3. INSTALLATION
MELSEC-A
3.
INSTALLATION
3.1
General Safety Requirements
E CAUTION This product is an open type equipment and itself does not comply with IP2X protection. The product must be installed in a suitable enclosure which should be selected and installed in accordance to the local and national standards. An enclosure which contains the product can be opened only under any of the following conditions (a) to (c) in order to protect operators from electrical shock in normal operations. The following measures must be taken: (a) The use of a key or tool is necessary. This method is only allowed for access by skilled or instructed persons. (b) Disconnection of supplied power before the enclosure is opened. (c) Barriers should be provided for all live parts except those supplied by Extra-Low Voltage. This products must be installed and used in environment specified as the environmental specifications. Otherwise, using in different environment could cause electrical shock, fire, malfunction, damage of the products and/or decrease of product capability. When mounting a module onto a base unit, securely insert the fixing hook on the bottom of the module into the hole provided on the base unit at first, then plug the body of module on the base unit. If the modules are not mounted correctly they may fall, malfunction or fail to operate correctly. Extension base cables must be securely connected. Make sure that no unsecured connection is made. Unsecured connection could cause PC to read and/or write wrong status from/to input or output modules. A memory cassette module or memory chips must be securely loaded on a connector or socket. Make sure that no unsecured loading was made or malfunction may occur.
3–1
Page 23
3. INSTALLATION 3.2
MELSEC-A
Requirements for Compliance to EMC Directive (89/336/EEC) The EMC Directive (89/336/EEC) will become mandatory within Europe from January 1st 1996. The EMC directive in essence defines the amount of electromagnetic output a product is allowed to produce and how susceptible that product is to electromagnetic interference. Any manufacturer or importer of electrical/electronic apparatus must before releasing or selling products within Europe after that date have either a CE mark attached to their goods. Testing to comply with the directive is done by use of agreed European standards which define limits for radiated and mains conducted electro-magnetic emissions from equipment, levels of immunity to radiated emissions, ability for equipment to cope with transient voltage surges and electro-static discharges. When installed in the specified manner this unit will be compliant with the relevant standards EN50081-2 and prEN50082-2 as applicable in the EMC directive. Failure to comply with these instructions could lead to impaired EMC performance of the equipment and as such Mitsubishi Electric Corporation can accept no liability for such actions.
3.2.1
EMC standards When the PC is installed following the directions given in this manual its EMC performance is compliant to the following standards and levels as required by the EMC directive.
Specifications
Test Item
Test Description
Standard Values
EN55011 Radiated noise
Measure the electric wave released by the product.
30M-230MHz
QP : 30dBµV/m (30m measurement) *1
EN55011 Conduction noise
Measure the noise released by the product to the power line.
150k-500kHz QP: 79dB, Mean : 66dB *1
IEC801-2 Static electricity immunity *2
Immunity test by applying static electricity to the module enclosure.
4kV contact discharge
IEC801-3 Radiated electromagnetic field *2
Immunity test by radiating an electric field to the product.
10V/m, 27-500MHz
IEC801-4 First transient burst noise
Immunity test by applying burst noise to the power line and signal cable.
2kV
EN61000-4-2 Static electricity immunity *2
Immunity test by applying static electricity to the module enclosure.
EN61000-4-4 First transient burst noise
Immunity test by applying burst noise to the power line and signal cable.
2kV
ENV50140 Radiated electromagnetic field AM modulation*2
Immunity test by radiating an electric field to the product.
10V/m, 80-1000MHz, 80% AM modulation@1kHz
ENV50204 Radiated electromagnetic field Pulse modulation*2
Immunity test by radiating an electric field to the product.
10V/m, 900MHz, 200Hz pulse modulation, 50% duty
ENV50141 Conduction noise
Immunity test by inducting electromagnetic field to the power line signal cable.
10Vrms, 0.15-80MHz, 80% modulation@1kHz
230M-1000MHz QP : 37dBµV/m (30m measurement)
EN50081-2: 1995 prEN50082-2: 1991
EN50082-2: 1995
3–2
500k-30MHz QP : 73dB, Mean: 60dB
8kV air discharge
4kV contact discharge 8kV air discharge
Page 24
3. INSTALLATION
MELSEC-A
(*1) QP: Quasi-peak value, Mean: Average value (*2) The PC is an open type device(device installed to another device) and must be installed in a conductive control box. The tests for the corresponding items were perfomed while the PC was installed to inside the control box.
3–3
Page 25
3. INSTALLATION 3.2.2 3.2.2.1
MELSEC-A
Installation instructions for EMC Control cabinet When constructing a control cabinet where the PC system will be installed, the following instructions must be followed.
3.2.2.2
(1)
Use a conductive control cabinet.
(2)
When attaching the control cabinet’s top plate or base plate, mask painting and weld so that good surface contact can be made between the cabinet and plate.
(3)
To ensure good electrical contact with the control cabinet, mask the paint on the installation bolts of the inner plate in the control cabinet so that contact between surfaces can be ensured over the widest possible area.
(4)
Earth the control cabinet with a thick wire so that a low impedance connection to ground can be ensured even at high frequencies. (22 mm 2 wire or thicker is recommended.)
(5)
Holes made in the control cabinet must be 10 cm diameter or less. If the holes are 10 cm or larger, radio frequency noise may be emitted.
(6)
Connect the door of cabinet to the main body with flat braided wires at as many points as possible so that a low impedance can be ensured even at high frequencies.
Connection of power and earth wires Earthing and power supply wires for the PC system must be connected as described below. (1)
Provide an earthing point near the power supply module. Earth the power supply’s LG and FG terminals (LG: Line Ground, FG: Frame Ground) with the thickest and shortest wire possible. (The wire length must be 30 cm or shorter.) The LG and FG terminals function is to pass the noise generated in the PC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.
