Page 273

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

19.1 Specifications

11 High-Speed Counters

19. Display Module(FX3G-5DM)

12

•

Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.

•

•

Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric distributor. Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause equipment failures or malfunctions. - Display module, peripheral devices, expansion boards, and special adapters - Connector conversion adapter, extension blocks, and FX Series terminal blocks - Battery and memory cassette

14 Test Run, Maintenance, Troubleshooting

19.1

Specifications

15 Input/Output Powered Extension Units

19.1.1 Applicable PLC Model name FX3G Series

Applicability

16

Ver.1.10 or later

Input/Output Extension Blocks

19.1.2 Display/switch specifications Item Display device

17

Green LED backlight 16 letters (half-width character)

4 lines

Characters

Alphabets, Numbers, Japanese character

Language for menu display

English/Japanese

Extension Power Supply Unit

Number of letters

Button

Specifications STN monochrome liquid crystal display

Backlight Displaed letters

13 Wiring for Various Uses

STARTUP AND MAINTENANCE PRECAUTIONS

Output Wiring

STARTUP AND MAINTENANCE PRECAUTIONS

4 operation buttons (OK, ESC, +, and -)

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

267

Page 274

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

19.1 Specifications

19.1.3 Part Names Liquid crystal screen "ESC" button "-" button "+" button "OK" button Cut off the part when using an expansion board at the same time.

Functions of operation buttons The display module has 4 operation buttons as shown in the following table. Name of button ESC

Function of operation button Use this button to cancel the operation and to return to the previous screen.

-

Use this button to move the cursor or to set a numeric value.

+

Use this button to move the cursor or to set a numeric value.

OK

Use this button to select an item or to determine the set numeric value.

19.1.4 External Dimensions

34.4(1.36") 49.4(1.95")

51.2(2.02")

Unit: mm(inches)

9.6(0.38") 12(0.48")

268

Page 275

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

11

Installation and Removal

High-Speed Counters

19.2

19.2 Installation and Removal

Be sure that the power is OFF when installing the display module.

The FX3G-40MT/ES is used as the main unit in this example.

1 Remove the top cover.

13 Wiring for Various Uses

Remove the top cover (A in the figure on the right) as shown in the right figure.

A

12 Output Wiring

19.2.1 Installation (when the expansion board/connector conversion adapter is not used together)

Top cover(S) 1

Caution: Display module cannot attach in the top cover(S) side of a 40/60point types main unit.

14 Test Run, Maintenance, Troubleshooting

15

Attach the display module to the main unit as shown in the right figure (arrow 2).

B 2

2'

Input/Output Powered Extension Units

2 Install/remove the display module.

16 Input/Output Extension Blocks

Remove the display module while pressing and holding the display module fixing hook (B in the figure on the right) as shown in the right figure (arrow 2').

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

269

Page 276

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

19.2 Installation and Removal

19.2.2 Installation (when the expansion board/connector conversion adapter is used together) The FX3G-40MT/ES is used as the main unit and the expansion board is used together in this example.

1 Attach the expansion board/connector conversion adapter to the main unit.

→ For the attachment method, refer to Chapter 8.

Caution: - Make sure to attach the expansion board/connector conversion adapter before the display module. - The display module cannot be attached to the expansion board/connector conversion adapter attached on the top cover (S) side of the 40/60-point type main unit.

2 Remove the upper connector cover (A in the right figure).

A Top cover (S)

2

3 Remove the part B shown in the right figure using a snipper, etc. Caution: B

Removal of the part B is not necessary when the connector conversion adapter is used together and the main unit is the 14/24point type.

4 Attach the display module to the option connector of the expansion board/connector conversion adapter. Attach the display module to the option connector (D in the figure on the right) of the expansion board/connector conversion adapter while pressing and holding the display module fixing hook (C in the figure on the right) as shown in the right figure (arrow 4).

Remove the display module while pressing and holding the display module fixing hook (C in the figure on the right) as shown in the right figure (arrow 4').

270

C 4 D

4'

Page 277

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

11

Summary of Functions

High-Speed Counters

19.3

19.3 Summary of Functions

The display module functions are summarized below. Item

Function

Remarks

Reference

Performs error checks and displays the results.

Button operation

Section 19.7

LANGUAGE (selects the menu display language)

Selects either Japanese or English as the menu display language. Button operation

Section 19.8

Contrast

Adjusts the contrast (-5 to 10); default setting: 0

Button operation

Section 19.9

Displays the current time.

