The text of a manual · part 3 of 15
Programmable Logic Controller User's Manual: I/O module type Building block: 1. NOTES ON SELECTING THE I/O MODULES
Pages 12 to 17 of 120, from Programmable Logic Controller User's Manual: I/O module type Building block
The original document is the PDF (3.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi AG62, Mitsubishi AX42 and Mitsubishi AY42
Page 12
“4, NOTES ON SELECTING THE !/O MODULES
1.1 GENERAL SPECIFICATIONS
Table 1.1 General specification item ‘Specifications Ambient operating ) temperature 0 to 50 °C Ambient storage ; temperature -20 to 75 °C
Ambient operating humidity
10 to 90 % RH, No-condensing
Ambient storage
10 to 90 % RH, No-condensing humidity Frequency | Acceleration | Amplitude sweeps Conforming |Under 10 to S7Hz 0.075mm . Vibration to JIS B intermittent {0.003in.} 10 times resistance 6501, vibration 57 to 150Hz | 9.8m/s%{1G eacn In IEC 1131-2 mis"t G} x, Y,Z Under 10 to 57Hz 00.35mm directions continuous {0.001in.) {for 80min.) vibration 57 to 150Hz | 4.9m/s*{1 G}
Shock resistance
Conforming to JIS B 3501, IEC 1131-2 (147 m/s*{15G}, 3 times in each of 3 directions X Y Z}
Operating No corrosive gases Operating 2000m (6562ft.) max. installation Contro! panel Pollution level *2 2. max.
*1: This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises. Category If applies to equipment for which electrical power is supplied from fixed facilitie withstand level for up to the rated voltage of 300 V is 2500 V.
s. The surge voltage
*2: This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected occasionally.
1-1
Page 13
1. NOTES ON SELECTING THE 1/0 MODULES /MELSEC-4
1.2 NOTES ON SELECTING THE !/O MODULES
(1) The maximum number of input points which may be switched ON at any one time (“Max. Simultaneously ON” in the following tables) for a 32 or 64 way module depends on the input voltage and ambient temperature as shown in the following diagrams.
Ambient Ambient Ambient (Example: AX60) temperature temperature = temperature 55°C Ambient temperature = 55°C s& ¥ x 45°C x J 100% 100% ne 1 Hy a Zz eS | =° ° = t ry o= < 3 80% ~ ~~~, ~~ ~~ == =~ - - tomes 3 60%+ - o 8 ! o°8 H Ss 5& H 25 ! gs =] =e: 55 <'o t i 2" + + 10.2V DC 20.4V 26.4V 85V DC | 121V 140V
85V/170V AC 120V/240V 132V/264V {60Hz}
(2) Triac output modules should be used instead of relay contact output modules when:
@ The outputs are being switched very frequently.
@ A large inductive load is being switched.
@ An inductive load with a low power factor is being switched.
The life of a relay switching any of the above conditions will be substantially reduced.
(3) The ON time and OFF time for any inductive load switched by an output module must be more than oné second.
(4) Beware of rush currents when an AY40, AY41 or AY42 output module is used to switch a load incorperating a DC/DC converter (e.g. a timer or counter).
Either connect a resistive or inductive toad in series with the load or use an AY50 or AY51 output module.
Resistor Load Inductance Load
Output Output | ae O | module | . module \ f, ~t
(5) The maximum number of output points which may be switched on at one time depends on the current capacity of the common terminal which, in turn, depends on the ambient temperature. Note that if certain output modules are installed next to a power supply module the current capacity of the common terminal must be de-rated. The de-rated current capacity is given in parentheses in the specification tables.
Page 14
1. NOTES ON SELECTING THE 1/0 MODULES / MELSEC-A
(6) Output modules fitted with on-board fuses will be protected by the fuses providing the following criteria are met:
Load ten Yotase; 12/24V DC Load 48V DC Load 100/200V AC Load
Wiring length 3m (118.1 1inch) 3m (118.7 1inch) 3m (118.1 1inch) minimum minimum minimum
Cable size 2mm? (14 AWG) 2mm? (14 AWG) 2mm (14 AWG) maximum maximum maximum
Short-circuit : .
current 20A maximum 8A maximum _ - _ - T paella, _ - _ _ 2kVA maximum
Where these criteria are not met and fuse protection is required an external “fast-blow” fuse should be provided. The following external fast-blow fuses are recommended. AC : HP fuse DC : MP fuse
(7} The relay life for relay output modules (AY10, AY10A, AY11, ww
AY13) is shown betow.
Relay output modules should be selected with reference to these characteristics and to the frequency of operation.
