The text of a manual · part 7 of 13

MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware): 3. INSTALLATION, pages 38 to 44

Pages 38 to 44 of 85, from MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware)

The original document is the PDF (773 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi A1S61PN, Mitsubishi A1S63P, Mitsubishi A1SHCPU, Mitsubishi A1SX10, Mitsubishi A1SX40, Mitsubishi A1SX40-S1, Mitsubishi A1SX42, Mitsubishi A1SX42-S2, and 6 more models

Page 38

3. INSTALLATION (3)

MELSEC-A Process signal cables Please be aware of the following points for process signal cable installations. (a) Do not install process signal cables with primary voltage lines. (b) If process cables are installed outside of the cabinet, use of screen cables is effective for EMI noise reduction.

3.7

Precautions When Unfailure Power System (UPS) is Connected When Unfailure Power System (abbreviated as UPS hereafter) is connected to the CPU system, care must be taken on the following matter: Use a UPS of inverter power supply type at all time with 5% or less voltage distortion. Do not use a UPS of commercial power supply type.

3 – 17

Page 39

3. INSTALLATION 3.8

MELSEC-A

Part Identification of the CPU This section gives the names of each part of the CPU. (6)

(2)

(1)

(11)

(8)

(11)

(3)

(7)

(9)

(5)

(10)

(4)

A1SCPU(S1)

A2SCPU(S1)

(1) RUN/STOP key switch

A2ASCPU(S1/S30/S60)

(6) Module fixing screws

RUN/STOP: Used to start/stop sequence program execution. L.CLR: Used to clear the data set in the latch range set in the parameters. (2) “RUN” LED ON: Indicates that the RUN key switch is set to the RUN position and the sequence program is being executed. OFF: The RUN LED is OFF in the following cases: • When the 100/200 VAC power supply is not being supplied to the CPU.

(7) Battery (8) Dip switch Memory write protect switch ...A1SCPU(S1), A1SCPUC24-R2 (OFF: Memory not protected, ON (ON : Memory write protected) I/O control switch (OFF: Refresh mode, ON: Direct mode) (9) Battery connector (10) Memory cassette installing connector (11) Memory write protect Dip switch

• When the RUN/STOP key switch is set to the STOP position. • When a remote STOP/PAUSE is currently effective. Flashing: The RUN LED flashes in the following cases: • When an error that stops sequence program operation has been detected in self-diagnosis. • When a latch clear operation is being executed. (3) “ERROR” LED ON: Indicates that an error has been detected in self-diagnosis. (Note that this LED remains OFF if the setting for the detected error in the ERROR LED indication priority settings is “OFF”.) OFF: Indicates that no error has occurred, or a fault has been detected by the CHK instruction. Flashing: Indicates that the annunciator (F) has been switched ON by the sequence program. (4) RS-422 connector (5) Cover

3 – 18

Memory Write Protect Range (kbytes)

Setting Switch A2SCPU A2ASCPU

A2SCPU-S1 A2ASCPUS1/S30/S60

0 to 16

1: ON

1: ON

16 to 32

2: ON

2: ON

32 to 48

3: ON

3: ON

48 to 64

4: ON

4: ON

64 to 80

Unused

5: ON

80 to 96

Unused

6: ON

96 to 112

Unused

7: ON

112 to 144

Unused

8: ON

144 to 256

Unused

9: ON

Latch clear method 1) Turn the RUN/STOP key switch from the “STOP” position to the “L.CLR” position several times to make the “RUN” LED start flashing. 2) Turn the RUN/STOP switch from the “STOP” position to the “L.CLR” position once more. 3) The latch clear operation is completed when the “RUN” LED goes OFF.

Page 40

3. INSTALLATION

MELSEC-A

MELSEC A1SCPUC24-R2 STOP RUN

L.CLR

ERROR

RESET

RUN

(12)

RESET

MITSUBISHI

ON 1

(13)

2

BC D

4

E 6 7

2

67

5

F0 1

8 9

3

A

34 5

8 9

(14)

(15)

A1SCPUC24-R2 (12) Transmission specification setting switch

(14) Computer link LED

Transmission specification settings (factory setting: all OFF)

LED No.

