What is in it
The hardware edition user's manual for the Mitsubishi MELSEC FX3G Series programmable controllers. It covers the main units and the equipment that extends them: input/output powered extension units, FX2N input/output extension blocks such as the FX2N-8EYR and FX2N-16EYR relay output blocks, special adapters, expansion boards, the display module, FX Series terminal blocks such as the FX-16EYR-TB, memory cassettes and the battery. Readers find specifications, system configuration rules, I/O numbering, enclosure installation, wiring, high-speed counters, test operation and troubleshooting.
Its parts
- Introduction
- Features and Part Names
- Introduction of Products
- Specifications, External Dimensions and Terminal Layout (Main Units)
- Version Information and Peripheral Equipment Connectability
- Examination of System Configuration
- Assignment of Input/Output Numbers and Unit Numbers
- Installation In Enclosure
- Preparation for Wiring and Power Supply Wiring Procedures
- Input Wiring Procedures
- Use of High-speed Counters
- Output Wiring Procedures
- Examples of Wiring for Various Uses
- Test Operation, Adjustment, Maintenance and Troubleshooting
- Input/Output Powered Extension Units
From the manual
Key facts from this manual
Each line names its page in the PDF.
Mitsubishi user's manual, hardware edition, for the MELSEC FX3G Series programmable controllers (JY997D31301 Version A). It covers the FX3G main units and the FX2N extension units and blocks used with them, including the FX2N-16EYR relay output block, but does not describe the FX-16EYR by that name. It gives specifications, product line-ups and LED troubleshooting.
- Main units
- FX3G-14MT/ES, FX3G-24MT/ES, FX3G-40MT/ES, FX3G-60MT/ES p. 34
- Main unit I/O
- FX3G-24MT/ES: 14 inputs, 10 outputs; FX3G-40MT/ES: 24 inputs, 16 outputs; FX3G-60MT/ES: 36 inputs, 24 outputs; transistor (sink) outputs p. 35
- Power supply
- 100 to 240V AC (85 to 264V AC allowable), 50/60Hz p. 43
- Inputs
- 24V DC ±10%, sink or source, photocoupler insulated, removable M3 terminal block p. 44
- Transistor outputs
- Sink type, 5 to 30V DC, 0.5A per point p. 45
- Program memory
- 32000 steps, EEPROM, up to 20,000 writes p. 46
- Maximum I/O
- 256 points: up to 128 on the PLC plus up to 128 remote CC-Link points p. 29
- USB port
- Built-in USB programming port, 12Mbps p. 29
- High-speed counters
- 1-phase 60kHz x 4 points + 10kHz x 2 points; 2-phase 30kHz x 2 points + 5kHz x 1 point p. 29
- Pulse output
- Up to 100kHz on 3 axes (Y000 to Y002) on transistor main units; 2 axes on 14- and 24-point units p. 30
- Temperature
- 0 to 55 C operating, -25 to 75 C storage p. 42
- FX2N-16EYR
- FX2N-16EYR: output extension block with 16 relay outputs on a terminal block p. 36
- Relay block ratings
- FX2N-8EYR and FX2N-16EYR: 250V AC or 30V DC or less, 2A per point, 80VA inductive, about 10ms response p. 243
What this manual walks you through
- Choosing FX3G main units, extension units and extension blocks p. 34, 35, 36, 37
- Checking the environmental and general specifications p. 42
- Running dielectric withstand and insulation resistance tests p. 43
- Main unit power, input and output specifications p. 43, 44, 45
- Device ranges and performance of the main unit p. 46, 47
- FX2N-8EYR and FX2N-16EYR specifications, terminals and dimensions p. 243, 244, 245
- Troubleshooting with the POW, ALM and ERR LEDs p. 181, 182
Good to know
- Dielectric and insulation tests must not be run between an expansion board and the main unit. p. 43
- Common grounding with heavy electrical equipment is not allowed. p. 42
- The PLC must not be used above atmospheric pressure. p. 42
- The clock is backed by a capacitor that needs 30 minutes or more of power to charge fully. p. 47
Questions this manual answers
Which relay output blocks does the FX3G hardware manual list?
