__8. 1/0 CONNECTION TROUBLESHOOTING /, MELSEC-AA
8. 1/0 CONNECTION TROUBLESHOOTING
8.1 Input Wiring Troubieshooting
This section describes possible problems with the input circuit and corrective actions.
Table 8.1 input Wiring Troubleshooting (Continue)
Condition
Cause
Corrective Action
Exampte 7
AC input signal does not turn off. {input LED may remain on or flicker)
@ Input device leakage current.
AC input, c Input {jr : Leakage current } | module
Power supply
@ Connect a CR network across input to drop the voltage below the input modules OFF threshold.
AC input
Input module
Use C = 0.1 to 0.47 F and R = 47 to 1209 (1/2W)
Example 2
AC input signal does not turn off. (Input LED may remain on or flicker)
@ Leakage current due to contact switch with neon indicator.
AC input
Input l if , Leakage current module
Power supply
@ As example 14, or. @ Construct independent indicator circuit.
Example 3
AC input signa! dogs not turn off. {Input LED may remain on or flicker)
@ Leakage current due to line capacity of wiring cable. (Line capacity of twisted pair wire is approx. 100 PF/m.)
AC input of Leakage } | Input ? ~~ current module + ~s) ~*~" Power supply
@ As Example 1.
@ Note that moving the power supply to the input device end of the cable will prevent leakage current from being generated.
AC input, | * 4 i a Input j ‘ o™ module tole i __. hws Power supply
Page 103
8. /0 CONNECTION TROUBLESHOOTING /MELSEC-Al
Table 8.1 Input Wiring Troubleshooting (Continued)
Condition Cause Corrective Action
@ Leakage current due to contact switch with| @ Connect a resistor across the input and COM
LED indicator. to drop the voltage below the input modules OFF threshold.
DC input (sink) DC input (sink) OC input signal, -~ - --- P ' does not turn off. f > = xample 4] (Input LED ma ke. j remainon or” { Leakage current Input resistor input flicker) ? a module a modure, t TT! ~ Te
* Sample resistor value calculation given on next page.
® Current flow due to the use of two power]! @ Use single power supply.
supplies. @ Use diode as shown below: DC input signal does not turn off. op vv = Example 5] (Input LED may -(L)- Input -(L)- Input remain on or E 7yE2E it module E,y €&, “Eb module flicker) | | | q £, >E, Example:
Calculation for Example 4, - AXA0 I> Consider a contact switch with | Leakage current LED indicator connected to an “AE Input, al module AX40 module, giving a 4mA i} leakage current. 3.6kQ ', _ - - 24V DC
® The voltage Vis across terminal and common is obtained by the following expression:
Vis = 4 [mA] X 2.4 [KQ] = 9.6 [V] (The voltage drop across the LED may be ignored.)
The OFF threshold voltage is 6V so that the input will remain energized when the contact switch is open. Use resistor R as shown below:, __- - _ AX40 J st ? 1 | AES ( Current I R | af 4} + -J 3:62 | y 24V DC Input impedance 2.4KQ
8-2
Page 104
8. 1/0 CONNECTION TROUBLESHOOTING SJIMELSEC fA
@ Calculate the resistor value, R, as shown below: For an input voltage < 6V, current | must be:
(24° - 6[V]) + 3.6[kQ] = 5mA
Resistor R must be selected to give a current | > 5mA, @ Hence, for resistor, R
6[V} + R > 5, 2.5[mA]
6[V] + 2.5[mA] > R
2.4{kQ] > R
For R = 2kQ, the power capacity must be:
W = (applied voltage)/R (or W = (maximum current)? < R}
Resistor R terminal voltage is: eo 2.4X 2 24X2 a X = 5.58(V)
Therefore, the power capacity W of resistor R is W = (5.58[V})/2[kQ] = 0.075[W]
@ Use a safety factor of 3 to 5. Resistor should therefore be rated at 0.5 to 1W.
A3kQ, 0.5 to 1W resistor should therefore be connected across the relevant input terminal and its COM.
. 8-3
Page 105
8. 1/0 CONNECTION TROUBLESHOOTING /MELSE CA
8.2 Output Wiring Troubleshooting
Table 8:2 Output Wiring Troubleshooting (Continue}
Condition
Cause
Corrective Action
AC voltage ap- plied to output
@ Half wave rectification by load (typical of some solenoids).
