Page 12

1. GENERAL SPECIFICATIONS 1.

MELSEC-A

GENERAL SPECIFICATIONS This product has been designed to be installed in the following environmental conditions. Please place the product in places where environmental conditions satisfies the specifications. Item

Specifications

Ambient operating temperature

0 to 55°C

Ambient storage temperature

-20 to 75°C

Ambient operating humidity

10 to 90% RH, Non-condensing

Ambient storage humidity

10 to 90% RH, Non-condensing Frequency

Vibration resistance

Conforming to JIS B 3501, IEC 1131-2

Under intermittent vibration Under continuous vibration

Acceleration

Amplitude

10 to 57Hz, 0.075mm (0.003inch)

57 to 150Hz

9.8m/s 2 {1G}, 10 to 57Hz, 0.035mm (0.001inch)

57 to 150Hz

4.9m/s2 {0.5G}, No. of sweeps 10 times each in X, Y, Z directions (for 80 min.)

Conforming to JIS B3501, IEC 1131-2 (147m/s 2 {15G}, 3 times in each of 3 directions X Y Z)

Shock resistance Operating ambience

No corrosive gases

Operating elevation

2000m (6562 feet) max.

Installation location

Control panel

Over voltage category * 1

II max.

Pollution level * 2

2 max.

*1:

This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.

*2:

This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally.

1–1

Page 13

2. MODULE SPECIFICATIONS MELSEC-A 2.

MODULE SPECIFICATIONS

2.1

Power Supply Modules Specifications of power supply modules are shown in the following table Specifications Item A161P

A1S62P

Base loading slot

A1S63P

Power supply module loading slot 100 to 120 VAC+10%/-15%(85 to 132 VAC)

24 VDC +30%/-35% (15.6 to 31.2VDC)

Rated input voltage 200 to 240 VAC+10%/-15%(170 to 264 VAC) 50/60 Hz ±3%

Rated input frequency

105 VA

41 Ω

20 A 8 ms or lower

81 A 1 ms or lower

Max. input apparent power Inrush current

5 VDC

5A

3A

5A

24 VDC±10%

0.6 A

5 VDC

5.5 A or higher

3.3 A or higher

5.5 A or higher

24 VDC

0.66 A or higher

Rated output current

Overcurrent protection

5 VDC

5.5 to 6.5 V

Overvoltage protection

24 VDC Efficiency

65% or higher

Allowable momentary power failure time *3

Dielectric withstand voltage

20ms or lower

1ms or lower

Between primary and 5 VDC

1500 VAC *1

1500 VAC *1

500 VAC

Between primary and 24 VDC

1500 VAC *1

5M Ω or highter at insulation resistance tester

Insulation resistor

Noise voltage 1500Vp-p, Noise width 1 µs, Noise frequency 25 to 60Hz (noise simulator condition)

Noise durability

Power indication

Noise voltage 500Vp-p, Noise width 1 µs, Noise frequency 25 to 60Hz (noise simulator condition)

Power LED indication (light at the time of output of 5VDC)

Terminal screw size

M3.5 × 7

Applicable wire size

0.75 to 2mm 2 (AWG18 to 14)

Applicable solderless terminal

RAV1.25 to 3.5, RAV2 to 3.5

Applicable tightenig torque

59 to 88 N⋅cm (6 to 9kg⋅cm) 130 × 55 × 93.6 (5.12 × 2.17 × 3.69)

External dimension mm (inch) Weight kg (lb)

0.53 (1.17)

0.55 (1.21)

0.5 (1.1)

*1: Overcurrent protection The overcurrent protection device shuts off the 5V, 24 VDC circuit and stops the system if the current flowing in the circuit exceeds the specified value. When this device is activated, the power supply module LED is switched OFF or dimly lit. If this happens, eliminate the cause of the overcurrent and start up the system again. *2: Overvoltage protection The overvoltage protection device shuts off the 5 VDC circuit and stops the system if a voltage of 5.5 to 6.5 V is applied to the circuit. When this device is activated, the power supply module LED is switched OFF. If this happens, switch the input power OFF, then ON to restart the system. The power supply module must be changed if the system is not booted and the LED remains OFF. *3: Allowable momentary power interruption time This value indicates the momentary power interruption time allowed for the PC CPU and varies according to the power supply module used with the PC CPU module. The allowable momentary power interruption time for a system in which an A1S63P is used is defined as starting when the primary power supply of the 24 VDC stabilized power supply of the A1S63P is turned OFF and lasting until the 24 VDC becomes less than the specified voltage (15.6 VDC).

