The text of a manual · part 4 of 13
MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware), pages 12 to 21
Pages 12 to 21 of 85: 1. GENERAL SPECIFICATIONS; 2. MODULE SPECIFICATIONS
The original document is the PDF (773 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi A1S61PN, Mitsubishi A1S63P, Mitsubishi A1SHCPU, Mitsubishi A1SX10, Mitsubishi A1SX40, Mitsubishi A1SX40-S1, Mitsubishi A1SX42, Mitsubishi A1SX42-S2, and 6 more models
Page 12
1. GENERAL SPECIFICATIONS 1.
MELSEC-A
GENERAL SPECIFICATIONS This product has been designed to be installed in the following environmental conditions. Please place the product in places where environmental conditions satisfies the specifications. Item
Specifications
Ambient operating temperature
0 to 55°C
Ambient storage temperature
-20 to 75°C
Ambient operating humidity
10 to 90% RH, Non-condensing
Ambient storage humidity
10 to 90% RH, Non-condensing Frequency
Vibration resistance
Conforming to JIS B 3501, IEC 1131-2
Under intermittent vibration Under continuous vibration
Acceleration
Amplitude
10 to 57Hz, 0.075mm (0.003inch)
57 to 150Hz
9.8m/s 2 {1G}, 10 to 57Hz, 0.035mm (0.001inch)
57 to 150Hz
4.9m/s2 {0.5G}, No. of sweeps 10 times each in X, Y, Z directions (for 80 min.)
Conforming to JIS B3501, IEC 1131-2 (147m/s 2 {15G}, 3 times in each of 3 directions X Y Z)
Shock resistance Operating ambience
No corrosive gases
Operating elevation
2000m (6562 feet) max.
Installation location
Control panel
Over voltage category * 1
II max.
Pollution level * 2
2 max.
*1:
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*2:
This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally.
1–1
Page 13
2. MODULE SPECIFICATIONS MELSEC-A 2.
MODULE SPECIFICATIONS
2.1
Power Supply Modules Specifications of power supply modules are shown in the following table Specifications Item A161P
A1S62P
Base loading slot
A1S63P
Power supply module loading slot 100 to 120 VAC+10%/-15%(85 to 132 VAC)
24 VDC +30%/-35% (15.6 to 31.2VDC)
Rated input voltage 200 to 240 VAC+10%/-15%(170 to 264 VAC) 50/60 Hz ±3%
Rated input frequency
105 VA
41 Ω
20 A 8 ms or lower
81 A 1 ms or lower
Max. input apparent power Inrush current
5 VDC
5A
3A
5A
24 VDC±10%
0.6 A
5 VDC
5.5 A or higher
3.3 A or higher
5.5 A or higher
24 VDC
0.66 A or higher
Rated output current
Overcurrent protection
5 VDC
5.5 to 6.5 V
Overvoltage protection
24 VDC Efficiency
65% or higher
Allowable momentary power failure time *3
Dielectric withstand voltage
20ms or lower
1ms or lower
Between primary and 5 VDC
1500 VAC *1
1500 VAC *1
500 VAC
Between primary and 24 VDC
1500 VAC *1
5M Ω or highter at insulation resistance tester
Insulation resistor
Noise voltage 1500Vp-p, Noise width 1 µs, Noise frequency 25 to 60Hz (noise simulator condition)
Noise durability
Power indication
Noise voltage 500Vp-p, Noise width 1 µs, Noise frequency 25 to 60Hz (noise simulator condition)
Power LED indication (light at the time of output of 5VDC)
Terminal screw size
M3.5 × 7
Applicable wire size
0.75 to 2mm 2 (AWG18 to 14)
Applicable solderless terminal
RAV1.25 to 3.5, RAV2 to 3.5
Applicable tightenig torque
59 to 88 N⋅cm (6 to 9kg⋅cm) 130 × 55 × 93.6 (5.12 × 2.17 × 3.69)
External dimension mm (inch) Weight kg (lb)
0.53 (1.17)
0.55 (1.21)
0.5 (1.1)
*1: Overcurrent protection The overcurrent protection device shuts off the 5V, 24 VDC circuit and stops the system if the current flowing in the circuit exceeds the specified value. When this device is activated, the power supply module LED is switched OFF or dimly lit. If this happens, eliminate the cause of the overcurrent and start up the system again. *2: Overvoltage protection The overvoltage protection device shuts off the 5 VDC circuit and stops the system if a voltage of 5.5 to 6.5 V is applied to the circuit. When this device is activated, the power supply module LED is switched OFF. If this happens, switch the input power OFF, then ON to restart the system. The power supply module must be changed if the system is not booted and the LED remains OFF. *3: Allowable momentary power interruption time This value indicates the momentary power interruption time allowed for the PC CPU and varies according to the power supply module used with the PC CPU module. The allowable momentary power interruption time for a system in which an A1S63P is used is defined as starting when the primary power supply of the 24 VDC stabilized power supply of the A1S63P is turned OFF and lasting until the 24 VDC becomes less than the specified voltage (15.6 VDC).