Pisition of Setting Switch SW

ON 1 2 3 4 5 6 7 8 9

1

0

Setting Items Write during RUN enabled/disabled setting

ON

OFF

Enabled

Disabled

1 2

2 3

Transmission speed setting

0

RUN

1

SD

Transmitting Flashes during data transmission

2

RD

Receiving Flashes during data receive

3

CPU

Communications with PC CPU Flashes during communications with PC CPU

4

NEU

Neutral Transmission sequence initial state (waiting for ENQ): ON ENQ received: OFF

5

ACK

ACK After sending ACK: ON After sending NAK: OFF

6

NAK

NAK After sending NAK: ON After sending ACK: OFF

7

C/N

Result of PC CPU communications Error: ON Normal: OFF

8

P/S

Parity/Sum check error Error: ON Normal: OFF

9

PRO

Protocol error Communications protocol error: ON Normal: OFF

10

SIO

SIO error Normal: OFF

3

See *1

4

4 5

Data bit setting

8 bit

7 bit

6

Parity bit setting

Set

Not set

7

Even/odd parity setting

Even

Odd

8

Stop bit setting

2 bit

1 bit

9

Sum check setting

Set

Not set

5 6 7 8 9

*1 Transmission speed setting Baud rate (BPS)

Description Normal run Normal: ON Error: OFF

10 300

600

1200

2400

4800

9600

19200

SW05

OFF

ON

OFF

ON

OFF

ON

OFF

SW06

OFF

OFF

ON

ON

OFF

OFF

ON

SW07

OFF

OFF

OFF

OFF

ON

ON

ON

(13) Mode setting switch Mode settings (factory setting: 0)

0

Unusable

F0 1

1

Protocol 1

2

67

A

BC D

Setting

2

Protocol 2

3

Protocol 3

4

Protocol 4

(15) RS-232C connector

E

8 9

Mode Setting Switch Number

34 5

MODE

5 6 to E F

No-protocol or printer function Unusable Used for testing the independent module

3 – 19

Page 41

3. INSTALLATION

MELSEC-A MELSEC A1SHCPU STOP RUN

LCLR

ERROR

RESET

RUN RESET

(16)

MITSUBISHI

(10)

A1SHCPU/A2SHCPU(S1) (16) Dip switch A1SHCPU

A2SHCPU

Switch No.

Application

2

Memory write protect setting (RAM and E 2 PROM) ON: With memory write protection *1 OFF: Without memory write protection

1

I/O select switch setting ON: Direct method OFF: Refresh method

Switch No. 5

Application I/O switch setting ON: Direct method OFF: Refresh method I/O select switch setting ON: With memory write protection *1 OFF: Without memory write protection Memory write protection range

1 2 3 4 5 6 7 8 9 10

A2SHCPU-S1

ON

OFF

4

48 to 64k bytes

3

32 to 48k bytes

2

16 to 32k bytes

1

0 to 16k bytes

Switch No. 10

Application I/O select switch setting ON: Direct method OFF:Refresh method Memory write protect setting (RAM and E 2 PROM) ON: With memory write protection *1 OFF:Without memory write protection Memory write protection range

9

144 to 192k bytes

8

112 to 144k bytes

7

96 to 112k bytes

6

80 to 96k bytes

5

64 to 80k bytes

4

48 to 64k bytes

3

32 to 48k bytes

2

16 to 32k bytes

1

0 to 16k bytes

*1 When installing the memory cassette, the setting becomes invalid to RAM only.

