FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 5. Version Information and Peripheral Equipment Connectability
Pages 50 to 58 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]
The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Mitsubishi FX-16EYR
Page 50
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.1 Version Information
5.
Version Information and Peripheral Equipment Connectability
5.1
Version Information
5.1.1
Version check method In FX3G PLCs, users can obtain the PLC version information by monitoring special data register D8001 (decimal number).
D8001
2
6
1
0
PLC type and version
0 Version information (Example: Ver. 1.00)
PLC type (Example: 26 = FX3G PLC)
5.1.2
How to look at manufacturer's serial number The year and month of production of the product can be seen from the manufacturer's serial number "SERIAL" indicated on the label adhered to the right side of the product. Example: FX3G-40MT/ES (manufacturer's serial number: 8X0001) PROGRAMMABLE CONTROLLER
MITSUBISHI Right side
MODEL
FX3G-40MT/ES 100-240VAC 50/60Hz 37W OUT:5~30VDC 0.5A
SERIAL
8X0001
MITSUBISHI ELECTRIC CORPORATION MADE IN JAPAN
8
X
0
0
0
1
Control number Month (Example: Oct.):(1 to 9 = January to September, X = October, Y = November, Z = December) Year (Example: 2008): Last digit of year
5.1.3
Version upgrade history FX3G Series performed the following upgrade. Version Ver.1.00
Manufacturer’s serial number 86**** (June, 2008)
Contents of version upgrade First product •
Ver.1.10
8X**** (October, 2008)
• • • •
44
Supports following 15 instructions: FLT(FNC49), VRRD(FNC85), VRSC(FNC86), ECMP(FNC110), EMOV(FNC112), EADD(FNC120), ESUB(FNC121), EMUL(FNC122), EDIV(FNC123), ESQR(FNC127), INT(FNC129), IVCK(FNC270), IVDR(FNC271), IVRD(FNC272), IVWR(FNC273) Supports connection of following expansion boards: FX3G-2AD-BD, FX3G-1DA-BD, FX3G-8AV-BD Supports connection of display module (FX3G-5DM) Supports of the inverter communication function Supports of the pulse width measurement function
Page 51
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.2 Programming Tool Applicability
1
Programming Tool Applicability
5.2.1
Applicable versions of programming tool
Introduction
5.2
2
GX Developer is applicable to FX3G PLCs from the following version. Applicable GX Developer version
FX3G PLC version Ver.1.00 or later (First product)
5.2.2
Description Model selection: FX3G
3
Supports FX3G PLCs (Ver.1.10 or later). Ver.8.72A or later Ver.1.10 or later
The following instructions will be supported in the near future FLT(FNC49), ECMP(FNC110), EMOV(FNC112), EADD(FNC120), ESUB(FNC121), EMUL(FNC122), EDIV(FNC123), ESQR(FNC127), INT(FNC129)
4
In the case of programming tool (version) not applicable
Specifications
Inapplicable programming tools can programme by setting alternative model.
1. Alternative model setting Model to be programmed
Model to be set
FX3G PLC
FX3G
FX2N*1
Low
5
FX2
Version and Peripheral Devices
*1.
Priority High FX1N*1
"FX2N" is selected when the FX-10P(-E) is used.
2. Contents of restrictions • Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in a PLC selected as the alternative model.
6 System Configuration
• Use a programming tool that can select either FX3G to change parameters, i.e. memory capacity, file register capacity, etc. • The built-in USB port cannot be used for programming communication.
5.2.3
Product Introduction
GX Developer • SW D5C(F)-GPPW-J • SW D5C(F)-GPPW-E
Features and Part Names
Model name (Media model name is shown below.)
Program transfer speed and programming tool
1. Applicable interface • Standard built-in port(RS-422) or function extension board FX3G-422-BD for RS-422 When the RS-232C/RS-422 converter FX-232AWC-H is connected
7 Input/Output Nos., Unit Nos.
When either of the following interfaces is used for GX Developer (Ver.8.72A or later), writing and reading of programs and monitoring of devices can be executed at high speed (115.2 kbps) in FX3G PLCs.
8 Installation
• Function extension board FX3G-232-BD for RS-232C • Special adapter FX3U-232ADP(-MB) for RS-232C
2. Communication speed setting by GX Developer The communication speed can be set in the following position: Select "Online" "Transfer setup..." "PC side I/F", and double-click the "Serial" icon.