2–1
Page 14
2. MODULE SPECIFICATIONS MELSEC-A
A1S61PEU
A1S62PEU
A1S61PN
200 to 240 VAC (10%/-15%) (170 to 264VAC)
A1S62PN
100 to 240 VAC(10%/-15%) (85 to 264VAC) 50/60 Hz ±5% 105VA
40 A 8ms or lower
20A 8ms or lower
5A
3A
5A
3A
0.6A
0.6A
5.5 A or higher
3.3 A or higher
5.5 A or higher
3.3 A or higher
0.66A or higher
0.66 A or higher
20ms or higher 1780 VAC
1780 VAC
1780 VAC
AC across input/LG and output/FG 2830VAC rms/3cycle (2000m)
5M Ω or highter at insulation resistance tester
AC across input/LG and output/FG5M Ω or highter, mesured with a 500VDC insulation resistance tester
(1) Noise voltage 1500Vp-p, Noise width 1 µs, Noise frequency 25 to 60Hz (noise simulator condition) (2) Noise voltage IEC801-4, 2kV
RAV1.25 to 3.5, RAV2 to 3.5
RAV1.25 to 4, RAV2 to 4
59 to 88 N⋅cm (6 to 9 kg⋅cm)
83 to 113 N⋅cm (8.5 to 11.5 kg⋅cm)
130 × 55 × 93.6 (5.12 × 2.17 × 3.69)
130 × 54.5 × 93.6 (5.12 × 2.15 × 3.69)
0.53 (1.17)
0.55 (1.21)
0.60(1.32)
*4: A1S61PEU and A1S62PEU comply with EN61010-1 and safety aspects of IEC1131-2 to meet the Low Voltage Directive which will be mandatory from the 1st of January 1997. *5: Do not apply over 400 Voltage between AC and LG as the Varistor is installed between the AC and LG.
2–2
Page 15
2. MODULE SPECIFICATIONS MELSEC-A 2.2
Digital I/O Modules
2.2.1
Input modules Specifications of input modules are shown in the following table. Operating Voltage
Model
Type
A1SX10 A1SX10EU
No. of Points
16 AC input
Rated Input Voltage
100 to 120 VAC, 50/60 Hz
16
A1SX20
16
A1SX20EU
16
200 to 240 VAC, 50/60 Hz
Input Current
Dielectric Withstand Voltage
6 mA
1500 VAC
7 mA
1780 VAC
9 mA
1500 VAC
11 mA
2830 VAC
ON Voltage
80 VAC or higher
OFF Voltage
30 VAC or lower
Maximum Simultaneous Input Points (Percentage Simultaneously ON) 100% (110 VAC) 60% (132 VAC) 100%
80 VAC or higher
30 VAC or lower
60% (220 VAC)
16
12/24 VAC, 50/60 Hz 12/24 VDC
4.2/8.6 mA
7 VAC/VDC or higher
2.7 VAC/VDC or lower
75% (26.4 VAC)
A1SX40
16
12/24 VDC
3/7 mA
8 VDC or higher
4 VDC or lower
100% (26.4 VDC)
A1SX40-S1
16
24 VDC
7 mA
14 VDC or higher
6.5 VDC or lower
100% (26.4 VDC)
A1SX40-S2
16
24 VDC
7 mA
14 VDC or higher
6.5 VDC or lower
100% (26.4 VDC)
32
12/24 VDC
3/7 mA
8 VDC or higher
4 VDC or lower 60% (26.4 VDC)
A1SX41-S2
32