3 – 20

Page 42

3. INSTALLATION 3.9

MELSEC-A

RS232C Interface (A1SCPUC24-R2 only) (1)

1 2 3 4 5

RS-232C connector specificatins

Pin Number

Signal Abbreviation

1

CD

2

RD(RXD)

Receive data

3

SD(TXD)

Send data

4

DTR(ER)

Data terminal ready

5

SG

Signal ground

6

DSR(DR)

Data set ready

7

RS(RTS)

Request to send

8

CS(CTS)

Clear to send

6 7 8 9

Signal Name

Signal Direction A1SCPUC24-R2 ↔ External Device

Receive carrier detection

A 9-pin D subconnector is supplied in the same package as the A1SCPUC24R2 body. Product name 9-pin Dsub (male), screw mounted 17JE-23090-02-D8A, made by DDK (2)

RS-232C cable For the RS-232C cable, use a cable that conforms to the RS-232C standard and is no longer than 15 m. (Recommended cable)

(3)

7/0. 127[ ]P HRV-SV............(RS-232C cable made by Oki Densen) Specify the number of wire pairs. For example, if the number of pairs is thirteen: 7/0. 127 13P HRV-SV Connecting the RS-232C connectors The standard method for connecting the RS-232C connectors is shown below. For details on the connection method, refer to the Computer Link Module User’s Manual (Com. link func./Print func.). (a) Example connection to an external device in which the CD signal (pin No.8) can be switched ON and OFF. A1SCPUC24-R2

Cable Connections and Signal Directions

External Device

Signal Names

Pin Number

CD

1

CD

RD(RXD)

2

RD(RXD)

SD(TXD)

3

SD(TXD)

DTR(ER)

4

DTR(ER)

SG

5

SG

DSR(DR)

6

DSR(DR)

RS(RTS)

7

RS(RTS)

CS(CTS)

8

CS(CTS)

3 – 21

Signal Names

Page 43

3. INSTALLATION

MELSEC-A (b) Example connection to an external device in which the CD signal (pin No.8) cannot be switched ON and OFF. In the case of a connection to a device in which the device’s CD signal cannot be switched ON and OFF, set non-execution of the buffer memory address 10BH RS232C CD terminal check. 1) Example connection to an external device in which DC code control or DTR/DSR code control is executed. A1SCPUC24-R2

Cable Connections and Signal Directions

External Device

Signal Names

Pin Number

Signal Names

CD

1

CD

RD(RXD)

2

RD(RXD)

SD(TXD)

3

SD(TXD)

DTR(ER)

4

DTR(ER)

SG

5

SG

DSR(DR)

6

DSR(DR)

RS(RTS)

7

RS(RTS)

CS(CTS)

8

CS(CTS)

2) Example connection to an external device in which DC code control is executed. A1SCPUC24-R2

Cable Connections and Signal Directions

External Device

Signal Names

Pin Number

CD

1

CD

RD(RXD)

2

RD(RXD)

SD(TXD)

3

SD(TXD)

DTR(ER)

4

DTR(ER)

SG

5

SG

DSR(DR)

6

DSR(DR)

RS(RTS)

7

RS(RTS)

CS(CTS)

8

CS(CTS)

3 – 22

Signal Names

Page 44

3. INSTALLATION

MELSEC-A

3.10 Self-Loopback Test (A1SCPUC24-R2 only) The self-loopback test checks whether or not the isolated A1SCPUC24-R2 (not connected to any external devices) will operate correctly. For details on the self-loopback test, refer to the Computer Link Module User’s Manual (Com. link func./Printer func.). Connect the cables • Connect cables to the RS-232C connectors. Pin Signal Number Abbreviation

1 2 3 4 5

6 7 8 9

Signal Name

Cable Connections

Receive carrier detection

1

CD

2

RD(RXD)

Receive data

3

SD(TXD)

Send data

4

DTR(ER)

Data terminal ready

5

SG

Signal ground

6

DSR(DR)

Data set ready

7

RS(RTS)

Request to send

8

CS(CTS)

Clear to send

Set the mode setting switch • Set the mode setting switch to “F”. Execute the self-loopback test • Turn the PC CPU power supply ON or reset the PC CPU. Check the LED display status Check Item

Display When Normal

PC CPU communications check RS-232C communications check

C/N

OFF

CPU

Flicker

SIO

OFF

SD RD

Completed • Turn the power supply OFF.

3 – 23

Flicker

Display in Error Status C/N (LED No.7)

ON

SIO (LED No.10)

ON