Page 45
4. WIRING
MELSEC-A
4.
WIRING
4.1
General Safety Requirements
P DANGER All external power supply must be turned off during installation and wiring. Unless all phases are cut off from the products, it could cause electrical shock or damage on the products. Before connecting the power to the products, put terminal covers back onto the terminals. Otherwise, it could cause electrical shock. A protective earth terminal which is marked with “ ted to the earth. Otherwise, it could cause electrical shock.
(LG)” must be connec-
All electrical connections should be carried out by trained and competent personnel, and must comply with the requirements of all relevant local and national wiring regulations for installation wiring. Particular attention is required when preparing the installation wiring for connection to terminal to ensure that hazardous live wiring are adequately separated from the Safety Extra Low Voltage wiring. All external power supplies and signals connected to other devices or equipment, of which rated voltage is 24 V or lower, should not compromise the Safety Extra Low Voltage requirements. A readily accessible switch or circuit breaker should be included in the equipment which contains the product so that the power supply for the product can be disconnected if necessary.
E CAUTION
Rated voltage and terminal assignment of each module should be confirmed before wiring is carried out. Connection of different voltage or wrong connection could cause fire and/or malfunction of the products. Do not supply 24 VDC power supply from more than one power supply modules in parallel to one I/O module. If they are connected so, the power supply modules will become not and could be caused fire and/or malfunction.
24 VDC
24 VDC External power supply
Terminal screws should be tighten by the specified torque. Loose connection could cause short-circuit, fire and/or malfunction of the products. During wiring, be sure that no off-cut of wires or other conductive dusts go into modules. It could cause fire, malfunction and/or failure of the products. Wiring for modules which provide connector for external wiring should be securely carried out with the specified tools or by soldering. Unsecured connection could cause short-circuit, fire, and/or malfunction of the products.
4–1
Page 46
4. WIRING
MELSEC-A Do not place process control signal cables and/or communication cables nearby main power cables or actuation power cables so that risk of noise trouble can be minimized. It is recommended to keep a distance of 100 mm or more between those cables.
4.2
Power Supply Modules (1)
Terminal assignment (a) A1S61P
A1S61P
FG SHORT 100VAC
Terminal Name
Wiring Instructions
INPUT AC100/200V
Connect 100 to 120/200 to 240 VAC power supply wires to these terminals. Either terminal can be connected to either live or neutral line.
SHORT 100VAC OPEN 200VAC
These are voltage selection terminals. Short the terminals for 100 to 120 VAC input, and open them for 200 to 240 VAC input.
LG
This is a functional earth terminal to be connected to the noise free earth. WARNING: If this terminal is not connected to the earth, the terminal holds half of the supplied voltage.
FG
This is a functional earth terminal to be connected to the noise free earth.
OPEN 200VAC LG INPUT 100/200VAC
(b) A1S61PEU
A1S61PEU
Terminal Name
Wiring Instructions
INPUT 200 to 240 VAC
Connect 200 to 240 VAC power supply wires to these terminals. Either terminal can be connected to either live or neutral line.
(LG)
(FG) (LG)
This is a protective earth terminal to be connected to the earth. WARNING: This terminal must be connected to the earth, otherwise, the secondary circuit cannot be ensured as safe.
INPUT 200 to 240VAC
4–2
(FG)
This is a functional earth terminal to be connected to the noise free earth.
Page 47
4. WIRING
MELSEC-A (c) A1S61PN
A1S61PN
Terminal Name
Wiring Instructions
INPUT 100 to 240 VAC
Connect 100 to 240 VAC power supply wires to these terminals. Either terminal can be connected to either live or neutral line.
NC NC (LG)
(FG) (LG)
This is a protective earth terminal to be connected to the earth. WARNING: This terminal must be connected to the earth, otherwise, the secondary circuit cannot be ensured as safe.
INPUT 100 to 240VAC
(FG)
NC
This is a functional earth terminal to be connected to the noise free earth. No Connectable
(d) A1S62P A1S62P
Terminal Name
Wiring Instructions
INPUT 100/200VAC
Connect 100 to 120/200 to 240 VAC power supply wires to these terminals. Either terminal can be connected to either live or neutral line.
SHORT 100VAC OPEN 200VAC
These are voltage selection terminals. Short the terminals for 100 to 120 VAC input, and open them for 200 to 240 VAC input.
LG
This is a functional earth terminal to be connected to the noise free earth. WARNING: If this terminal is not connected to the earth, the terminal holds half of the supplied voltage.
FG
This is a functional earth terminal to be connected to the noise free earth.
+24V 24G
These are output terminals of 24 VDC service power which can be used as I/O load power and/or other purposes.