2–1

Page 14

2. MODULE SPECIFICATIONS MELSEC-A

A1S61PEU

A1S62PEU

A1S61PN

200 to 240 VAC (10%/-15%) (170 to 264VAC)

A1S62PN

100 to 240 VAC(10%/-15%) (85 to 264VAC) 50/60 Hz ±5% 105VA

40 A 8ms or lower

20A 8ms or lower

5A

3A

5A

3A

0.6A

0.6A

5.5 A or higher

3.3 A or higher

5.5 A or higher

3.3 A or higher

0.66A or higher

0.66 A or higher

20ms or higher 1780 VAC

1780 VAC

1780 VAC

AC across input/LG and output/FG 2830VAC rms/3cycle (2000m)

5M Ω or highter at insulation resistance tester

AC across input/LG and output/FG5M Ω or highter, mesured with a 500VDC insulation resistance tester

(1) Noise voltage 1500Vp-p, Noise width 1 µs, Noise frequency 25 to 60Hz (noise simulator condition) (2) Noise voltage IEC801-4, 2kV

RAV1.25 to 3.5, RAV2 to 3.5

RAV1.25 to 4, RAV2 to 4

59 to 88 N⋅cm (6 to 9 kg⋅cm)

83 to 113 N⋅cm (8.5 to 11.5 kg⋅cm)

130 × 55 × 93.6 (5.12 × 2.17 × 3.69)

130 × 54.5 × 93.6 (5.12 × 2.15 × 3.69)

0.53 (1.17)

0.55 (1.21)

0.60(1.32)

*4: A1S61PEU and A1S62PEU comply with EN61010-1 and safety aspects of IEC1131-2 to meet the Low Voltage Directive which will be mandatory from the 1st of January 1997. *5: Do not apply over 400 Voltage between AC and LG as the Varistor is installed between the AC and LG.

2–2

Page 15

2. MODULE SPECIFICATIONS MELSEC-A 2.2

Digital I/O Modules

2.2.1

Input modules Specifications of input modules are shown in the following table. Operating Voltage

Model

Type

A1SX10 A1SX10EU

No. of Points

16 AC input

Rated Input Voltage

100 to 120 VAC, 50/60 Hz

16

A1SX20

16

A1SX20EU

16

200 to 240 VAC, 50/60 Hz

Input Current

Dielectric Withstand Voltage

6 mA

1500 VAC

7 mA

1780 VAC

9 mA

1500 VAC

11 mA

2830 VAC

ON Voltage

80 VAC or higher

OFF Voltage

30 VAC or lower

Maximum Simultaneous Input Points (Percentage Simultaneously ON) 100% (110 VAC) 60% (132 VAC) 100%

80 VAC or higher

30 VAC or lower

60% (220 VAC)

16

12/24 VAC, 50/60 Hz 12/24 VDC

4.2/8.6 mA

7 VAC/VDC or higher

2.7 VAC/VDC or lower

75% (26.4 VAC)

A1SX40

16

12/24 VDC

3/7 mA

8 VDC or higher

4 VDC or lower

100% (26.4 VDC)

A1SX40-S1

16

24 VDC

7 mA

14 VDC or higher

6.5 VDC or lower

100% (26.4 VDC)

A1SX40-S2

16

24 VDC

7 mA

14 VDC or higher

6.5 VDC or lower

100% (26.4 VDC)