24 VDC
7 mA
14 VDC or higher
6.5 VDC or lower
A1SX42
64
12/24 VDC
2/5 mA
8 VDC or higher
4 VDC or lower 50% (24 VDC)
A1SX42-S2
64
24 VDC
5 mA
17.5 VDC or higher
7 VDC or lower 50% (24 VDC)
A1SX71
32
5/12 VDC
1.2/3.3 mA
3.5 VDC or higher
1 VDC or lower 100%
A1SX80
16
12/24 VDC
3/7 mA
8 VDC or higher
4 VDC or lower
100% (26.4 VDC)
16
24 VDC
7 mA
17 VDC or higher
5 VDC or lower
100% (26.4 VDC)
A1DX80-S2
16
24 VDC
7 mA
13 VDC or higher
6 VDC or lower
100% (26.4 VDC)
A1SX81
32
12/24 VDC
3/7 mA
8 VDC or higher
4 VDC or lower 60% (26.4 VDC)
A1SX81-S2
32
24 VDC
7 mA
13 VDC or higher
6 VDC or lower 60% (26.4 VDC)
16/32/ 48/64
12/24 VDC
4/9 mA
8 VDC or higher
4 VDC or lower
A1SX30
A1SX41
A1SX80-S1
A1S42X
AC/DC input
DC input (sink type)
DC input (sink/source)
DC input (dynamic)
2–3
500 VAC
60% (26.4 VDC)
100% (26.4 VDC)
Page 16
2. MODULE SPECIFICATIONS MELSEC-A
Specifications of input modules are shown in the following table. Max. Response Time Field Wiring OFF to ON
ON to OFF
20 ms
35 ms
30 ms
Applicable Wire Size
Points/ Common
Noise Immunity
Internal Current Consumption (5 VDC)
No. of Occupied Points
Terminal
16
1000 VAC
0.05 A
16
Terminal
16
1000 VAC
0.05 A
16
Terminal
16
1500 VAC
0.05 A
16
Terminal
16
1000 VAC
0.05 A
16
1500 VAC
0.05 A
16
Power Supply Requirement
55 ms
25 ms 20 ms
20 ms 20 ms
Terminal
0.75 to 1.25 mm 2 AWG 15 to 19 16
10 ms
10 ms
Terminal
16
500 VAC
0.05 A
16
0.1 ms
0.2 ms
Terminal
16
500 VAC
0.05 A
16
10 ms
10 ms
Terminal
16
500 VAC
0.05 A
16
10 ms
10 ms
40-pin connector
32
500 VAC
0.08 A
32
10 ms
10 ms
40-pin connector
32
500 VAC
0.08 A
32
32
500 VAC
0.09 A
64
0.3 mm 2 AWG22
10 ms
10 ms
40-pin connector
10 ms
10 ms
40-pin connector
32
500 VAC
0.09 A
64
1.5 ms
3 ms
40-pin connector
32
500 VAC
0.075 A
32
10 ms
10 ms
Terminal
16
1000 VAC
0.05 A
16
16
1000 VAC
0.05 A
16
0.75 to 1.25 mm AWG15 to 19
2
0.4 ms
0.5 ms
Terminal
10 ms
10 ms
Terminal
16
1000 VAC
0.05 A
16
10 ms
10 ms
37-pin connector
32
1000 VAC
0.08 A
32
10 ms
10 ms
37-pin connector
32
1000 VAC
0.08 A
32
0.4 ms
0.4 ms
24-pin connector
500 VAC
0.08 A
16/32/48/64
0.3 mm 2 AWG22
2–4
SELV power supply is required
Page 17
2. MODULE SPECIFICATIONS MELSEC-A 2.2.2
Output modules Specifications of output modules are shown in the following table.
