Page 59

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.1 Configuration of a Whole System

1

Examination of System Configuration

6.1

Configuration of a Whole System

Introduction

6.

2 Features and Part Names

The configuration of a whole system is shown below as an example. Configuration of whole system

Memory cassette Expansion board

3

Determination of number of 2 extension devices to be connected to main unit

Product Introduction

1 Expansion board/Special adapters/Memory cassette Display module/Connector conversion adapter Display module

Extension devices for FX2N/FX3U Series

Special adapters

Connector conversion adapter*1

FX3G-40MT/ES X000 to X027

FX2N-16EX X030 to X047

Specifications

Main unit

4

Input extension Output block extension block FX2N-16EYT -

5

3

Y020 to Y037 Range of devices powered from main unit

Refer to this chapter.

Extension devices for FX2N/FX3U Series

7

Input extension Special block*2 function block

Input/Output Nos., Unit Nos.

FX2N-16EX-C FX2N-16CCL-M Unit No.0 X070 to X107

Refer to Chapter 19.

The range of devices powered from the FX2N input/output powered extension unit or the extension power supply unit

8 Installation

Y040 to Y057

6 FX Series terminal block

System Configuration extension power supply unit

FX2N-32ER-ES/UL X050 to X067

6

Selection of extension cable

4 Determination of number of devices to be connected to extension unit/ FX2N input/output powered extension unit Extension power supply unit

Version and Peripheral Devices

Y000 to Y017

5 When CC-Link is used

9 Preparation and Power Supply Wiring

*1 The connector conversion adapter is required to use a special adapter. *2 Included in the number of units connectable to the main unit when the input extension block (including the FX2N-8ER-ES/UL and FX2N-8ER) is used and the extension power supply unit is located on the upstream side.

10 Input Wiring

53

Page 60

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.1.1

6.1 Configuration of a Whole System

Expansion board/connector conversion adapter/memory cassette/display module configuration The connection positions and number of expansion boards, connector conversion adapter and memory cassette configuration vary depending on the number of points in main units. For details, refer to the description below. • In the case of the main units(40/60 point type) Main unit

BD1 (2nd position)

BD2 (2nd position)

BD1 (1st position)

BD2 (1st position)

BD1 (2nd position) BD1 (1st position)

BD2 (2nd position) BD2 (1st position)

Main unit

(Side)

(Front panel)

Available connection position

Model name

BD1 (1st position)

BD1 (2nd position)

Expansion board (Except FX3G-8AV-BD) FX3G-8AV-BD

-

Connector conversion adapter (FX3G-CNV-ADP)

BD2 (1st position)

-

-

-

-

Memory cassette*1

*2

Display module*1

BD2 (2nd position)

-

-

*2*3

-

-

*4*5

*1.

When the memory cassette and display module are used together, the transfer function of the memory cassette is not available. Use the display module to transfer data stored in the memory cassette.

*2.

Can be connected in any position however only one device can be connected at one time.

*3.

The memory cassette cannot be connected when the display module is connected to the BD2 (1st position).

*4.

Only the BD2 (1st position) and the BD2 (2nd position) can be used for connection. Only one display module can be connected to the main unit.

*5.

The display module cannot be connected when the memory cassette is connected to the BD2 (1st position).

• In the case of the main units(14/24 point type) Main unit

BD (2nd position) BD (1st position)

BD (2nd position) BD (1st position)

Main unit

(Side)

(Front panel) Model name

Available connection position BD (1st position)

Expansion board Connector conversion adapter (FX3G-CNV-ADP)

54

BD (2nd position) -

Memory cassette

*1

*1*2

Display module

*1

*1*3

*1.

Can be connected in either position only one device can be at one time.

*2.

The memory cassette cannot be connected when the display module is connected to the BD (1st position).

*3.

The display module cannot be connected when the memory cassette is connected to the BD (1st position).

Page 61

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

1

Rules of System Configuration

Introduction

6.2

6.2 Rules of System Configuration

The system configuration must meet the following four requirements.

