Page 42
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
4.
4.1 Generic Specifications
Specifications, External Dimensions and Terminal Layout (Main Units) This Chapter explains the specifications, external dimensions and terminal layout of the main units. → For the specifications for the input/output powered extension units, refer to Chapter 15. → For the specifications for the input/output extension blocks, refer to Chapter 16.
4.1
Generic Specifications Item
Specifications
Ambient temperature 0 to 55 C (32 to 131 F) when operating and -25 to 75 C (-13 to 167 F) when stored Ambient humidity
5 to 95%RH (no condensation) when operating Frequency(Hz)
Vibration resistance
Acceleration(m/s2)
Half amplitude(mm)
When installed on DIN rail
10 to 57
-
0.035
57 to 150
4.9
-
When installed directly
10 to 57
-
0.075
57 to 150
9.8
-
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Shock resistance
147m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
Noise resistance
By noise simulator at noise voltage of 1,000Vp-p, noise width of 1 s, rise time of 1ns and period of 30 to 100Hz
Dielectric withstand voltage
1.5kV AC for one minute
Insulation resistance
5M or more by 500V DC megger
Between each terminals and ground terminal*1
500V AC for one minute Class D grounding (grounding resistance: 100
Grounding or less)
<Common grounding with a heavy electrical system is not allowed>*2
Working atmosphere Free from corrosive or flammable gas and excessive conductive dust Working altitude
< 2000m*3
*1.
For more information on the dielectric withstand voltage test and the insulation resistance test of the terminals of each product, refer to the following. → Refer to Subsection 4.1.1.
*2.
Ground the PLC independently or jointly. PLC
Other equipment
Independent grounding Best condition
*3.
36
PLC
→ Refer to Section 9.3. Other equipment
Shared grounding Good condition
PLC
Other equipment
Common grounding Not allowed
The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
Page 43
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
1
Dielectric withstand voltage test and insulation resistance test Perform dielectric withstand voltage test and insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Insulation resistance
Dielectric strength
Remarks
2 Features and Part Names
Between terminals
Terminals of main unit and input/output powered extension unit/block -
Between 24V DC service power supply connected to input terminal (24V DC) and ground terminal
500V AC for 1min
-
Between input terminal (100V AC) and ground terminal
1.5kV AC for 1min
Between output terminal (relay) and ground terminal
1.5kV AC for 1min
Between output terminal (transistor) and ground terminal
500V AC for 1min
-
Between output terminal (triac) and ground terminal
1.5kV AC for 1min
Only input/output powered extension unit/block
5M or more Only input/output powered extension unit/block on 500V DC Megger Only input/output powered extension unit/block
Terminals of expansion board, special adapter and special function block Not allowed
Since the expansion board and the main unit CPU are not insulated, it is not allowed to perform the dielectric withstand voltage test and insulation resistance test between them.
500V AC for 1min
5M or more on 500V DC Megger
-
Special function block
4.2
Refer to the manual for each special function block.
Each manual
Power Supply Specifications
FX3G-24MT/ES
FX3G-40MT/ES
FX3G-60MT/ES
100 to 240V AC
Allowable supply voltage range
85 to 264V AC
Rated frequency
50/60Hz
Allowable instantaneous power failure time
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
Power fuse
250V 1A
Rush current
30A max. 5ms or less/100V AC, 50A max. 5ms or less/200V AC
Power consumption*1
31W
8 Installation
250V 3.15A 32W
37W
40W
24V DC service power 400mA supply
This item shows values when all 24V DC service power supplies are used in the maximum configuration connectable to the main unit, and includes the input current (7 or 5mA per point).
9 Preparation and Power Supply Wiring
*1.
7 Input/Output Nos., Unit Nos.
Supply voltage
System Configuration
Specifications FX3G-14MT/ES
5
6
The specifications for the main unit power supply are explained below. For the power (current) consumed by the special function blocks, refer to this manual or the special function units/blocks manual. Item
4
Version and Peripheral Devices
Between terminal of special adapter and ground terminal
Not allowed
3
Specifications
1.5kV AC for 1min
Product Introduction
Between power supply terminal (AC power supply) and ground terminal
Between terminal of expansion board and ground terminal
Introduction
4.1.1
4.2 Power Supply Specifications
10 Input Wiring
37
Page 44
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
4.3
4.3 Input Specifications
Input Specifications The main unit input specifications are explained below.
