Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 11 of 13

MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware): 6. MAINTENANCE

Pages 66 to 69 of 85, from MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware)

The original document is the PDF (773 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi A1S61PN, Mitsubishi A1S63P, Mitsubishi A1SHCPU, Mitsubishi A1SX10, Mitsubishi A1SX40, Mitsubishi A1SX40-S1, Mitsubishi A1SX42, Mitsubishi A1SX42-S2, and 6 more models

Page 66

6. MAINTENANCE 6.

MAINTENANCE

6.1

General Safety Requirement

MELSEC-A

P DANGER Maintenance activities for the product should be carried out by trained and competent personnel. Do not touch terminals while the power is supplied. Cleaning or screw tightening must be carried out while the power is off.

E CAUTION Do not change program, move switch of RUN, STOP of PAUSE, nor proceed to force output during CPU RUN without confirmation of safety. Do not disassemble nor modify the products. Do not mount a module while the power is supplied. Connect the battery properly. Do not recharge, disassemble, heat, burn, short, nor solder the battery. Only use A6BAT for battery replacement.

6–1

Page 67

6. MAINTENANCE Daily Inspection

It is recommended to inspect items listed in the following table to keep the equipment running without trouble. No.

Check Item

Check Point

Judgment

Corrective Action

1

Base unit mounting conditions

Check for loose mounting screws and cover.

The base unit should be securely mounted.

Retighten screws.

2

Mounting conditions of I/O module, etc.

Check if the module is disengaged or the hook is securely engaged.

The hook should be securely engaged and the module should be positively mounted.

Securely engage the hook.

3

Connecting condition

Check for loose terminal screws.

Screws should not be loose.

Retigten terminal screws.

Check distance between solderless terminals.

Proper clearance should be provided between solderless terminals.

Correct.

Check connectors of extension cable.

Connections should not be loose.

Retighten connector mounting screws.

“POWER” LED

Check that the LED is ON.

ON (OFF indicates an error.)

Refer to User’s Manual

“RUN” LED

Check that the LED is ON during RUN.

ON (OFF or flash indicates an error.)

Refer to User’s Manual

“ERROR” LED

Check that the LED is ON when an error occurred.

OFF (ON when an error occurred.)

Refer to User’s Manual

Input LED

Check that the LED turns ON and OFF.

ON when input is ON. OFF when input is OFF. (Display, which is not as mentioned above, indicates an error.)

Refer to User’s Manual

Output LED

Check that the LED turns ON and OFF.

ON when output is ON. OFF when output is OFF. (Display, which is not as mentioned above, indicates an error)

Refer to User’s Manual

4

CPU module indicator lamps

6.2

MELSEC-A

6–2

Page 68

6. MAINTENANCE Periodic Inspection

This section explains the inspection items which are to be checked every six months to one year. This inspection should also be performed when the equipment is moved or modified or the wiring is changed.

2

3

Ambient humidity

Measure with thermometer and hygrometer. Measure corrosive gas.

Ambience

Judgment 0 to 55 °C 10 to 90 %RH

Corrective Action When PC is used inside a panel, the temperature in the panel is ambient temperature.

There should be no corrosive gases.

85 to 132 VAC

Change supply power . Change transformer tap.

Line voltage check.

Measure voltage across 100/200 VAC terminal.

Looseness, play

Move the unit.

The module should be mounted securely and positively.

Retighten screws.

Ingress of dust or foreign material

Visual check.

There should be no dust or foreign material, in the vicinity of the PC.

Remove and clean.

Loose terminal screws

Retighten.

Connectors should not be loose.

Retighten.

Distances between solderless terminals.

Visual check.

Proper clearance should be provided between solderless terminals.

Correct.

Loose connector

Visual check.

Connectors should not be loose.

Retighten connector mounting screws.

Check battery status by monitoring special auxiliary relays M9006 and M9007. Retighten battery if necessary.

Preventive maintenance

If battery capacity reduction is not indicated, change the battery when specified service life is exceeded.

4

5

Ambient temperature

Checking Method

Mounting conditions

1

Check Item Ambient environment

No.

Connecting conditions

6.3

MELSEC-A

Battery

6–3

170 to 264 VAC

Page 69

6. MAINTENANCE 6.4

MELSEC-A

Battery Replacement A lithium battery is used in a CPU module to keep program and data during power failure time. When the voltage of battery comes low, M9006 and/or M9007 internal diagnostic signal come on. Please replace the battery as soon as possible once the signal is activated.

6–4