32

12/24 VDC

3/7 mA

8 VDC or higher

4 VDC or lower 60% (26.4 VDC)

A1SX41-S2

32

24 VDC

7 mA

14 VDC or higher

6.5 VDC or lower

A1SX42

64

12/24 VDC

2/5 mA

8 VDC or higher

4 VDC or lower 50% (24 VDC)

A1SX42-S2

64

24 VDC

5 mA

17.5 VDC or higher

7 VDC or lower 50% (24 VDC)

A1SX71

32

5/12 VDC

1.2/3.3 mA

3.5 VDC or higher

1 VDC or lower 100%

A1SX80

16

12/24 VDC

3/7 mA

8 VDC or higher

4 VDC or lower

100% (26.4 VDC)

16

24 VDC

7 mA

17 VDC or higher

5 VDC or lower

100% (26.4 VDC)

A1DX80-S2

16

24 VDC

7 mA

13 VDC or higher

6 VDC or lower

100% (26.4 VDC)

A1SX81

32

12/24 VDC

3/7 mA

8 VDC or higher

4 VDC or lower 60% (26.4 VDC)

A1SX81-S2

32

24 VDC

7 mA

13 VDC or higher

6 VDC or lower 60% (26.4 VDC)

16/32/ 48/64

12/24 VDC

4/9 mA

8 VDC or higher

4 VDC or lower

A1SX30

A1SX41

A1SX80-S1

A1S42X

AC/DC input

DC input (sink type)

DC input (sink/source)

DC input (dynamic)

2–3

500 VAC

60% (26.4 VDC)

100% (26.4 VDC)

Page 16

2. MODULE SPECIFICATIONS MELSEC-A

Specifications of input modules are shown in the following table. Max. Response Time Field Wiring OFF to ON

ON to OFF

20 ms

35 ms

30 ms

Applicable Wire Size

Points/ Common

Noise Immunity

Internal Current Consumption (5 VDC)

No. of Occupied Points

Terminal

16

1000 VAC

0.05 A

16

Terminal

16

1000 VAC

0.05 A

16

Terminal

16

1500 VAC

0.05 A

16

Terminal

16

1000 VAC

0.05 A

16

1500 VAC

0.05 A

16

Power Supply Requirement

55 ms

25 ms 20 ms

20 ms 20 ms

Terminal

0.75 to 1.25 mm 2 AWG 15 to 19 16

10 ms

10 ms

Terminal

16

500 VAC

0.05 A

16

0.1 ms

0.2 ms

Terminal

16

500 VAC

0.05 A

16

10 ms

10 ms

Terminal

16

500 VAC

0.05 A

16

10 ms

10 ms

40-pin connector

32

500 VAC

0.08 A

32

10 ms

10 ms

40-pin connector

32

500 VAC

0.08 A

32

32

500 VAC

0.09 A

64

0.3 mm 2 AWG22

10 ms

10 ms

40-pin connector

10 ms

10 ms

40-pin connector

32

500 VAC

0.09 A

64

1.5 ms

3 ms

40-pin connector

32

500 VAC

0.075 A

32

10 ms

10 ms

Terminal

16

1000 VAC

0.05 A

16

16

1000 VAC

0.05 A

16

0.75 to 1.25 mm AWG15 to 19

2

0.4 ms

0.5 ms

Terminal

10 ms

10 ms

Terminal

16

1000 VAC

0.05 A

16

10 ms

10 ms

37-pin connector

32

1000 VAC

0.08 A

32

10 ms

10 ms

37-pin connector

32

1000 VAC

0.08 A

32

0.4 ms

0.4 ms

24-pin connector

500 VAC

0.08 A

16/32/48/64

0.3 mm 2 AWG22

2–4

SELV power supply is required

Page 17

2. MODULE SPECIFICATIONS MELSEC-A 2.2.2

Output modules Specifications of output modules are shown in the following table.

