MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware): 5. FAIL-SAFE CONSTRUCTIONS

Pages 62 to 65 of 85, from MELSEC A series Programmable Controller User's Manual, Type A1S(S1)/A1SC24-R2/A2S(S1)/A1SH/A2SHCPU(S1)/A2ASCPU(S1/S30/S60) (Hardware)

The original document is the PDF (773 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi A1S61PN, Mitsubishi A1S63P, Mitsubishi A1SHCPU, Mitsubishi A1SX10, Mitsubishi A1SX40, Mitsubishi A1SX40-S1, Mitsubishi A1SX42, Mitsubishi A1SX42-S2, and 6 more models

Page 62

5. FAIL-SAFE CONSTRUCTIONS 5.

FAIL-SAFE CONSTRUCTIONS

5.1

General Safety Requirements

MELSEC-A

P DANGER Safety circuitry must be so designed and constructed externally that an entire system stays in safe in case of a external power supply failure and/or PC failure. In particular, the following safety circuitry are required to constructed outside of the PC. (1)

Emergency stop circuit, protection circuit, interlocking circuit for contrary operations such as forward and reverse movement, and hardware stroke limit circuit for positioning controls must be constructed externally.

(2)

In case of hardware failure which PC CPU cannot detect occurs, all or some output signals could be turned on without program instructions. An external safety circuitry must be so constructed that safety of equipment or machine can be protected from such case. Please refer to Sub-clause 5.2 for details.

(3)

In some cases, relays or transistors used in output modules stay always ON or OFF as failure symptoms. If such failure could cause serious damage on persons or properties, those safety critical output signals must be externally monitored.

If the power to the PC is turned ON after turning ON the external power supply used for the process control with the DC output module, the DC output module may make an erroneous output for an instant. Take the following procedures for power up of the equipment, in order to prevent such erroneous input and output to/from the PC.

5.2

(1)

Turn ON the power to the PC.

(2)

Turn ON the external power supply used for the process control.

(3)

Turn ON the START switch.

(4)

Turn ON the power to the output devices by using a program.

(5)

Confirm that all external power supplies are turned ON, and then, an I/O control program should be executed.

Fail-Safe Circuitry Against to Failure of the PC Though Mitsubishi PCs are manufactured under strict quality control, they may cause failure or abnormal operations due to unspecific reasons. To prevent the abnormal operation of the whole system, machine breakdown, and accidents, fail-safe circuitry against to failure of the PC must be constructed outside the PC. The following page gives an example of system designing that conforms to the explanation mentioned above and an example of fail-safe measures when the PC causes a failure.

5โ€“1

Page 63

5. FAIL-SAFE CONSTRUCTIONS (1)

MELSEC-A

System design circuit example

Mixed AC and DC

ALL AC POWER

POWER

TRANSFORMER TRANSFORMER FUSE

TRANSFORMER

FUSE FUSE

FUSE

FUSE

FUSE

CPU CPU

M9006 Ym

M9006

M9039 *5

Yn Y1

RA2

Yn

(-) (+)

*6

TM

M9084 PROGRAM

MC

DC POWER SUPPLY

XM

XM

START SW

Ym M9039

*1

RA1

No

MC STOP SW INPUT MODULE XM

START

TM MC1 M9084 TM No M10 M10 PROGRAM

FUSE

FUSE *1

RA1 MC

MC

STOP SW

*2: Low battery alarm (Lamp or buzzer)

INPUT MODULE RA2

OUTPUT MODULE

XM

*3: RA1 switched ON by M9039 (run monitor relay)

*2

Ym L

OUTPUT MODULE

*3

Yn

Ym

RA1

*2 L *7

Yn

MC

MC

RA1

OUTPUT MODULE

OUTPUT MODULE

MC

MC *4

MC2

Y1

MC1

*8 MC1

RA2

*6: Set time for DC power supply to be established. *8: Interlock circuits as necessary.

MC2

MC2

In the case of an emergency stop or a stop caused by a limit switch.

*7: ON when run by M9039

RA2 MC1

MC1

*4: Power to output equipment switched OFF when the STOP signal is given.

*5: Input switched when power supply established.

*4 *4

*1: RUN/STOP circuit interlokked with RA1 (run monitor relay)

MC2

*8 Voltage relay is recommended

Provide external interlock circuits for conflicting operations, such as forward rotation and reverse rotation, and for parts that could damage the machine or cause accidents if no interlock were used.

For AC/DC

The power-ON procedure is as follows: For AC

1) Switch CPU to RUN.

1) Switch CPU to RUN.

2) Set the ON the power.

2) Set the ON the power.

3) Turn ON the start switch.

3) Turn ON the start switch.

4) When DC power is established, RA2 goes ON.

4) When the magnetic contactor (MC) comes in, the output equipment is powered and may be driven by the program.

5) Timer (TM) times out after the DC power reaches 100%. (The TM set value should be the period of time from when RA2 goes ON to the establishment of 100% DC voltage. Set this value to approximately 0.5 seconds.) 6) When the magnetic contactor (MC) comes in, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.)

5โ€“2

Page 64

5. FAIL-SAFE CONSTRUCTIONS

MELSEC-A

Failure of a CPU or memory can be detected by the self diagnosis function. However, Failure of I/O control area may not be detected by the CPU. In such cases, all I/O points turn ON or OFF depending on a condition of problem, and normal operating conditions and operating safety cannot sometimes be maintained. Examples of fail-safe circuitry are described as follows: (a) Using on-delay and off-delay timers ON delay timer Internal program

Y00

T1

1 sec

OFF delay timer

M9032 Y00

T2

Y00

Y01

External load L

Y0F

L

1 sec MC

24 V 0.5 sec

0.5 sec 0V

24 VDC

Output module *1

CPU module

T1

T2 MC

*1: Y00 repeats turning ON and then OFF at 0.5 second intervals. Use a no-contact output module (transistor in the example shown above).

5โ€“3

Page 65

MEMO