Button operation

Subsection 19.10.1

Sets the current time.

Button operation

Subsection 19.10.2

Keyword

The currently specified keyword can be canceled.

Button operation

Section 19.11

Cassette (Memory cassette transfer)

Allows data transfers between the internal EEPROM and the Button operation memory cassette.

Section 19.12

Specified device monitor function

Displays the monitor/test screen for a specified device at the top.

Section 19.14

Screen saver function

Displays the screen saver if key operation is not given for specified Requires program*3 Section 19.15 period of time.

Display screen protect function

Enables all functions, prohibits change (test) functions, and Requires program protects the top screen (time display).

Operation button ON/OFF information

Allows monitoring of operation button ON/OFF status.

Hexadecimal current value display setting

Changes the display format of the current values and setting values for the timer, counter, data register, extended register, and Requires program*2 Section 19.18 extended file register to a hexadecimal display format.

Display ClockMenu Setting

Non-menu functions Requires program

Section 19.16

Requires program Section 19.17 or monitor

There is no test function for "Input (X)".

*2.

A sequence program is required to enable a hexadecimal display of the timer (T), counter (C), data register (file register) (D) [16-bit/32-bit], extended register (R) [16-bit/32-bit], and extended file register (ER) [16-bit/32-bit] current values. → Refer to Section 19.19 for the setting procedure.

*3.

When no setting is made within a program the screen saver function becomes effective after 10 minutes. → Refer to Section 19.15 for screen saver function.

14

15

16

17 Extension Power Supply Unit

*1.

13

Input/Output Extension Blocks

ErrorCheck

Input/Output Powered Extension Units

Section 19.6

Menu screen functions

12

Test Run, Maintenance, Troubleshooting

Monitor/Test

Input (X)*1, output (Y), auxiliary relay (M), state (S), timer (T), counter (C), data register (D) [16-bit/32-bit], extended register (R) Button operation [16-bit/32-bit], and extended file register (ER) [16-bit/32-bit] monitor/test function.

Top screen (time display)

Wiring for Various Uses

Subsection 19.4.2

Output Wiring

Displays the time indicated by the main unit’s internal real-time Button operation clock.

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

271

Page 278

FX3G Series Programmable Controllers User's Manual - Hardware Edition

19.4

19 Display Module(FX3G-5DM) 19.4 Procedure for Accessing the Menu Screen from the

Procedure for Accessing the Menu Screen from the Title Screen All operation explanations and display screen examples in this manual are in English. When the menu display language is set to Japanese, please convert the screen messages to their Japanese translations. → Refer to Section 19.20 for the Japanese and English display character correspondence table. → Refer to Section 19.8 for menu display language setting.

19.4.1 Title screen The screen shown at right is displayed for 1.5 seconds after the power is turned on. Content

[1]

Model name

[2]

Version

ME L S E C - F FX 3G S e r i e s

[1]

Ve r . 1 . 10

[2]

19.4.2 Top screen (time display) Following the title screen display, the "Current Time screen" is then displayed. 01 . 10 . 08 2 3 : 5 9 : 5 9 ( Wed )

The specified device monitor screen is displayed instead when the specified device monitor function is used. → Refer to Section 19.14 for details of the specified device monitor function. Although the year displays in a 2-digit format (08), this can be changed to a 4-digit format (2008) by revising the program. → Refer to Subsection 19.10.3 for the 2-digit year to 4-digit year change procedure.

19.4.3 Menu screen As shown in the figure at right, the menu screen displays 4 lines of the total menu. Press the [+] button to scroll downward through the menu.

Mo n i t o r / T e s t E r r o r Ch e c k

Button operations at this menu screen are explained below. Button ESC

272

Operation Description

L A NGU A G E Co n t r a s t

Returns to the "top screen" (time display).

C l o c kMe n u

-

Scrolls upward through the menu. Hold for 1 second or longer for high-speed scrolling. This button is disabled when the cursor is located at the beginning of the menu.

Ca s s e t t e

+

Scrolls downward through the menu. Hold for 1 second or longer for high-speed scrolling. This button is disabled when the cursor is located at the end of the menu.

OK

Selects the item where the cursor is blinking.