+24V 24G FG SHORT 100VAC OPEN 200VAC LG INPUT 100/200VAC
4–3
Page 48
4. WIRING
MELSEC-A (e) A1S62PEU
A1S62PEU
Terminal Name
Wiring Instructions
INPUT 200 to 240 VAC
Connect 200 to 240 VAC power supply wires to these terminals. Either terminal can be connected to either live or neutral line.
+24V 24G (LG)
(FG) (LG)
This is a protective earth terminal to be connected to the earth. WARNING: This terminal must be connected to the earth, otherwise, the secondary circuit cannot be ensured as safe.
INPUT 200 to 240 VAC
(FG)
+24V 24G
This is a functional earth terminal to be connected to the noise free earth. These are output terminals of 24 VDC service power which can be used as I/O load power and/or other purposes.
(f) A1S62PN A1S62PN
Terminal Name
Wiring Instructions
INPUT 100 to 240 VAC
Connect 100 to 240 VAC power supply wires to these terminals. Either terminal can be connected to either live or neutral line.
+24V 24G (FG)
(LG)
(LG)
INPUT 100 to 240VAC (FG)
+24V 24G
This is a protective earth terminal to be connected to the earth. WARNING: This terminal must be connected to the earth, otherwise, the secondary circuit cannot be ensured as safe. This is a functional earth terminal to be connected to the noise free earth. These are output terminals of 24 VDC service power which can be used as I/O load power and/or other purposes.
(g) A1S63P Terminal Name
A1S63P
INPUT +24V 24G
Connect 24 VDC power supply wires to these terminals. A 24 VDC SELV power supply is required.
LG
This is a functional earth terminal to be connected to the noise free earth.
FG
This is a functional earth terminal to be connected to the noise free earth.
NC
No Connectable
NC NC FG NC NC LG +24V INPUT 24G
SELV power supply
Functional earth
4–4
Wiring Instructions
Page 49
4. WIRING
MELSEC-A (2)
Take following measures so that electrical noise is minimized. (a) Provide separate wiring for the PC power, I/O devices, and other operating devices as shown below. Further more, insert an isolated transformer if intensive noise is expected. Main power supply
PC power supply
Isolation transformer
200 to 240 VAC
PC I/O power supply Control devices Main power supply Main power devices
(b) Power supply wires should be twisted as tightly as possible, and connect to power supply modules at the shortest distance. To minimize voltage drop, use wires as thick as possible. (c) As a measure against lightning surges, insert surge absorbers as shown below.
PC I/O devices
AC power source
E2
E1
E1
Lightning surge absorber
POINTS (1) Provide separator grounding for the lightning surge absorber (E1) and for the PC (E2). (2) Select a lightning surge absorber of which maximum allowable line voltage is higher than input voltage of the power supply module.
4.3
Digital I/O Modules The following instructions should be observed for I/O module wiring. (1)
I/O signal wires must be installed at least 100 mm (3.94 inch) away from high-voltage and large-current main power wires so that noise induction from such high power circuit is minimized.
(2)
If the I/O signal wires cannot be separately installed from the high power wires, use shielded cables for I/O signal and connect their shield to the earth.
4–5
Page 50
4. WIRING 4.3.1
MELSEC-A
Input module connections Rated Input Voltage
Model
Model
Rated Input Voltage
(2) A1SX30
12/24 VAC/DC
A1SX10 100 to 120 VAC
(1) A1SX10EU
X01
A1SX20 200 to 240 VAC
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
X03 X05 X07 X08 X0A X0C X0E COM
1
3 4 5 6 X07 8 7 9 X08 10 11 X0A 12 13 X0C 14 X0E 16 15 17 COM 18 19 20 X03 X05
A1SX20EU
X01
2
X00 X02 X04 X06 COM
X09 X0B X0D X0F
+
-
-
+
X00 X02 X04 X06 COM
X09 X0B X0D X0F
9 and 18 are connected internally.
9 and 18 are connected internally.
P DANGER Do not touch terminals while the power is supplied. Model (3)
A1SX40
Model
Rated Input Voltage 12/24 VDC
(4)
A1SX80
12/24 VDC
A1SX80-S1
A1SX40-S1
24 VDC
24 VDC A1SX80-S2
A1SX40-S2
X01 X03 X05 X07 X08
2 4 6 8 10
X0A
12
X0C
14
X0E - +
Rated Input Voltage
COM
16 18 20
1 3 5 7 9 11 13 15 17
X00
1 2 3 X03 4 5 X05 6 X07 8 7 9 X08 10 11 X0A 12 X0C 14 13 X0E 16 15 17 COM 18 19 20 X01
X02 X04 X06 COM
X09 X0B X0D X0F
+ -
19
- +
X00 X02 X04 X06 COM
X09 X0B X0D X0F
9 and 18 are connected internally.
9 and 18 are connected internally.
