438-44
- 4. WIRING, pages 45 to 5345-53
- 4. WIRING, pages 54 to 6154-61
- 5. FAIL-SAFE CONSTRUCTIONS62-65
- 6. MAINTENANCE66-69
- Pages 70 to 7770-77
- Pages 78 to 8578-85
The file