It lists the FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL, FX2N-8EYR and FX2N-16EYR relay output extension blocks. p. 36
How much current can each FX2N-16EYR relay output switch?
2A per point with a resistive load, and 8A or less in total per common. p. 243
What supply voltage does an FX3G main unit need?
100 to 240V AC at 50/60Hz, with an allowable range of 85 to 264V AC. p. 43
What does a flashing ERR LED mean on an FX3G PLC?
A parameter, syntax or ladder error has occurred; run PLC diagnosis and a program check with the programming tool. p. 182
What does the ALM LED mean when it is lit?
The battery voltage is low, and the battery should be replaced at once. p. 181
Contents
Chapters and sections
Each line opens the PDF at its page.
- Front Cover1
- Safety Precautions3
- Manual number7
- 1. Introduction20
- 2. Features and Part Names29
- 3. Introduction of Products34
- 4. Specifications, External Dimensions and Terminal Layout (Main Units)42
- 5. Version Information and Peripheral Equipment Connectability50
- 5.1 Version Information50
- 5.2 Programming Tool Applicability51
- 5.3 Precautions on Use of (Built-in USB) Programming Port55
- 5.4 Cautions on using transparent function by way of USB in GOT1000 Series56
- 5.5 Cautions on using transparent port (2-port) function of GOT-F900 Series57
- 5.6 Other Peripheral Equipment Applicability58
- 6. Examination of System Configuration59
- 6.1 Configuration of a Whole System59
- 6.2 Rules of System Configuration61
- 6.3 Number of Input/Output Points and Maximum Number of Input/Output Points63
- 6.4 Number of Connected Extension Devices (Including Extension Cable)66
- 6.5 Expansion of Main Unit67
- 6.6 Expansion of FX2N Series I/O Powered Extension Unit72
- 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)76
- 6.8 Number of Input/Output (Occupied) Points and Current Consumption78
- 7. Assignment of Input/Output Numbers and Unit Numbers81
140 more lines, from page 85 on
- 7.3 Assignment of Communication Channels85
- 8. Installation In Enclosure87
- 9. Preparation for Wiring and Power Supply Wiring Procedures109
- 10. Input Wiring Procedures122
- 11. Use of High-speed Counters136
- 11.1 Outline136
- 11.2 Types of Counting and Operations136
- 11.3 List of Device Numbers and Functions137
- 11.4 Allocation of Device Numbers to Input Numbers138
- 11.5 Handling of High-speed Counters139
- 11.6 Timing of Updating of Current Value and Comparison of Current Value142
- 11.7 Response Frequency and Overall Frequency143
- 11.8 Related Devices and Function Switching Procedures144
- 12. Output Wiring Procedures146
- 13. Examples of Wiring for Various Uses159
- 14. Test Operation, Adjustment, Maintenance and Troubleshooting170
- 14.1 Preparation for Test Operation171
- 14.2 Running and Stopping Procedures [Power ON]174
- 14.3 Operation and Test [Power ON and PLC Running]176
- 14.4 Maintenance and Periodic Inspection178
- 14.5 Troubleshooting with LEDs181
- 14.6 Judgment by Error Codes and Representation of Error Codes183
- 14.7 Troubleshooting192
- 15. Input/Output Powered Extension Units194
- 16. Input/Output Extension Blocks216
- 16.1 Outline217
- 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)219
- 16.3 FX2N-8ER (24V DC Sink Input, Relay Output)222
- 16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)225
- 16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C228
- 16.6 FX2N-16EXL-C (5V DC Input: 16 Points)232
- 16.7 FX2N-8EX-UA1/UL (100V AC Input)235
- 16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)237
- 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)240
- 16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)243
- 16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)246
- 16.12 FX2N-8EYT-H (Transistor Output)250