Note) A long conductor will become a highly efficient antenna at high frequency. (2)
The earth wire lead from the earthing point must be twisted with the power supply wires. By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.
(3)
Except for A1S61PEU and A1S62PEU, short between FG and LG terminals by a short jumper wire.
3–4
Page 26
3. INSTALLATION 3.2.2.3
MELSEC-A
Cables The cables led from the control cabinet contain a high frequency noise element and outside the control panel these cables act as antenna and radiate noise. The cables connected to input/output modules or special modules which leave the control panel must always be shielded cables. Mounting of a ferrite core on the cables is not required (excluding some models) but if a ferrite core is mounted, the noise radiated through the cable can be suppressed further. Use of a shielded cable is also effective for increasing the noise immunity level. The PC system’s input/output and special function module provide a noise immunity level of equivalent to that stated in IEC801-4: 2 kV when a shielded cable is used. If a shielded cable is not used or if the shield earthing treatment is not suitable even when used (refer to section 3.2.2.4), the noise immunity level is less than 2 kV Note) prEN50082-2 specifies the noise resistance level based on the signal wire application Signals involved in process control: 2 kV Signals not involved in process control: 1 kV The meaning of “involved in process control” is not defined in prEN50082-2. However, when the purposes of the EMC Directive are considered, the signals that could cause personal injury or risks in the facility if a malfunction occurs should be defined as “signals involved in process control”. Thus, it is assumed that a high noise immunity level is required.
3–5
Page 27
3. INSTALLATION 3.2.2.4
MELSEC-A
Shield earthing When a shield of shield cable is earthed to the cabinet body, please ensure that the shield contact with the body is over a large surface area. If the cabinet body is painted it will be necessary to remove paint from the contact area. All fastenings must be metallic and the shield and earthing contact must be made over the largest available surface area. If the contact surfaces are too uneven for optimal contact to be made either use washers to correct for surface inconsistencies or use an abrasive to level the surfaces. The following diagrams show examples of how to provide good surface contact of shield earthing by use of a cable clamp. Screw Clamp fitting
Shield section
Paint mask (a) Peal the cable insulation off and expose the shield section.
Shielded cable
(b) Sandwich the exposed shield section with the clamp and earth to the control cabinet over a wide area.
Note) The method of earthing by soldering a wire onto the shield section of the shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.
Shielded cable Wire Crimp terminal
3.2.2.5
MELSECNET/II module The following requirements apply to A1SJ71AR21, A1SJ71BR11, AnNCPUR21, AnACPUR21. (1)
Always use a triaxial cable for the module. The radiated noise in the band of 30 MHz or higher can be suppressed by using a triax cable. Earth the outer shield by the method described in Section 3.2.2.4.
Earth this section
(2)
Always mount a ferrite core onto the triaxial cable. Mount the ferrite core near the control cabinet outlet of each cable. Use of the TDK ZCAT3035 ferrite core is recommended.
3–6
Page 28
3. INSTALLATION 3.2.2.6
MELSEC-A
Ethernet module (1)
Always earth the AUI cable connected to the A1SJ71E71-B5. The AUI is a shielded cable so remove the outer insulation and connect to earth the exposed shield section using as wide a surface area as possible in the manner shown below.
AUI cable Shield
3.2.2.7
(2)
Always use a triaxial cable for the coaxial cable connected to the A1SJ71E71-B2. The earthing precautions are the same as Section 3.2.2.5.
(3)
For A1SJ71E71-B2/B5, always mount a ferrite core in addition to items (1) and (2) above. Use of the TDK ZCAT3035 ferrite core is recommended.
I/O and other communication cables Always earth the shield section of the I/O signal cables and other communication cables (RS-232-C, RS-422, etc.) in the same manner as described in Section 3.2.2.4 if the cables go outside of the control cabinet.
3.2.2.8
Power supply module The precautions required for each power supply module are described below. Always observe the items noted as precautions. Model
Precautions
A1S61P A1S62P A1S63P (*1)
Always mount one of the filters listed in section 3.2.2.10 to the incoming power supply lines.
A1S61PEU A1S62PEU A1S61PN A1S62PN
None
(*1) If a sufficient filter circuitry is built into a 24 VDC external power supply unit, the noise generated by A1S63P will be absorbed by that filter circuit, so a line filter may not be required.
3–7
Page 29
3. INSTALLATION 3.2.2.9
MELSEC-A
Ferrite core A ferrite core is effective for reducing noise in the band of 30 MHz to 100 MHz. Mounting of a ferrite core is not necessary except for some particular models described in Section 3.2.2.5 and 3.2.2.6. However if further attenuation of noise is necessary, mounting of a ferrite core on cables which radiate noise is recommended. When a ferrite core is mounted, mount the ferrite core just before the point where the cable goes outside of the cabinet. The ferrite will not be effective if the mounting position is not adequate.
Ferrite core
Ferrite core
Noise
Noise
(a) When there is a distance from the cable exit hole, the noise will jump over the forrite, thus the effect will be halved.
(b) When mounted by the cable exit hole, the noise will not jump over the ferrite.
3.2.2.10 Noise filter (power supply line filter) The noise filter (power supply line filter) is a device effective to reduce conducted noise. Except some particular models described in Section 3.2.2.8, installation of a noise filter onto the power supply lines is not necessary. However conducted noise can be reduced if it is installed. (The noise filter is generally effective for reducing conducted noise in the band of 10 MHz or less.) Usage of the following filters is recommended. Model name
FN343-3/01
FN660-6/06
ZHC2203-11
Manufacturer
SCHAFFNER
SCHAFFNER
TDK
Rated current
3A
6A
3A
Rated voltage
250 V
3–8