AY22, AY23 Output module
@ Connect a resistor of several ten kQ to several hundred kQ across the load.
Note: This solution may lead to damage to the diode. Suitable output loads should be substituted for the existing solenoids.
Example 1 Cc load when out- i ® Current flow in direction © causes capacitor, C, to charge. Current flow in direction @ applies capacitor voltage plus E across 01 (Voltage = 2.2E {approx)). @ Leakage current due to built-in noise suppres- | @ Connect a R network across the load. sion. Where long cable runs between output mod- ule and load are used, there may be a leakage AY22,. AY23 current due to the line capacity. k 5 AC load dogs not Output module xample turn off. 7 (triac output) fi ( Leakage current, - - - _ Load | ‘ ee | @ Leakage current due to load noise suppressor. } @ Remove noise suppressor from both sides Output module of the load and connect a resistor. High frequency current . When wiring distance from output card to Load High frequency toad is long, there may be a leakage current corrent due to the line capacity. Load turns OFF Cc Example 3} with adetay AY22, AY23 Recommended resistance Put) |Output module Toad At 200 VAC: 10 to 20 KQ, 15 to 10 W é a J = tLoad } “@ Connect a resistor to both ends of CR timer. When wiring distance from output card to toad is long, there may be a leakage current due to the line capacity. AC load is o Ave a8 C-R type timer, utput module ~ Example 4| time constant » CR fluctuates. x timer PJ (triac output) ij Leakage current_» timer
R values will depend on the load.
Exampie 5
DC load does not turn off. Transister out- put with clamp diode
@ Current flow due to the use of two power supplies.
AY40, 41, 42 Output module}12/24V d8) 4 coon = 7 (b) il 1-4 Load
OV
@ When E: < Ez, current flows.
@ Use single power supply.
Use diode (a} as shown on the left.
When a relay (or similar load) is used, a free wheel diode should be connected across the load {see diode (b) on the left).
84
Page 106
8. 1/0 CONNECTION TROUBLESHOOTING
MELSEC-A
Table 8.2 Output Wiring Troubleshooting (Continued)
Condition
Cause
Corrective Action
Example 6
Load does not operate normal- ly {due to exter- nal shorting, etc.)
AY60EP, AY80EP, AY8iEP, AY82EP,
Externa! load malfunction or incorrect connection.
@ Check the external load.
@ Check voltage across the following terminals with output (Y) on.
@ If output voltage > 3V, check external load and wiring for short circuits.
b
Source driver
Load
Example 7
When an exter- nal switch is con- nected parallel between output and common, the voltage be- tween Y1 and COM1 does not increase to a load voltage (24 V) and drops to 0 to 24 V though output {Y1)} to which an exter- nal switch is not connected is turned OFF. Output voltage drops occur usually when toad L2 is alight load such as LED famp, photocou- pler, etc. (when a load current is 2 few mA).
AY40 AY4i AY42
Incorrect output due to parasitic transistor (Tr4). . I
'
LYO
‘ad q t [vs +
Y2 (4)
Trt is}
(tip hd
Tr2 E OFF
Tr3 E
OFF
| 73) t Nl co po
24V
01 Mi
Y2 is used to turn ON load L3 from either PC or PB.
When PB is turned ON, YO is turned ON, and Y1 is turned OFF by PC.
(4) L1 ({1} current) and L3 {{2) current) are turned ON
(2} Diode D1 is connected between emitters Tr1 to 4{E) and COM1, and electrical potentia! difference occurs at COM1.
{3) Transistors AY40 to 42 have parasitic transistors (Tr4}.
(4) Electrical potential difference above (2) is supplied between Tr4 base (B) and emitter (E}, and {3) base current flows.
{Tr4 is turned ON.)
(5) Collector current (4) flows due to (4), and the voltage of Yi drops to 0 to 24 V.
COM
Add diode D2 of IF=1A to output {Y2} to which an external switch is connected as shown in the figure above.
(This prevents (3), (4) current {in the left figure) from flowing.)
However, voltage drop increases 0.6 to 1 V when Y2 is turned ON.
Confirm the operating voltage of L3.
8-5