Model
Type
No. of Rated Load Voltage Points
Max. Output Response Time Max. Load Current
Dielectric Withstand Voltage OFF to ON
A1SY10
Relay output
16
240 VAC, 50/60 Hz 24 VDC
2 A/pt, 8 A/com
1500 VAC
Relay output (for 24 VDC)
16
120 VAC, 24 VDC
2 A/pt, 8 A/com
AC terminal-Relay coil, 5 VAC
1780 VAC
A1SY10EU
Relay coil, 5 VAC
500 VAC
AC terminal-Relay coil, 5 VAC
2830 VAC
Relay coil, 5 VAC
500 VAC
A1SY14EU
Relay output
12
240 VAC, 24 VDC
2 A/pt, 8 A/com
A1SY18A
Relay output
8
240 VAC, 50/60 Hz 24 VDC
2 A/pt, 8 A/module
1500 VAC
Relay output
8
240 VAC, 24 VDC
2 A/pt
AC terminal-Relay coil, 5 VAC
2830 VAC
A1SY18AEU
Relay coil, 5 VAC
500 VAC
A1SY22
Triac output
A1SY28A
Triac output
A1SY28EU
Triac output
A1SY40 A1SY41
12 ms
10 ms
12 ms
10 ms
12 ms
10 ms
12 ms
10 ms
12 ms
1 ms
0.5 cycle + 1 ms
0.6 A/pt, 2.4 A/com
8
240 VAC, 50/60 Hz
1 A/pt, 4 A/module
1500 VAC
1 ms
0.5 cycle + 1 ms
8
100 - 240 VAC
0.6 A/pt, 1.9 A/com
2830 VAC
1 ms
0.5 cycle + 1 ms
16
12/24 VDC
0.1 A/pt, 0.8 A/com
2 ms
2 ms
32
12/24 VDC
0.1 A/pt, 2 A/com
2 ms
2 ms
A1SY42
64
12/24 VDC
0.1 A/pt, 1.6 A/com
2 ms
2 ms
A1SY50
16
12/24 VDC
0.5 A/pt, 2 A/com
2 ms
2 ms
16
24 VDC
2 A/pt, 4 A/com
2 ms
2 ms
A1SY60E A1SY68A
Transistor output
1500 VAC
10 ms
240 VAC, 50/60 Hz
A1SY60
16
ON to OFF
500 VAC 16
5/12/24 VDC
2 A/pt, 4 A/com
3 ms
10 ms
8
5/12/24 VDC
2 A/pt
3 ms
10 ms
A1SY71
32
5/12 VDC
16 mA/pt, 256 mA/com
1 ms
1 ms
A1SY80
16
12/24 VDC
0.8 A/pt, 3.2 A/com
2 ms
2 ms
A1SY81
32
12/24 VDC
0.1 A/pt, 2 A/com
2 ms
2 ms
0.5ms
1.5ms
2 ms
2 ms
A1SY81EP
32
12/24 VDC
0.1 A/pt, 2 A/com 0.05 A/pt, 1.6 A/com
A1S42Y
64
12/24 VDC
0.1 A/pt
2–5
Page 18
2. MODULE SPECIFICATIONS MELSEC-A
Field Wiring
Applicable Wire Size
Points/ Common
Surge Suppression
External Power Supply
Noise Durability
Fuse Rating
Current
Internal Current Consumption (5 VDC) Requirement
No of Occupied Points
Terminal
8
None
None
1000 VAC
0.09 A
0.12 A
16
Terminal
8
None
None
1000 VAC
0.09 A
0.12 A
16
Terminal
4
None
None
1000 VAC
0.1 A
0.12 A
16
1
None
None
1000 VAC
0.075 A
0.24 A
16
None
None
1000 VAC
0.75 A
0.24 A
16
0.02 A
0.27 A
16
Terminal
0.75 to 1.25 mm 2 AWG15 to 19
Terminal
SELV power supply required
Terminal
8
CR
5A
1500 VAC
Terminal
1
CR
None
1500 VAC
0.13 A
16
Terminal
4
CR
None
1000 VAC
0.27 A
16
8
Zener diode
1.6 A
500 VAC
0.08 A
0.27 A
16
32
Zener diode
3.2 A
500 VAC
0.08 A
0.5 A
32
32
Zener diode
3.2 A
500 VAC
0.08 A
0.93 A
64
Terminal 40-pin connector 40-pin connector
2
0.3 mm AWG22
Terminal Terminal Terminal
0.75 to 1.25 mm 2 AWG15 to 19
Terminal
8
Zener diode
3.2 A
500 VAC
0.06 A
0.12 A
16
8
Zener diode
5A
500 VAC
0.015 A
0.12 A
16
8
Zener diode
7A
500 VAC
0.01 A
1
Zener diode
None
500 VAC
32
None
1.6 A
500 VAC
0.2 A
16
0.11 A
16
0.15 A
0.4 A
32
SELV power supply required
40-pin connector.