4.3.1
24V DC Input (sink/source) The input numbers in the table indicate the main unit terminal numbers. "X010 or more" means the numbers from X010 to the largest number that the main unit has. (The input numbers for FX3G-14MT/ES are X000 to X007.) → For details on input and source input, refer to Subsection 10.1.1 Specifications
Item Number of input points
FX3G-14MT/ES
FX3G-24MT/ES
FX3G-40MT/ES
FX3G-60MT/ES
8 points
14 points (16)*1
24 points
36 points (40)*1
Input connecting type
Removable terminal block (M3 screw)
Input form sink/source
Input signal voltage
24V DC ±10%
Input impedance Input signal current
X000 to X007 X010 or more
3.3k -
4.3k
X000 to X007
7mA/24V DC
X010 or more
-
X000 to X007 ON input sensitivity current X010 or more
-
5mA/24V DC 4.5mA or more 3.5mA or more
OFF input sensitivity current
1.5mA or less
Input response time
Approx. 10ms
Input signal form
No-voltage contact input Sink input: NPN open collector transistor Source input: PNP open collector transistor
Input circuit insulation
Photocoupler insulation
Input operation display
LED on panel lights when photocoupler is driven.
Sink input wiring
Source input wiring L N
Input circuit configuration
Fuse
100 to 240V AC *3 24V *3 0V S/S *2 X
38
*1.
Each value inside ( ) indicates the number of occupied points.
*2.
Input impedance
*3.
The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.
L N
Fuse
100 to 240V AC *3 24V *3 0V S/S *2
X
Page 45
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
1
Output Specifications
Introduction
4.4
4.4 Output Specifications
The main unit output specifications are explained below.
4.4.1
Transistor output
Number of output points
Transistor output specifications FX3G-14MT/ES
FX3G-24MT/ES
FX3G-40MT/ES
FX3G-60MT/ES
6 points(8)*1
10 points(16)*1
16 points
24 points
Removable terminal block (M3 screw)
Output type/form
Transistor/sink output
External power supply
5 to 30V DC
0.5A/point The total load current of resistance loads per common terminal should be the following value. Resistance → For details on the common terminal for each model, load refer to the 4.7 Terminal Layout. • 1 output point/common terminal: 0.5A or less • 4 output points/common terminal: 0.8A or less
Inductive load
12W/24V DC The total of inductive loads per common terminal should be the following value. → For details on the common terminal for each model, refer to the 4.7 Terminal Layout. • 1 output point/common terminal: 12W or less/24V DC • 4 output points/common terminal: 19.2W or less/24V DC
Open circuit leakage current ON voltage
1.5 V or less Y000, Y001:5 s or less/10mA or more (5 to 24V DC) Y002 or more:0.2ms or less/200mA or more (at 24V DC)
Y000 to Y002:5 s or less/10mA or more (5 to 24V DC) Y003 or more:0.2ms or less/200mA or more (at 24V DC)
ON OFF
Y000, Y001:5 s or less/10mA or more (5 to 24V DC) Y002 or more:0.2ms or less/200mA or more (at 24V DC)
Y000 to Y002:5 s or less/10mA or more (5 to 24V DC) Y003 or more:0.2ms or less/200mA or more (at 24V DC)
Response time
Circuit insulation
Photocoupler insulation
Display of output operation
LED on panel lights when photocoupler is driven.
6 System Configuration
OFF ON
7 Input/Output Nos., Unit Nos.
Load Y Output circuit configuration
Fuse
8
COM
*1.
of [COM
Installation
DC power supply A common number applies to the
5 Version and Peripheral Devices
0.1mA or less/30V DC
4 Specifications
Max. load
3 Product Introduction
Connecting type
Features and Part Names
Item
2
].
Each value inside ( ) indicates the number of occupied points.
9 Preparation and Power Supply Wiring
10 Input Wiring
39
Page 46
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
4.5
4.5 Performance Specifications
Performance Specifications The main unit performance specifications are explained below. Item
Stored program repetitive operation system with interruption function
Input/output control system
Batch processing system (when END instruction is executed) Input/output refresh instruction and pulse catch function are provided.
Programming language
Relay symbol system + step-ladder system (SFC notation possible)
Max. memory capacity/type
32000-step/EEPROM memory Max. allowable write: 20,000 times
Memory cassette (Option)
32000-step/EEPROM memory (with loader function) Max. allowable write: 10,000 times
Writing function during running
Provided (Program can be modified while the PLC is running.)