AKL AAA , XA
Q
200
AA Z LL
L 30V DC Rr Oms, - - ~» Switching fife (unit: 10,000 times) LLM LN Wa 77 Li Cc
120V AC COS$¢ =1
240V AC COS¢ =1 1 \\ \ . KAUN ‘heey loos | KYA 5 4100V to 120V DC . \ 1 tea? to 40ms N RN 30v DC RT 7ms 3 \ 120V AC COS¢ =0.4 1 \ \ 240V AC COS =0.4 2 x b \ 30V DC Ro 40ms
LZ
05 07 10 #420 «30 5.0
-__ - » Switching current (A)
1-3
Page 15
1. NOTES ON SELECTING THE I/O MODULES / MELSE ch
(8) When using a pressure displacement type connector jack (flat cable (pitch: 1.27 mm)) for an AX42 input unit or AY42 output unit, the following type connector jack should be prepared by the user. Consult your nearest Mitsubishi representative about the connector jack.
Type: FCN-367J040-AU/F (close end type, gold plated)
Connect cables referring to Sections 2.7 and 3.15 for pin arrangement and flat cable arrangement.
(9) The maximum number of output points which may be simultaneously on in the AY80EP, AY81EP or AY60EP output units varies with output current and ambient temperature as follows. {A} 0.84 (A) 45°C 51°C (60% ONSS°C "C40" 08 = ) os 20°C 32°C 35°C 41 ~ <3 ON 0.74 ra ' ¥ ‘ 2 06 ® 06 0.664 5 0.55A = N x & 3 - 4, 0.47A Ba 04 3 J 2 . Bm OA 20) 0.4A 5 s ‘NY <) } 0.284 02 0.2 0.1A 0 10 20 30 40 50 55 60 Tarc) 0 10 20 30 40 BO 5560 Tare) Ambient temperature Ambient temperature AY80EP AY81EP . {mA) (A) ; sc 16C 36°C 100 27C_ 34°C 37C_ 42°C 55°C. 100mA, 20 SSN a yeneeee -=3 (25% ON) RAY 25. ‘ % 1 <= # PP & Ww: 5 80 £ 1s Se oF 14a 5 = p> 3 2 |, ~2003, eo Pe) DB * se. ee ae % on ~ 3 a © 2 10 =<] £ = DQ 0.94 3 = PISS 0.8A OQ ° NNoza N 05 O.55A 40 \ 40mA 27mA _ 20 0 10 20 30 40 50 55 60 Ta{c) Ambient temperature 3mA 0 70 20 ) 65 Tat AY60EP eo 8 8S Talc)
Ambient temperature
AY82EP *70mA/point if ali of Yn8 X m to YAS X m+ 7 {n = 0, 1, 2, m = 0, 1) are on.
Page 16
1. NOTES ON SELECTING THE I/O MODULES /MELSEC-4
{10) The maximum number of output points which may be simultaneously on in the AY42-S3 (with fuse) varies with output current and ambient temperature as follows.
IO (mA) ‘ ° 100 29.6°C 36°C 80 ps < *1: Number of points simultaneously £ | 4. ON indicates the number per 3 60 NI common (32 points). 3 \Q47.2ma é 40 : 40.3mMA ! 30mA 20 L 0 }
10 20 30 40 50 55 28.5 Ta (C)
Ambient temperature
Consult your nearest supplier with the following YO module related parts and cable.
(1) Connector/terminal block converter module and cable /O wiring can be instalied using a termina! block by connecting a connector type I/O unit to a connector/terminal block converter module via a cabie.
Littl Connector/terminal block
[SS converter module a RREL (ASTBIIE IT AW AGTB Sse)
) Cable Connector type = (AC{1E°71B, AC(1E.71B-E) vO module [Supplier]
Consult your nearest Mitsubishi representative.
(2) ¥O cable (connectable) Wiring becomes easy by using I/O cable with connector which can be connected to 40-pin or 37-pin D subconnector of I/O unit. {Consult your nearest Mitsubishi representative with I/O cable with connector.} wn End treatment
(with ring mark fwith Y terminal/with round
Connector type _~ VO wnit
E~ Connector terminal/as cut, etc.) AX42, AH42, AX82 (soldered/solderiess/ Cable AY42, AY42-S3, S4 pressure displacement (separate wires/round/flat, etc.) AY72, AY82EP type)
4-5
Page 17
1. NOTES ON SELECTING THE I/O MODULES / MELSEC-A
(11) When using AXOIEU, AYCIEU, etc., if the wires are connected to the terminal block without using solderless terminals, observe the following points.
(a) Bare the end of insulated wires to expose about 6 to 8 mm of naked wire,
When making connections, ensure that bared wire dose project from the terminal block. If it dose, it may close the gap to a distance shorter than that required for insulation between the terminalis.
Terminal block ao” (barrier) insulation >| Bared tength: 6 to 8 mm (0.24 to 0.31 in.), ~_ ?
Connection to the terminal block (viewed from side)
Treatment of end of wire i
(b) If twisted wire is used, make sure that is dose not unravel.
1-6