Model

Type

No. of Rated Load Voltage Points

Max. Output Response Time Max. Load Current

Dielectric Withstand Voltage OFF to ON

A1SY10

Relay output

16

240 VAC, 50/60 Hz 24 VDC

2 A/pt, 8 A/com

1500 VAC

Relay output (for 24 VDC)

16

120 VAC, 24 VDC

2 A/pt, 8 A/com

AC terminal-Relay coil, 5 VAC

1780 VAC

A1SY10EU

Relay coil, 5 VAC

500 VAC

AC terminal-Relay coil, 5 VAC

2830 VAC

Relay coil, 5 VAC

500 VAC

A1SY14EU

Relay output

12

240 VAC, 24 VDC

2 A/pt, 8 A/com

A1SY18A

Relay output

8

240 VAC, 50/60 Hz 24 VDC

2 A/pt, 8 A/module

1500 VAC

Relay output

8

240 VAC, 24 VDC

2 A/pt

AC terminal-Relay coil, 5 VAC

2830 VAC

A1SY18AEU

Relay coil, 5 VAC

500 VAC

A1SY22

Triac output

A1SY28A

Triac output

A1SY28EU

Triac output

A1SY40 A1SY41

12 ms

10 ms

12 ms

10 ms

12 ms

10 ms

12 ms

10 ms

12 ms

1 ms

0.5 cycle + 1 ms

0.6 A/pt, 2.4 A/com

8

240 VAC, 50/60 Hz

1 A/pt, 4 A/module

1500 VAC

1 ms

0.5 cycle + 1 ms

8

100 - 240 VAC

0.6 A/pt, 1.9 A/com

2830 VAC

1 ms

0.5 cycle + 1 ms

16

12/24 VDC

0.1 A/pt, 0.8 A/com

2 ms

2 ms

32

12/24 VDC

0.1 A/pt, 2 A/com

2 ms

2 ms

A1SY42

64

12/24 VDC

0.1 A/pt, 1.6 A/com

2 ms

2 ms

A1SY50

16

12/24 VDC

0.5 A/pt, 2 A/com

2 ms

2 ms

16

24 VDC

2 A/pt, 4 A/com

2 ms

2 ms

A1SY60E A1SY68A

Transistor output

1500 VAC

10 ms

240 VAC, 50/60 Hz

A1SY60

16

ON to OFF

500 VAC 16

5/12/24 VDC

2 A/pt, 4 A/com

3 ms

10 ms

8

5/12/24 VDC

2 A/pt

3 ms

10 ms

A1SY71

32

5/12 VDC

16 mA/pt, 256 mA/com

1 ms

1 ms

A1SY80

16

12/24 VDC

0.8 A/pt, 3.2 A/com

2 ms

2 ms

A1SY81

32

12/24 VDC

0.1 A/pt, 2 A/com

2 ms

2 ms

0.5ms

1.5ms

2 ms

2 ms

A1SY81EP

32

12/24 VDC

0.1 A/pt, 2 A/com 0.05 A/pt, 1.6 A/com

A1S42Y

64

12/24 VDC

0.1 A/pt

2–5

Page 18

2. MODULE SPECIFICATIONS MELSEC-A

Field Wiring

Applicable Wire Size

Points/ Common

Surge Suppression

External Power Supply

Noise Durability

Fuse Rating

Current

Internal Current Consumption (5 VDC) Requirement

No of Occupied Points

Terminal

8

None

None

1000 VAC

0.09 A

0.12 A

16

Terminal

8

None

None

1000 VAC

0.09 A

0.12 A

16

Terminal

4

None

None

1000 VAC

0.1 A

0.12 A

16

1

None

None

1000 VAC

0.075 A

0.24 A

16

None

None

1000 VAC

0.75 A

0.24 A

16

0.02 A

0.27 A

16

Terminal

0.75 to 1.25 mm 2 AWG15 to 19

Terminal

SELV power supply required

Terminal

8

CR

5A

1500 VAC

Terminal

1

CR

None

1500 VAC

0.13 A

16

Terminal

4

CR

None

1000 VAC

0.27 A

16

8

Zener diode

1.6 A

500 VAC

0.08 A

0.27 A

16

32

Zener diode

3.2 A

500 VAC

0.08 A

0.5 A

32

32

Zener diode

3.2 A

500 VAC

0.08 A

0.93 A

64

Terminal 40-pin connector 40-pin connector