Ke ywo r d

Page 279

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

11

Menu Structure

High-Speed Counters

19.5

19.5 Menu Structure

Title screen

Operation keys

12

OK

Press the [OK] button

FX 3G S e r i e s

ESC

Press the [ESC] button

Ve r . 1 . 10 -

01 . 10 . 08

ESC

+ The [+] / [-] button are used to move the cursor and switch between display screens.

13 OK

D( 16b i t )

ESC

DD ( 3 2 b i t )

Wiring for Various Uses

Approx. 1.5 secs. OK Menu screen Top screen (Time display) or ESC Mo n i t o r / T e s t

Output Wiring

ME L S E C - F

T

2 3 : 5 9 : 5 9 ( W ed )

C

14

R( 16b i t ) DR ( 3 2 b i t )

Specified device monitor screen

DER ( 3 2 b i t )

Test Run, Maintenance, Troubleshooting

Switched by system information setting

ER ( 1 6 b i t ) X

ESC X010

. . . 34567

15

Y

ESC

Input/Output Powered Extension Units

M S

( Spe c i f i ed )

Display example OK ESC

16

E r r o r Ch e c k No

Input/Output Extension Blocks

E r r o r Ch e c k er ror s

17 ESC

Extension Power Supply Unit

L A N GU A G E

OK

L A N GU A G E Japanese Eng l i s h

18 Co n t r a s t

OK

Other Extension Units and Options

Display example Co n t r a s t

ESC

0 ( - 5 ~ 10 )

19 Display Module

C l o c kMe n u

OK ESC

Cu r r e n t Cl ock t i me

20

Se t t i ng

Terminal Block

273

Page 280

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

19.5 Menu Structure

Display example Ke ywo r d

OK ESC

The i s

Ke ywo r d no t se t

Display example Ca s s e t t e

OK ESC

274

Memo r y

Ca s s e t t e

Ca s s e t t e

PLC

Ca s s e t t e

PLC

Page 281

FX3G Series Programmable Controllers

19 Display Module(FX3G-5DM)

User's Manual - Hardware Edition

11

Monitor/Test Mode

High-Speed Counters

19.6

19.6 Monitor/Test Mode

19.6.1 Relevant devices

12

Monitored Items Device

Output Wiring

Monitoring and testing can be performed from the "Monitor/Test" menu for the devices listed below. (Monitoring/testing is not possible for the file register (D) and the index register (V/Z)). : Possible : Possible under certain conditions : Not possible -: Item not supported by this device Test Items

Operation Direction

Current Value

Setting Value

Forced ON/OFF

Input [X]

-

-

-

-

-

-

-

Output [Y]

-

-

-

-

*1

-

-

Auxiliary relay [M]

-

-

-

-

*1

-

-

-

*1

-

-

State [S]

-

-

-

Setting Change

-

*2

Counter [C]

*3

*2

-

-

-

-

-

-

File register [D, DD]

-

-

-

-

-

-

Extended register [R, DR]

-

-

-

-

-

-

Extended file register [ER, DER]*4

-

-

-

-

-

-

Index register (V, Z)

-

-

-

-

-

-

A forced ON or OFF is executed for only one operation cycle, and therefore has a considerable effect on the SET/RST and self retaining circuits when the PLC is running. Moreover, a forced ON/OFF result is retained for devices (Y,M,S) which are not being driven by an OUT instruction, etc., in the program.

*2.

Setting values of timer and counter can be changed when the PLC status is as shown below. Program Memory Type Internal EEPROM PROTECT switch ON

Setting Change Enabled/Disabled

RUN

Enabled

STOP

Enabled

RUN

Disabled

STOP

Disabled

RUN

Enabled

STOP

Enabled

17

*3.

The C200 to C255 32-bit up/down counters and the high-speed counters have counting directions.

Extension Power Supply Unit

Memory cassette

RUN/STOP Status

16 Input/Output Extension Blocks

*1.

15 Input/Output Powered Extension Units

Data register [D, DD]

14 Test Run, Maintenance, Troubleshooting

Timer [T]

13 Wiring for Various Uses

Current Value Change

Reset

Contact

*4.

Extended file registers stored in the EEPROM in the main unit, or extended file registers stored in the EEPROM inside the memory cassette when the memory cassette is attached.

18

PROTECT switch OFF

Other Extension Units and Options

19 Display Module

20 Terminal Block

275