9 Preparation and Power Supply Wiring
3. In programming software not applicable to the FX3G Series Communication is executed at 9,600 or 19,200 bps.
10 Input Wiring
45
Page 52
FX3G Series Programmable Controllers User's Manual - Hardware Edition
5.2.4
5 Version Information and Peripheral Equipment Connectability 5.2 Programming Tool Applicability
Cautions on connecting peripheral equipment by way of expansion board or special adapter. When connecting peripheral equipment (programming tool or GOT [CPU direct connection]) by way of the FX3G-232-BD, FX3G-422-BD or FX3U-232ADP(-MB), set the connection channel (CH1 or CH2) as follows. If the connection channel is not specified with the status below, communication error may occur in the connected peripheral equipment. → For details, refer to the Data Communication Edition. - Set to "K0" the special data register for communication format setting of the channel connecting the peripheral equipment (CH1: D8400 or D8120, CH2: 8420). - Set the communication parameter "PLC system [2]" of the channel connecting the peripheral equipment to "Not set" (as shown in the window below).
Leave this unchecked.
46
Page 53
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
1
Cautions on write during RUN In FX 3G PLCs, write during RUN (program changes in the RUN mode) is enabled using the following programming tools. → For the operating procedure of and cautions on write during RUN, refer to the manual of the used programming tool.
Programming tool
Version
Remarks
Supports write during RUN in the instruction and device ranges in FX2N PLCs Ver.2.00A or later Ver.1.00 or later. GX Developer
Ver.8.72A or later
Supports write during RUN in the instruction and device ranges in FX3G PLCs Ver.1.00 or later.
Ver.2.00 or later
Supports write during RUN in the instruction and device ranges in FX2N PLCs Ver.1.00 or later.
Ver.4.00 or later
Supports write during RUN in the instruction and device ranges in FX1N PLCs Ver.1.00 or later.
Ver.2.00 or later
Supports write during RUN in the instruction and device ranges in FX2N PLCs Ver.1.00 or later.
Ver.3.00 or later
Supports write during RUN in the instruction and device ranges in FX1N PLCs Ver.1.00 or later.
FX-PCS/WIN
FX-PCS/WIN-E
Cautions on write during RUN Item
Built-in EEPROM and optional memory cassette (whose write protect switch is set to OFF)
GX Developer Ver.8.72A or later •
256 steps or less after edition (addition/deletion) (including NOP immediately after circuit blocks except final circuit)
GX Developer Ver.8.70Y or 127 steps or less after edition (addition/deletion) (including NOP former immediately after circuit blocks except final circuit) FX-PCS/WIN(-E)
6
Circuit blocks in which labels P and I are added, deleted or changed in edited circuits Circuit blocks which written in RUN mode cannot be
Circuit blocks in which 1-ms timers (T246 to T249 and T256 to T319) are added in edited circuits Circuit blocks in which the following instructions are included in edited circuits • Instruction to output high speed counters C235 to C255 (OUT instruction) • TBL (FNC152) instruction
System Configuration
•
Version and Peripheral Devices
Number of program steps which can be written for circuit change in RUN mode
4
5
Caution
Program memories which can be written in RUN mode
3
Specifications
Supports write during RUN in the instruction and device ranges in FX1N PLCs Ver.1.00 or later.
Product Introduction
Ver.5.00A or later
2 Features and Part Names
Programming tools supporting write during RUN
Introduction
5.2.5
5.2 Programming Tool Applicability
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
47
Page 54
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.2 Programming Tool Applicability
Item
Caution Avoid write during RUN to a circuit block including the following instructions during execution. If write during RUN is executed to such a circuit block, the PLC decelerates and stops pulse output. • DSZR (FNC150), ZRN (FNC156), PLSV (FNC157) instruction [with acceleration/deceleration operation], DRVI (FNC158) and/or DRVA (FNC159) instruction Avoid write during RUN to a circuit block including the following instruction during execution. If write during RUN is executed to such a circuit block, the PLC immediately stops pulse output. • PLSV (FNC157) instruction [without acceleration/deceleration operation] Avoid write during RUN to a circuit block including the following instructions during execution of communication. If write during RUN is executed to such a circuit block, the PLC may stop communication after that. If the PLC stops communication, set the PLC to the STOP mode once, and then set it to the RUN mode again. • IVCK (FNC270), IVDR (FNC271), IVRD (FNC272) and/or IVWR (FNC273) instruction •
Circuit blocks which written in RUN mode cannot be
•