4–6
Page 51
4. WIRING Model
MELSEC-A Rated Input Voltage
Model
Rated Input Voltage
(6) (5)
A1SX41
12/24 VDC
A1SX41-S2
24 VDC
A1SX42
12/24 VDC
X00
A1SX42-S2
24 VDC
X01
A1SX71
5/24 VDC
X02 X03 X00 X01 X02 X03 X04 X05 X06 X07 X08 X09 X0A X0B
B19 A19 B18 A18 B17 A17 B16 A16 B15 A15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10
X10 X04 X11 X05 X12 X06 X13 X07 X14 X08 X15 X09 X16 X0A X17 X0B
B6
A6
B5
A5
Vacant
B4
A4
Vacant
Vacant
B3
A3
Vacant
B2
A2
Vacant
B1
A1
Vacant
X0E X0F
COM COM
X18
B12 A12
X19
B11 A11
X1A
B10 A10
X1B
A6
B5
A5
Vacant
B4
A4
Vacant
Vacant
B3
A3
Vacant
B2
A2
Vacant
B1
A1
X0F X1C
X1E
X17
B13 A13
B6
X0E
X1D
X16
B14 A14
A7
X1B
A7
X15
B15 A15
B7
X0D
B7
X0D
X14
B16 A16
A8
X1A
A8
X13
B17 A17
B8
X0C
B8
X12
B18 A18
A9
X19
A9
X11
B19 A19
B9
X18
B9
X0C
- +
B20 A20
X10
B20 A20
- +
COM
X1F COM
X1C X1D X1E X1F
Vacant
*1 The figure above shows the connections for the open collector (sink) type. B1 and B2 are connected internally. •
*1 The figure above indicates F (the first half 32 points). The connections for L (the latter half 32 points) are the same as for F (regard X00 to X1F as X20 to X3F.) B1 and B2 are connected internally.
TTL, LS-TTL, CMOS buffer (sink) connection B20
+
-
B2
•
*2 The A and B pin number rows shown above are transposed with respect to the diagram of the A and B rows which is printed on the module. Remember that the A row pin numbers correspond to the B row of the module.
Sensor (source) connection
B20
+ -
B2
*2 The A and B pin number rows shown above are transposed with respect to the diagram of the A and B rows which is printed on the module. Remember that the A row pin numbers correspond to the B row of the module.
4–7
Page 52
4. WIRING Model (7)
MELSEC-A Rated Input Voltage
A1SX81
12/24 VDC
A1SX81-S2
24 VDC
1
X01
2
X03
X02
21 3
X05
X04
22 4
X07
X06
23 5
X09
X08
24 6
X0B
X0A
25 7
X0D
26
X0F
27
8 9
X11
X0C X0E X10
28 10
X13
X12
29 11
X15
X14
30 12
X17
•
X00
20
X16
31 13
X19
32
X1B
33
X1D
34
X1F
35
COM
36
Vacant
37
14 15 16
17 , 18 and 36 are connected internally.
4–8
X18 X1A X1C X1E
17
COM
-
+
18
COM
+
-
19
Vacant
Page 53
4. WIRING Model
MELSEC-A Pin Arrangement
Rated Input Voltage
(8) A1S42X
12/24 VDC
Input terminals
Pin No.
Internal control circuit
R
X38 X30 X28 X20 X18 X10 X08 X00
R
B12
A12
B11
A11
B10
A10
B9
A9
B8
A8
B7
A7
B12
XD0
A12
XD1
B6
A6
B11
XD2
B5
A5
B4
A4
B3
A3
B2
A2
B1
A1
X39 X31 X29 X21 X19 X11 X09 X01 X3A X32 X2A X22 X1A X12 X0A X02 X3B X33 X2B X23 X1B X13 X0B X03 A11
XD3
X3C X34 X2C X24 X1C X14 X0C X04 B10
XD4
A10
XD5
B9
XD6
A9
XD7
B8
XSCN0
A8
XSCN1
B7
XSCN2
A7
XSCN3
B6
XSCN4
A6
X3D X35 X2D X25 X1D X15 X0D X05 X3E X36 X2E X26 X1E X16 X0E X06 X3F X37 X2F X27 X1F X17 X0F X07
Seen from front face of the module Internal control circuit
R
Pin No.
Signal Name
Pin No.
Signal Name
B12
XD0
A12
XD1
B11
XD2
A11
XD3
B10
XD4
A10
XD5
XSCN5
B9
XD6
A9
XD7
B5
XSCN6
B8
XSCN0
A8
XSCN1
A5
XSCN7
B7
SXCN2
A7
XSCN3
B6
XSCN4
A6
XSCN5
B5
XSCN6
A5
XSCN7
B4
Vacant
A4
Vacant
B3
12/24 VDC
A3
12/24 VDC
B2
0V
A2
0V
B1
FG
A1
FG
Internal scan at 1/8th duty
B3, A3 12/24 VDC B2, A2
*1
If there will be cases where two or more switches are pressed simultaneously, install a diode at each switch (see right).
4–9