0.3mm 2 AWG22
Terminal
0.75 to 8 1.25 mm 2 AWG15 to 19
Zener diode
5A
1000 VAC
0.02 A
0.12 A
16
32
Zener diode
3.2 A
1000 VAC
0.08 A
0.5 A
32
32
Clamping diode
None
1000VAC
0.08A
0.5A
32
None
1.6 A
500 VAC
0.08 A
0.1 A
16/32/48/64
37-pin connector 37-pin connector 24-pin connector
0.3 mm 2 AWG22
2–6
Page 19
2. MODULE SPECIFICATIONS MELSEC-A 2.2.3
Input/output combined modules Specifications of input/output combined modules are shown in the following table. (1)
Input specifications Operating Voltagee
Model
A1SH42 A1SX48Y18
No. of Points
Type
DC input (sink type)
A1SX48Y58
Type
Input Current
32
12/24 VDC
2/5 mA
8
24 VDC
7 mA
8
24 VDC
7 mA
(2) Model
Rated Input Voltage
Insulation Withstand Voltage
500 VAC
ON Voltage
OFF Voltage
Maximum Simultaneous Input Points (Percentage Simultaneously ON)
8 VDC or higher
4 VDC or lower
60% (24 VDC)
14 VDC or higher
6.5 VDC or lower
100% (26.4 VDC)
14 VDC or higher
6.5 VDC or lower
100% (26.4 VDC)
Output specifications
No. of Points
Rated Load Voltage
A1SH42
Transistor output
32
12/24 VDC
A1SX48Y18
Relay output
8
A1SX48Y58
Transistor output
8
12/24 VDC
Max. Load Current 0.1 A/pt, 0.8 A/com
Dielectric Withstand Voltage
Max. Output Response Time OFF to ON
ON to OFF
500 VAC
0.4 ms
0.4 ms
2 A/pt, 240 VAC, 50/60 Hz 24 VDC 8 A/com
1500 VAC
10 ms
12 ms
0.5 A/pt, 2 A/com
500 VAC
2 ms
2 ms
2–7
Page 20
2. MODULE SPECIFICATIONS MELSEC-A
Max. Response Time
OFF to ON
ON to OFF
10 ms
10 ms
40-pin connector
0.3 mm 2 AWG22
10 ms
10 ms
Terminal
10 ms
10 ms
Terminal
0.75 to 1.25 mm 2 AWG15 to 19
Field Wiring
Applicable Wire Size
40-pin connector
0.3 mm 2 AWG22
Terminal
0.75 to 1.25 mm 2 AWG 15 to 19
Terminal
Noise Durability
Internal Current Consumption (5 VDC)
32
500 VAC
0.05 A
32
8
500 VAC
0.05 A
16
8
500 VAC
0.05 A
16
Applicable Wire Size
Field Wiring
Points/ Common
Points/ Common
Power Supply Requirement
SELV power supply required
External Power Supply
Surge Suppression
Fuse Rating
32
None
None
500 VAC
0.08 A
8
Zener diode
3.2 A
1000 VAC
0.045 A
8
None
None
500 VAC
0.06 A
2–8
Noise Durability
No. of Occupied Points
Current
Requirement
SELV power supply required
Page 21
MEMO