Instructions for falling edge pulse When write during RUN is completed for a circuit including an instruction for falling edge pulse (LDF, ANDF, or ORF instruction), the instruction for falling edge pulse is not executed without regard to the ON/OFF status of the target device. When write during RUN is completed for a circuit including an instruction for falling edge pulse (PLF instruction), the instruction for falling edge pulse is not executed without regard to the ON/ OFF status of the device that is set as the operation condition. It is necessary to set to ON the target device or operation condition device once and then set it to OFF for executing the instruction for falling edge pulse. Instructions for rising edge pulse When write during RUN is completed for a circuit including an instruction for rising edge pulse, the instruction for rising edge pulse is executed if a target device of the instruction for rising edge pulse or the operation condition device is ON. Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse operation type applied instructions (such as MOVP) Contact ON/OFF status (while write during RUN is executed)
Instruction for rising edge pulse
Instruction for falling edge pulse
OFF
Not executed
Not executed
ON
Executed*1
Not executed
*1 The PLS instruction is not executed. Writing in RUN mode to circuit blocks including the following instructions results in the following operation • MEP instruction (Conversion of operation result to leading edge pulse instruction) When completing Write during RUN to a circuit including the MEP instruction, the execution result of the MEP instruction turns ON (conducting state) if the operation result up to the MEP instruction is ON. • MEF instruction (Conversion of operation result to trailing edge pulse instruction) When completing Write during RUN to a circuit including the MEF instruction, the execution result of the MEF instruction turns OFF (nonconducting state) regardless of the operation result Circuit blocks which require attention (ON or OFF) up to the MEF instruction. on operation after write during RUN When the operation result up to the MEF instruction is set to ON once and then set to OFF, the execution result of the MEF instruction turns ON (conducting state)
• Others
48
Operation result up to MEP/MEF instruction
MEP instruction
MEF instruction
OFF
OFF (nonconducting)
OFF (nonconducting)
ON
ON (conducting)
OFF (nonconducting)
When writing during RUN with GX Developer Ver. 8.72A or later, the program is as follows. When the number of program steps is reduced by deletion of contacts, coils and applied instructions, the program capacity becomes smaller by as many as the reduced number of steps.
Page 55
FX3G Series Programmable Controllers User's Manual - Hardware Edition
5.3 Precautions on Use of (Built-in USB) Programming Port
1
Precautions on Use of (Built-in USB) Programming Port Make sure to set the contents described in this section when executing circuit monitor, device registration monitor, program reading/writing, etc. in the FX3G PLC using the (built-in USB) programming port and GX Developer Ver. 8.72A or later. For GX Developer is prior to Ver. 8.72A, communication using the (built-in USB) programming port is not available.
Installation of USB driver (GX Developer Ver. 8.72A or later)
5.3.2
Setting in GX Developer (Ver. 8.72A or later) 1. Select [Online]
[Transfer setup...] to open the "Transfer setup" dialog box.
3 Product Introduction
It is necessary to install the USB driver to execute USB communication using the (built-in USB) programming port. For the USB driver installation method and procedure, refer to the following manual. → GX Developer Operating Manual (Startup)
2 Features and Part Names
5.3.1
Introduction
5.3
5 Version Information and Peripheral Equipment Connectability
4 Specifications
2. Double-click [Serial] in [PC side I/F] to open the "PC side I/F Serial setting" dialog box. 3. Select "USB (Built-in port)".
5 Version and Peripheral Devices
Double-click it.
6 System Configuration
Select "USB (Built-in port)"
7 Input/Output Nos., Unit Nos.
A display screen is the example of Ver.8.72A.
4. Click the [OK] button to finish the setting.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
49
Page 56
FX3G Series Programmable Controllers User's Manual - Hardware Edition
5.4
5 Version Information and Peripheral Equipment Connectability 5.4 Cautions on using transparent function by way of USB in GOT1000 Series
Cautions on using transparent function by way of USB in GOT1000 Series When monitoring circuits, device registration, etc. or reading/writing programs in an FX 3G PLC from GX Developer Ver.8.22Y or later using the transparent function by way of USB in the GOT1000 Series, make sure to execute the following setting. If the following setting is not provided, a communication error occurs. GX Developer Ver.8.21X or former
GX Developer Ver8.22Y or later*1
Not supported (not available)
Setting shown below is required.
When using transparent function by way of USB in GOT1000 Series
When using transparent function by way of Select "RS-232C" in setting shown below, RS-232 in GOT1000 Series Set "COM port" and "Transmission speed" and set "COM port" and "Transmission on "PC side I/F Serial setting" dialog box. When directly connecting GX Developer to speed". PLC
*1.