- 16.13 FX2N-16EYS (Triac Output: 16 Points)252
- 17. Extension Power Supply Unit254
- 18. Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement)257
- 19. Display Module(FX3G-5DM)273
- 19.1 Specifications273
- 19.2 Installation and Removal275
- 19.3 Summary of Functions277
- 19.4 Procedure for Accessing the Menu Screen from the Title Screen278
- 19.5 Menu Structure279
- 19.6 Monitor/Test Mode281
- 19.7 Error Check288
- 19.8 LANGUAGE (Menu Display Language Setting)289
- 19.9 Contrast291
- 19.10 Clock Menu (Current Time Setting)292
- 19.11 Keyword294
- 19.12 Memory Cassette Transfers298
- 19.13 System Information (Restrictions From PLC)301
- 19.14 Specified Device Monitor Function302
- 19.15 Screen saver function308
- 19.16 Display Screen Protect Function309
- 19.17 Operation Button ON/OFF Information313
- 19.18 Specifying a Hexadecimal Current Value Display Format314
- 19.19 Operation Error Messages and Corrective Actions315
- 20. Terminal Block318
- 21. Memory Cassette341
- 22. Battery351
- Appendix A: Special Device List355
- Appendix B: Instruction List374
- Warranty379
- Revised History380
- Back Cover382
The whole text · 49 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 61-6
- Pages 7 to 127-12
- Pages 13 to 1613-16
- Pages 17 to 1917-19
- 1. Introduction20-28
- 2. Features and Part Names29-33
- 3. Introduction of Products34-41
- 4. Specifications, External Dimensions and Terminal Layout (Main Units)42-49
- 5. Version Information and Peripheral Equipment Connectability50-58
- 6. Examination of System Configuration, pages 59 to 6659-66
- 6. Examination of System Configuration, pages 67 to 7467-74
- 6. Examination of System Configuration, pages 75 to 8075-80
- 7. Assignment of Input/Output Numbers and Unit Numbers81-86
- 8. Installation In Enclosure, pages 87 to 9487-94
- 8. Installation In Enclosure, pages 95 to 10295-102
- 8. Installation In Enclosure, pages 103 to 108103-108
- 9. Preparation for Wiring and Power Supply Wiring Procedures109-121
- 10. Input Wiring Procedures122-135
- 11. Use of High-speed Counters136-145
- 12. Output Wiring Procedures146-158
- 13. Examples of Wiring for Various Uses159-169
- 14. Test Operation, Adjustment, Maintenance and Troubleshooting, pages 170 to 177170-177
- 14. Test Operation, Adjustment, Maintenance and Troubleshooting, pages 178 to 185178-185
- 14. Test Operation, Adjustment, Maintenance and Troubleshooting, pages 186 to 193186-193
- 15. Input/Output Powered Extension Units, pages 194 to 201194-201
- 15. Input/Output Powered Extension Units, pages 202 to 209202-209
- 15. Input/Output Powered Extension Units, pages 210 to 215210-215
- 16. Input/Output Extension Blocks, pages 216 to 225216-225
- 16. Input/Output Extension Blocks, pages 226 to 235226-235
- 16. Input/Output Extension Blocks, pages 236 to 245236-245
- 16. Input/Output Extension Blocks, pages 246 to 253246-253
- 17. Extension Power Supply Unit254-256
- 18. Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement), pages 257 to 264257-264
- 18. Other Extension Devices and Optional Units (External Dimensions and Terminal Arrangement), pages 265 to 272265-272
- 19. Display Module(FX3G-5DM), pages 273 to 281273-281
- 19. Display Module(FX3G-5DM), pages 282 to 290282-290
- 19. Display Module(FX3G-5DM), pages 291 to 299291-299
- 19. Display Module(FX3G-5DM), pages 300 to 308300-308
- 19. Display Module(FX3G-5DM), pages 309 to 317309-317
- 20. Terminal Block, pages 318 to 325318-325
- 20. Terminal Block, pages 326 to 333326-333
- 20. Terminal Block, pages 334 to 340334-340
- 21. Memory Cassette341-350
- 22. Battery351-354
- Appendix A: Special Device List, pages 355 to 364355-364
- Appendix A: Special Device List, pages 365 to 373365-373
- Appendix B: Instruction List374-378
- Pages 379 to 381379-381
- Back Cover382-384