Page 30
3. INSTALLATION
MELSEC-A
The precautions required when installing a noise filter are described below. (1)
Do not bundle the wires on the input side and output side of the noise filter. When bundled, the output side noise will be induced into the input side wires from which the noise was filtered. Input side (power supply side)
Input side (power supply side)
Introduction Filter
Filter Output side (device side)
(a) The noise will be included when the input and output wires are bundled.
(2) 3.3
Output side (device side) (b) Separate and lay the input and output wires.
Earth the noise filter earthing terminal to the control cabinet with the shortest wire possible (approx. 10 cm).
Requirement to Conform to the Low-Voltage Instruction The low-voltage instruction, one of the European Instructions, is now regulated. The low-voltage instruction require each device which operates with power supply ranging from 50VAC to 1000V and 75VDC to 1500V to satisfy necessary safety items. In the sections from 3.3.1 to 3.3.7, cautions on installation and wiring of the MELSEC-AnS series PC to conform to the low-voltage instruction regulation are described. We have put the maximum effort to develop this material based on the requirements and standards of the regulation that we have collected. However, compatibility of the devices which are fabricated according to the contents of this manual to the above regulation is not guaranteed. Each manufacturer who fabricates such device should make the final judgment about the application method of the low-voltage instruction and the product compatibility.
3.3.1
Standard applied for MELSEC-AnS The standard applied for MELSEC-AnS is EN61010-1 safety of devices used in measurement rooms, control rooms, or laboratories. For the modules which operate with the rated voltage of 50VAC/75VDC or above, we have developed new models that conform to the above standard. (See Appendix 4.) For the modules which operate with the rated voltage under 50VAC/75VDC, the conventional models can be used, because they are out of the low-voltage instruction application range.
3–9
Page 31
3. INSTALLATION 3.3.2
MELSEC-A
Precautions when using the MELSEC-AnS series PC Module selection (1)
Power module For a power module with rated input voltage of 100/200VAC, select a model in which the internal part between the first order and second order is intensively insulated, because it generates hazardous voltage (voltage of 42.4V or more at the peak) area. (See Appendix 4.) For a power module with 24VDC rated input, a conventional model can be used.
(2)
I/O module For I/O module with rated input voltage of 100/200VAC, select a model in which the internal area between the first order and second order is intensively insulated, because it has hazardous voltage area. (See Appendix 4.) For I/O module with 24VDC rated input, a conventional model can be used.
(3)
CPU module, memory cassette, base module Conventional models can be used for these modules, because they only have a 5VDC circuit inside.
(4)
Special module Conventional models can be used for the special modules including analog module, network module, and positioning module, because the rated voltage is 24VDC or smaller.
(5)
Display device Use an A870GOT CE compatible model.
3.3.3
Power supply The insulation specification of the power module was designed assuming installation category II. Be sure to use the installation category II power supply to the PC. The installation category indicates the durability level against surge voltage generated by a thunderbolt. Category I has the lowest durability; category IV has the highest durability.
Category IV
Category III
Category II
Category I
Figure 1. : Installation Category Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution.
3 – 10
Page 32
3. INSTALLATION 3.3.4
MELSEC-A
Control box Because the PC is an open device (a device designed to be stored within another unit), be sure to use it after storing in the control box. (1)
Electrical shock prevention In order to prevent persons who are not familiar with the electric facility such as the operators from electrical shocks, the control box must have the following functions: (a) The control box must be equipped with a lock so that only the personnel who has studied about the electric facility and have enough knowledge can open it. (b) The control box must have a structure which automatically stops the power supply when the box is opened.