GX Developer Ver.8.72A or later supports the FX3G Series.
Setting in GX Developer (Ver. 8.22Y or later) 1. Select [Online]
[Transfer setup...] to open the "Transfer setup" dialog box.
2. Double-click [Serial] in [PC side I/F] to open the "PC side I/F Serial setting" dialog box. 3. Select "USB (GOT Transparent mode)".
Double-click it.
Select "USB (GOT transparent mode)"
A display screen is the example of Ver.8.72A.
4. Click the [OK] button to finish the setting.
50
Page 57
FX3G Series Programmable Controllers User's Manual - Hardware Edition
5.5 Cautions on using transparent port (2-port) function of GOT-F900 Series
1
Cautions on using transparent port (2-port) function of GOT-F900 Series
Introduction
5.5
5 Version Information and Peripheral Equipment Connectability
When monitoring circuits, device registration, etc. in an FX3G PLC from GX Developer Ver. 8.72A or later using the transparent (2-port) function in the GOT-F900 Series, make sure to execute the following setting. If the following setting is not provided, monitoring cannot be executed normally.
Setting shown below is not required.
Setting shown required.
below is not
Select "RS-232C" on "PC side I/F Serial setting" dialog box, and execute setting shown below.
Setting in GX Developer (Ver.8.22Y or later) 1. Select [Online]
[Transfer setup...] to open the "Transfer Setup" dialog box.
3. Put a check mark to the check box [via GOT-F900 transparent mode] as shown below
4 Specifications
2. Double-click [PLC module] in [PLC side I/F] to open the [PLC side I/F Detailed setting of PLC module] dialog box.
3 Product Introduction
Select "RS-232C" on "PC side I/F Select "RS-232C" on "PC side I/F When directly Set "COM port" and "Transmission Serial setting" dialog box, and set Serial setting" dialog box, and set connecting GX Developer speed" on "PC side I/F Serial "COM port" and "Transmission "COM port" and "Transmission to PLC setting" dialog box. speed." speed."
Features and Part Names
GX Developer Ver.8.12N or earlier GX Developer Ver.8.22Y or later GX Developer Ver.8.72A or later When using transparent function in GOT-F900 Series
2
5 Version and Peripheral Devices
Double-click it.
6 System Configuration
Put a check mark to the check box "via GOT-F900 transparent mode."
7 Input/Output Nos., Unit Nos.
A display screen is the example of Ver.8.72A.
8
4. Click the [OK] button to finish the setting.
Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
51
Page 58
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.6 Other Peripheral Equipment Applicability
5.6
Other Peripheral Equipment Applicability
5.6.1
Other Peripheral Equipment Applicability Model name
Applicability
Remarks This series is compatible with the FX3G PLC when GT Designer2 Ver. 2.85P or later is used. GT15 and GT11: Standard monitor OS[03.14.**]or later Communication driver MELSEC-FX[03.14.**]or later Option OS List editor for MELSEC-FX[03.14.**]or later GT10: Standard monitor OS[01.10.**]or later Communication driver MELSEC-FX[01.06.**]or later
GOT1000 Series
Applicable
This series is subject to the following restrictions when connected using unsupported standard monitor OS, communication driver or option OS. Contents of restrictions • Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX1N and FX1NC PLCs. • The list editor function for MELSEC-FX is not available. When using the list editor function for MELSEC-FX, upgrade the standard monitor OS, communication driver and option OS to the version compatible with the FX3G PLC. Check the applicability of other items in the GOT manual.
F940WGOT
Not available
F940GOT F940 Handy GOT Not available F930GOT(-K)
Not available
F920GOT(-K)
Not available
ET-940
Not available
The following restriction applies when connected. Contents of restrictions • Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX1N and FX1NC PLCs. → For applicable models, refer to the GOT manual. For connection using the 2-port interface function*1, refer to Section 5.5. The following restriction applies when connected.
FX-10DM(-SET0)
Not available
Contents of restrictions • Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX1N and FX1NC PLCs. → For supported models and device ranges, refer to the FX10DM USER'S MANUAL (Manual No. JY992D86401). The following restriction applies when connected.
FX-10DU
*1.
52
Not available
Contents of restrictions It is limited to the device range and function range supported by the highest class model (FX1N or FX2N ) applicable in the product version. → For supported models and device ranges, refer to the FX-10DU-E/FX-20DU-E User's Manual (Manual No. JY992D54801).
The F940GOT and ET-940 whose version is former than Ver.1.10 do not support the transparent (2port) function of the GX Developer.