2

0.3 mm AWG22

Terminal Terminal Terminal

0.75 to 1.25 mm 2 AWG15 to 19

Terminal

8

Zener diode

3.2 A

500 VAC

0.06 A

0.12 A

16

8

Zener diode

5A

500 VAC

0.015 A

0.12 A

16

8

Zener diode

7A

500 VAC

0.01 A

1

Zener diode

None

500 VAC

32

None

1.6 A

500 VAC

0.2 A

16

0.11 A

16

0.15 A

0.4 A

32

SELV power supply required

40-pin connector.

0.3mm 2 AWG22

Terminal

0.75 to 8 1.25 mm 2 AWG15 to 19

Zener diode

5A

1000 VAC

0.02 A

0.12 A

16

32

Zener diode

3.2 A

1000 VAC

0.08 A

0.5 A

32

32

Clamping diode

None

1000VAC

0.08A

0.5A

32

None

1.6 A

500 VAC

0.08 A

0.1 A

16/32/48/64

37-pin connector 37-pin connector 24-pin connector

0.3 mm 2 AWG22

2–6

Page 19

2. MODULE SPECIFICATIONS MELSEC-A 2.2.3

Input/output combined modules Specifications of input/output combined modules are shown in the following table. (1)

Input specifications Operating Voltagee

Model

A1SH42 A1SX48Y18

No. of Points

Type

DC input (sink type)

A1SX48Y58

Type

Input Current

32

12/24 VDC

2/5 mA

8

24 VDC

7 mA

8

24 VDC

7 mA

(2) Model

Rated Input Voltage

Insulation Withstand Voltage

500 VAC

ON Voltage

OFF Voltage

Maximum Simultaneous Input Points (Percentage Simultaneously ON)

8 VDC or higher

4 VDC or lower

60% (24 VDC)

14 VDC or higher

6.5 VDC or lower

100% (26.4 VDC)

14 VDC or higher

6.5 VDC or lower

100% (26.4 VDC)

Output specifications

No. of Points

Rated Load Voltage

A1SH42

Transistor output

32

12/24 VDC

A1SX48Y18

Relay output

8

A1SX48Y58

Transistor output

8

12/24 VDC

Max. Load Current 0.1 A/pt, 0.8 A/com

Dielectric Withstand Voltage

Max. Output Response Time OFF to ON

ON to OFF

500 VAC

0.4 ms

0.4 ms

2 A/pt, 240 VAC, 50/60 Hz 24 VDC 8 A/com

1500 VAC

10 ms

12 ms

0.5 A/pt, 2 A/com

500 VAC

2 ms

2 ms

2–7

Page 20

2. MODULE SPECIFICATIONS MELSEC-A

Max. Response Time

OFF to ON

ON to OFF

10 ms

10 ms

40-pin connector

0.3 mm 2 AWG22

10 ms

10 ms

Terminal

10 ms

10 ms

Terminal

0.75 to 1.25 mm 2 AWG15 to 19

Field Wiring

Applicable Wire Size

40-pin connector

0.3 mm 2 AWG22

Terminal

0.75 to 1.25 mm 2 AWG 15 to 19

Terminal

Noise Durability

Internal Current Consumption (5 VDC)

32

500 VAC

0.05 A

32

8

500 VAC

0.05 A

16

8

500 VAC

0.05 A

16

Applicable Wire Size

Field Wiring

Points/ Common

Points/ Common

Power Supply Requirement

SELV power supply required

External Power Supply

Surge Suppression

Fuse Rating

32

None

None

500 VAC

0.08 A

8

Zener diode

3.2 A

1000 VAC

0.045 A

8

None

None

500 VAC

0.06 A

2–8

Noise Durability

No. of Occupied Points

Current

Requirement

SELV power supply required

Page 21