(2)
Dustproof and waterproof features The control box also has the dustproof and waterproof functions. Insufficient dustproof and waterproof features lower the insulation withstand voltage, resulting in insulation destruction. The insulation in our PC is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or below. Pollution level 1:
An environment where the air is dry and conductive dust does not exist. Pollution level 2: An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust. Generally, this is the level for inside the control box equivalent to IP54 in a control room or on the floor of a typical factory. Pollution level 3: An environment where conductive dust exits and conductivity may be generated due to the accumulated dust. An environment for a typical factory floor. Pollution level 4: Continuous conductivity may occur due to rain, snow, etc. An outdoor environment. As shown above, the PC can realize the pollution level 2 when stored in a control box equivalent to IP54. 3.3.5
Module installation (1)
Installing modules contiguously In AnS series PCs, the left side of each I/O module is left open. When installing an I/O module to the base, do not make any open slots between any two modules. If there is an open slot on the left side of a module with 100/200VAC rating, the printed board which contains the hazardous voltage circuit becomes bare. When it is unavoidable to make an open slot, be sure to install the blank module (A1SG60). When using the A1S5aB expansion base with no power supply, attach the cover packaged with the expansion base to the side of the leftmost module.
3 – 11
Page 33
3. INSTALLATION 3.3.6
MELSEC-A
Grounding There are two kinds of grounding terminals as shown below. Either grounding terminal must be used grounded. Be sure to ground the protective grounding for the safety reasons.
3.3.7
Protective grounding
: Maintains the safety of the PC and improves the noise resistance.
Functional grounding
: Improves the noise resistance.
External wiring (1)
24VDC external power supply For special modules that require a 24VDC I/O module or external power supply, user a model whose 24VDC circuit is intensively insulated from the hazardous voltage circuit.
(2)
External devices When a device with a hazardous voltage circuit is externally connected to the PC, use a model whose circuit section of the interface to the PC is intensively insulated from the hazardous voltage circuit.
(3)
Intensive insulation Intensive insulation refers to the insulation with the dielectric withstand voltage shown in table 2. Table 2: Intensive Insulation Withstand Voltage (Installation Category II, source: IEC664)
Rated voltage of hazardous voltage area
Surge withstand voltage (1.2/50µs)
150VAC or below
2500V
300VAC or below
4000V
3 – 12
Page 34
3. INSTALLATION 3.4
MELSEC-A
Module Handling
E CAUTION Do not disassemble or modify the modules. Doing so could cause trouble, erroneous operation, injury, or fire. When wiring, be sure there are no foreign substances such as sawdust or wiring debris inside the module. Such debris could cause fires, damages, or erroneous operation. Tighten the terminal screws with the specified torque. If the terminal screws are loose, it could result in short circuits, fire, or erroneous operation. If the terminal screws are too tight, it may cause falling, short circuit or erroneous operation due to damage of the screws or module. Install so that the pegs on the bottom of the module fit securely into the base unit peg holes, and use the specified torque to tighten the module’s fixing screws. Not installing the module correctry could result in erroneous operation, damage, or pieces of the product falling. If the terminal screws are too tight, it may cause falling, short circuit or erroneous operation due to damage of the screws or module. Do not directry touch the module’s conductive parts or electronic componets. Doing so could cause erroneous operation or damage of the module.
(1)
Module enclosure, terminal block connectors and pin connectors are made of resin; do not drop them or subject them to strong impact.
(2)
Do not remove modules’ printed circuit boards from the enclosure in order to avoid changes in operation.
(3)
During wiring, take care to ensure that wiring off-cuts, etc. do not get inside the case. If anything does get inside the case, remove it.