Keyword function
With keyword/Customer keyword function
Real-time clock
Clock function*1
Built-in 1980 to 2079 (with correction for leap year) 2- or 4-digit year, accuracy within 45 seconds/month at 25 C
Kinds of instructions
Basic instructions
Sequence instructions: 29 Step-ladder instructions: 2
Applied instructions
123 kinds
Program memory
Basic instructions Processing speed Applied instructions (1)Extension-combined number of input points (2)Extension-combined Number of input/ number of output points output points (4)Remote I/O number of points (CC-Link) (3) + (4) total number of points Input/output relay
Auxiliary relay
State
Timer timer)
(on-delay
Extension mode*3 : 0.42 s/instruction Standard mode*3 : 0.5 s/instruction Extension mode*3 : 1.2 s/instruction 128 points or less (3)Total points 128 points or less 128 points or less
(1) + (2) (3) total number of points is 128 or less.
-
256 points or less X000 to X177
Output relay
Y000 to Y177
The device numbers are octal.
M0 to M383
384 points
-
EEPROM keep
M384 to M1535
1152 points
-
For general*2
M1536 to M7679
6144 points
-
For special
M8000 to M8511
512 points
-
For initial state (EEPROM keep)
S0 to S9
10 points
-
EEPROM keep
S10 to S999
990 points
-
For general*2
S1000 to S4095
3096 points
100ms
T0 to T199
200 points
0.1 to 3,276.7 sec
10ms
T200 to T245
46 points
0.01 to 327.67 sec
1ms accumulating type (EEPROM keep)
T246 to T249
4 points
0.001 to 32.767 sec
100ms accumulating type (EEPROM keep)
T250 to T255
6 points
0.1 to 3,276.7 sec
T256 to T319
64 points
0.01 to 327.67 sec
1ms Variable analog potentiometers
Counter
Standard mode*3 : 0.21 s/instruction
Input relay For general
40
Performance
Operation control system
-
Available as analog timers VR1 : D8030 VR2 : D8031
16 bits up (For general)
C0 to C15
16 points
Counting from 0 to 32,767
16 bits up (EEPROM keep)
C16 to C199
184 points
Counting from 0 to 32,767
Page 47
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
4.5 Performance Specifications
1 Counter
C200 to C219
20 points
32 bits up/down (EEPROM keep)
C220 to C234
15 points
1-phase 1-count input in both directions (32 bits up/down) (EEPROM keep)
C235 to C245
1-phase 2-count input in both directions (32 bits up/down) (EEPROM keep)
C246 to C250
2-phase 2-count input in both directions (32 bits up/down) (EEPROM keep)
C251 to C255
For general (16 bits)
D0 to D127
128 points
-
For EEPROM keep (16 bits)
D128 to D1099
972 points
-
For general*2 (16 bits)
D1100 to D7999
6900 points
-
File register (EEPROM keep)
D1000 to D7999
Maximum 7000 points
For special (16 bits)
D8000 to D8511
512 points
-
For index (16 bits)
V0 to V7 Z0 to Z7
16 points
-
24000 points
-
ER0 to ER23999
24000 points
Stored in the EEPROM built-in the main unit, or stored in the EEPROM in the memory cassette when the memory cassette is used.
For branching of JUMP and CALL
P0 to P2047
2048 points
For CJ instructions and CALL instructions
Input interruption
I0 to I5
6 points
Timer interruption
I6 to I8
3 points
N0 to N7
8 points
For EEPROM keep (16 bits)
Pointer
Nesting
For master control
Constant
Hexadecimal number (H) Real number (E)*4
R0 to R23999
4
Can be set as file registers in units of 500 points from D1000 in the program area (EEPROM) using parameters.
5
-
7
For MC instructions
16bits
-32,768 to +32,767
32bits
-2,147,483,648 to +2,147,483,647
16bits
0 to FFFF
32bits
0 to FFFFFFFF
32bits
-1.0 x 2128 to -1.0 x 2-126, 0 , 1.0 x 2-126 to 1.0 x 2128 Decimal-point and exponential notations are possible.
8
These devices can be changed to the keep (battery backup) type using a parameter when the optional battery is used. → For the parameter setting method, refer to Chapter 22.
*3.
