5. FAIL-SAFE CONSTRUCTIONS 5.
FAIL-SAFE CONSTRUCTIONS
5.1
General Safety Requirements
MELSEC-A
P DANGER Safety circuitry must be so designed and constructed externally that an entire system stays in safe in case of a external power supply failure and/or PC failure. In particular, the following safety circuitry are required to constructed outside of the PC. (1)
Emergency stop circuit, protection circuit, interlocking circuit for contrary operations such as forward and reverse movement, and hardware stroke limit circuit for positioning controls must be constructed externally.
(2)
In case of hardware failure which PC CPU cannot detect occurs, all or some output signals could be turned on without program instructions. An external safety circuitry must be so constructed that safety of equipment or machine can be protected from such case. Please refer to Sub-clause 5.2 for details.
(3)
In some cases, relays or transistors used in output modules stay always ON or OFF as failure symptoms. If such failure could cause serious damage on persons or properties, those safety critical output signals must be externally monitored.
If the power to the PC is turned ON after turning ON the external power supply used for the process control with the DC output module, the DC output module may make an erroneous output for an instant. Take the following procedures for power up of the equipment, in order to prevent such erroneous input and output to/from the PC.
5.2
(1)
Turn ON the power to the PC.
(2)
Turn ON the external power supply used for the process control.
(3)
Turn ON the START switch.
(4)
Turn ON the power to the output devices by using a program.
(5)
Confirm that all external power supplies are turned ON, and then, an I/O control program should be executed.
Fail-Safe Circuitry Against to Failure of the PC Though Mitsubishi PCs are manufactured under strict quality control, they may cause failure or abnormal operations due to unspecific reasons. To prevent the abnormal operation of the whole system, machine breakdown, and accidents, fail-safe circuitry against to failure of the PC must be constructed outside the PC. The following page gives an example of system designing that conforms to the explanation mentioned above and an example of fail-safe measures when the PC causes a failure.
5โ1
Page 63
5. FAIL-SAFE CONSTRUCTIONS (1)
MELSEC-A
System design circuit example
Mixed AC and DC
ALL AC POWER
POWER
TRANSFORMER TRANSFORMER FUSE
TRANSFORMER
FUSE FUSE
FUSE
FUSE
FUSE
CPU CPU
M9006 Ym
M9006
M9039 *5
Yn Y1
RA2
Yn
(-) (+)
*6
TM
M9084 PROGRAM
MC
DC POWER SUPPLY
XM
XM
START SW
Ym M9039
*1
RA1
No
MC STOP SW INPUT MODULE XM
START
TM MC1 M9084 TM No M10 M10 PROGRAM
FUSE
FUSE *1
RA1 MC
MC
STOP SW
*2: Low battery alarm (Lamp or buzzer)
INPUT MODULE RA2
OUTPUT MODULE
XM
*3: RA1 switched ON by M9039 (run monitor relay)
*2
Ym L
OUTPUT MODULE
*3
Yn
Ym
RA1
*2 L *7
Yn
MC
MC
RA1
OUTPUT MODULE
OUTPUT MODULE
MC
MC *4
MC2
Y1
MC1
*8 MC1
RA2
*6: Set time for DC power supply to be established. *8: Interlock circuits as necessary.
MC2
MC2
In the case of an emergency stop or a stop caused by a limit switch.
*7: ON when run by M9039
RA2 MC1
MC1
*4: Power to output equipment switched OFF when the STOP signal is given.
*5: Input switched when power supply established.
*4 *4
*1: RUN/STOP circuit interlokked with RA1 (run monitor relay)
MC2
*8 Voltage relay is recommended
Provide external interlock circuits for conflicting operations, such as forward rotation and reverse rotation, and for parts that could damage the machine or cause accidents if no interlock were used.
For AC/DC
The power-ON procedure is as follows: For AC
1) Switch CPU to RUN.
1) Switch CPU to RUN.
2) Set the ON the power.
2) Set the ON the power.
3) Turn ON the start switch.
3) Turn ON the start switch.
4) When DC power is established, RA2 goes ON.
4) When the magnetic contactor (MC) comes in, the output equipment is powered and may be driven by the program.
5) Timer (TM) times out after the DC power reaches 100%. (The TM set value should be the period of time from when RA2 goes ON to the establishment of 100% DC voltage. Set this value to approximately 0.5 seconds.) 6) When the magnetic contactor (MC) comes in, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.)
5โ2
Page 64
5. FAIL-SAFE CONSTRUCTIONS
MELSEC-A
Failure of a CPU or memory can be detected by the self diagnosis function. However, Failure of I/O control area may not be detected by the CPU. In such cases, all I/O points turn ON or OFF depending on a condition of problem, and normal operating conditions and operating safety cannot sometimes be maintained. Examples of fail-safe circuitry are described as follows: (a) Using on-delay and off-delay timers ON delay timer Internal program
Y00
T1
1 sec
OFF delay timer
M9032 Y00
T2
Y00
Y01
External load L
Y0F
L
1 sec MC
24 V 0.5 sec
0.5 sec 0V
24 VDC
Output module *1
CPU module
T1
T2 MC
*1: Y00 repeats turning ON and then OFF at 0.5 second intervals. Use a no-contact output module (transistor in the example shown above).
5โ3