(4)
Tighten the module mounting and fixing screws as specified below. Screw
Tightenig Torque N⋅cm (kg⋅cm) [lb⋅inch]
Module mounting screws (M4)
78 to 118 (8 to 12) [6.9 to 10.4]
I/O module terminal screw (M3.5)
59 to 88 (6 to 9) [5.2 to 7.8]
Power spply module terminal screws (M3.5)
59 to 88 (6 to 9) [5.2 to 7.8]
3 – 13
Page 35
3. INSTALLATION 3.5
MELSEC-A
Base Mounting
(1)
Mounting dimension
Mounting dimensions of each base unit are as follows:
out
HS
CPU
I/O 0
I/O 1
I/O 3
I/O 2
I/O 4
I/O 5
I/O 6
I/O 7
80626E80G52
MITSUBISHI ELECTRIC CORPORATION
POWER
H
OUT
MADE IN JAPAN E.S.D
A1S38B
WS W
Dimensions mm (inch) A1S32B
A1S33B
A1S35B
A1S38B
A1S52B (S1)
A1S55B (S1)
A1S58B (S1)
A1S65B (S1)
A1S68B (S1)
W
220 (8.66)
255 (10.04)
325 (12.80)
430 (16.93)
155 (6.10)
260 (10.24)
365 (14.37)
315 (12.40)
420 (16.54)
Ws
200 (7.87)
235 (9.25)
305 (12.01)
410 (16.14)
135 (5.31)
240 (9.45)
345 (13.58)
295 (11.61)
400 (15.75)
H
130 (5.12)
Hs
110 (4.33)
(2)
Base unit mounting position
Provide a clearance between the top and bottom of modules and wall of structure or components as given below. This is required for ventilation and allows easy replacement of modules. Main base, Extension base (A1S5[ ]B(S1),A1S6[ ]B(S1))
30 mm (1.18 inch) or over
Extension base (A5[ ]B, A6[ ]B)
80 mm (3.15 inch) or over
30mm (1.18 inch) or over
Main base
Main base
30 mm (1.18 inch) or over
30mm (1.18 inch) or over
Extension base (A1S5[ ]B(S1),A1S6[ ]B(S1))
Conduit (50mm (1.97 inch) or less in height)
30mm (1.18 inch) or over
30mm (1.18 inch) or over
Extension base (A5[ ]B,A6[ ]B)
80 mm (3.15 inch) or over
Conduit (50mm (1.97 inch) or less in height) 30mm (1.18 inch) or over
80 mm (3.15 inch) or over
3 – 14
Page 36
3. INSTALLATION (3)
MELSEC-A Unit mounting orientation (a) Since the PC generates heat, it should be mounted on a well ventilated location in the orientation shown below.
(b) Do not mount it in either of the orientations shown below.
Flat Vertical
(4)
Mount base unit on a flat surface. If the mounting surface is not even, this may strain the printed circuit boards and cause malfunctions.
(5)
Avoid mounting base unit in proximity to vibration sources such as large magnetic contractors and no-fuse circuit breakers; mount these on a separate panel or at a distance.
(6)
In order to avoid the effects of radiated noise and heat, provide the clearances indicated below between the PC and devices that generate noise or heat (contactors and relays). Required clearance in front of: at least 100 mm (3.94 inches) Required clearance on the right and left of <R>: at least 50 mm (1.97 inches)
At least 100 mm (3.94 inches)
At least 50mm(1.97 inches)
Contactor, relay, etc.
3 – 15
Page 37
3. INSTALLATION (7)
MELSEC-A If you want to mount base units on a DIN rail, please note the following points. (a) Suitable DIN rail types are listed as follows: TH35-7.5Fe TH35-7.5Al TH35-15Fe *JIS: Japanese Industrial Standard (b) Spacing intervals for DIN rail mounting screws When using a TH35-7.5Fe or TH35-7.5Al DIN rail, rail mounting screws should be placed at a pitch of 200 mm (7.87 inch) or less in order to ensure that the rail has sufficient strength. DIN rail
DIN rail mounting screws
35 mm (1.38 inches)
P
P
P P=200 mm (7.87 inches) or less
3.6
Constructions to Reduce EMI Noise The following measures are effective to reduce EMI noise generated by equipment which contains the AnS products. (1)
Grouding of a control cabinet Material of the control cabinet should be steel or equivarent conductor so that radiation of noise is protected. However, if grounding of the cabinet is not good enough, the cabinet body to which noise is inducted becomes an antenna to radiate noise. Therefore, impedance of grouding cable of the cabinet should be as low as possible. Use of a flat braided wire at shortest distance to the earth is recommended to minimize high frequency impedance. Door of the cabinet should be also connected to the body low impedance wires.
(2)
Grouding of AnS Please be aware of the following points for grouding of AnS. (a) Connect both LG and FG terminal on power supply modules to the control cabinet at shortest distance. Approx. 20cm. 2
(b) Use thick wire for the earth connections. 2mm or thicker.
3 – 16