The standard mode is selected when the program capacity is set to 16000 steps or less using a parameter. The extension mode is selected when the program capacity is set to 16001 steps or more using a parameter. → For parameter settings, refer to the Programming Manual. Supported in Ver. 1.10 or later
41
9
10 Input Wiring
*2.
Preparation and Power Supply Wiring
The current time of the clock is backed up by the capacitor built-in the PLC. Supply the power to the PLC for 30 minutes or more to completely charge this large-capacity capacitor. (The capacitor works for 10 days (atmosphere: 25 C ) The current time can be backed up by the battery when the optional battery is incorporated. → For details on the battery, refer to Chapter 22.
Installation
*1.
*4.
6
Input/Output Nos., Unit Nos.
Decimal number (K)
3
System Configuration
Extension file register
Counting from -2,147,483,648 to +2,147,483,647
Version and Peripheral Devices
For general*2 (16 bits)
2
Specifications
Extension register
Counting from -2,147,483,648 to +2,147,483,647
Product Introduction
Data register (32 bits when paired)
Performance
Features and Part Names
High-speed counter
Introduction
Item 32 bits up/down (For general)
Page 48
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
4.6
4.6 External Dimensions (Weight/Accessories/Installation)
External Dimensions (Weight/Accessories/Installation) The external dimensions of the main unit are explained.
4.6.1
Main units 2- 4.5 mounting holes
90(3.55")
82(3.23")(mounting hole pitch)
Unit: mm (inches)
W1(mounting hole pitch)
8(0.32") 86(3.39")
W
Series
Model name
W: mm (inches)
W1: mm (inches)
MASS (weight): kg (lbs)
FX3G-14M
FX3G-14MT/ES
90 (3.55")
82 (3.23")
0.50 (1.10 lbs)
FX3G-24M
FX3G-24MT/ES
90 (3.55")
82 (3.23")
0.55 (1.21lbs)
FX3G-40M
FX3G-40MT/ES
130 (5.12")
122 (4.81")
0.70 (1.54 lbs)
FX3G-60M
FX3G-60MT/ES
175 (6.89")
167 (6.58")
0.85 (1.87 lbs)
1) Accessories Dust proof protection sheet Manual supplied with product 2) Installation 35mm(1.38") wide DIN rail or Direct installation (with screws) (M4 x 2)
4.7
Terminal Layout The terminal layout in the main unit is shown below.
4.7.1
Interpretation of terminal block layout Power supply terminals
L
Input terminal
S/S X1 X3 X5 X7 X11 X13 X15 X17X21 X23 X25 X27 N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 Output terminals connected to COM5
FX3G-40MT/ES
0V Y0 Y1 Y2
Y4 Y6
Y10 Y12
[ · ] Vacant terminal (Do not use.)
Y14 Y16
24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17
24V DC service Common terminal Output power supply (4 points/common terminal terminal)
Partition
• Indication of output terminals connected to common terminal One common terminal covers 1, 2, 3 or 4 output points. The output numbers (Y) connected to a common terminal are enclosed with heavy partition lines.
42
Page 49
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal
User's Manual - Hardware Edition
1
FX3G-14MT/ES
L
Introduction
4.7.2
4.7 Terminal Layout
S/S X1 X3 X5 X7 N X0 X2 X4 X6
2 Features and Part Names
FX 3G -14MT/ES
0V Y0 Y1 Y2 Y3 Y4 Y5 24V COM0 COM1 COM2 COM3 COM4 COM5
3
FX3G-24MT/ES
L
Product Introduction
4.7.3
S/S X1 X3 X5 X7 X11 X13 X15 N X0 X2 X4 X6 X10 X12 X14
4 Specifications
FX3G -24MT/ES
0V Y0 Y1 Y2 Y3 Y5 Y6 Y10 24V COM0 COM1 COM2 COM3 Y4 COM4 Y7 Y11
5
FX3G-40MT/ES
L
Version and Peripheral Devices
4.7.4
S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26
6
0V Y0 Y1 Y2
Y4 Y6
Y10 Y12
System Configuration
FX3G -40 MT/ES
Y14 Y16
24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17
7
FX3G-60MT/ES
L
Input/Output Nos., Unit Nos.
4.7.5
S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42
8
0V Y0 Y1 Y2
Y4 Y6
Y10 Y12
Y14 Y16
Y20 Y22
Installation
FX3G -60MT/ES Y24 Y26
24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 Y21 Y23 COM7 Y25 Y27
9 Preparation and Power Supply Wiring
10 Input Wiring
43