1 Number of input/output points

2

→ For details, refer to 6.3 Number of Input/Output Points and Maximum Number of Input/Output Points. Number of input/output points on whole system

Up to 256 points

· Expansion board · Special adapter

Main unit

Input/output extension unit/block

Special function block

3 Up to 128 points

CC-Link/LT master

Product Introduction

1. Number of input/output points (including input/output occupied points)

CC-Link master

4

CC-Link/LT Remote I/O station

2. Number of remote I/O points

Remote I/O station

Specifications

Remote I/O station

Remote I/O station

Up to 128 points

5

Remote I/O station

Remote I/O station

Version and Peripheral Devices

CC-Link system Remote I/O station

Remote I/O station

6

The figure below shows the number of connectable expansion boards, special adapters, extension power supply units and special function blocks. The connector conversion adapter (FX3G-CNVADP) is required as the expansion board when special adapters are connected. → For details, refer to 6.4 Number of Connected Extension Devices (Including Extension Cable).

Special adapter (communication)

Expansion board

Up to 2 units

Up to 2 units

Up to 2 units

Main unit 40/60 point type

Input/output Extension Special powered power supply function block extension unit unit Up to 2 units

Only 1 unit

Up to 8 units

8

Special adapter (communication)

Expansion board

Only 1 unit

Only 1 unit

Only 1 unit

Main unit 14/24 point type

Installation

• FX3G Main units (14/24 point type) Special adapter (analog)

Input/output Extension Special powered power supply function block extension unit unit Up to 2 units

Only 1 unit

7 Input/Output Nos., Unit Nos.

• FX3G Main units (40/60 point type)

System Configuration

2 Number of connected special extension devices

Special adapter (analog)

Features and Part Names

The total number of input and output points should be 256 or less in the whole system.

9

Up to 8 units

Preparation and Power Supply Wiring

10 Input Wiring

55

Page 62

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.2 Rules of System Configuration

3 Connection restriction and calculation of current consumption The number of points and number of units connected are restricted by the number of extension blocks connected to the main unit. The built-in power supply of the input/output powered extension unit and extension power supply unit supplies the power to a unit/block/board extended to the corresponding unit. The built-in power supply refers to the 24V DC service power supply, 5V DC power supply and internal 24V DC power supply.The consumed power varies depending on the type of extended unit/block/board. Special Expansion Main unit board adapter

Power supply from main unit

Power supply from main unit Refer to Section 6.4.

*1.

Extension block (some blocks can be connected)

Refer to Section 6.5.

Input/output Extension block Extension Extension block powered (some blocks can power supply (some blocks can extension unit be connected) be connected) unit Power supply from input/output powered extension unit Refer to Section 6.6.

Power supply from extension power supply unit*1 Refer to Section 6.7.

When connecting an input extension block on the downstream side of an extension power supply unit, supply the power to the input extension block from the nearest main unit on the upstream side, or from an input/output powered extension unit on the upstream side of the extension power supply unit. In the example above, the input/output powered extension unit supplies the power to extension blocks. → For details, refer to 6.5 Expansion of Main Unit. → For details, refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit. → For details, refer to 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V).

4 Other restrictions • Restrictions in the use of the FX3G-422-BD - When connecting a device (such as GOT) which consumes an internal 5V DC to each of the RS-422 port built in the main unit and the FX3G-422-BD at the same time, avoid continuous use of either device. If both devices are used continuously, their life may be shortened due to heat generation. <Configuration example 1> RS-422 port built-in main unit + GT1020LBL (5V DC type) FX3G-422-BD + GT1020LBL (5V DC type) Avoid continuous use of two GT1020LBL (5V DC type) units. - When connecting a device (such as GOT) which consumes an internal 5V DC to each of two FX3G-422BD units connected to the (40-point/60-point type) main unit, avoid continuous use of either device. If both devices are used continuously, their life may be shortened due to heat generation. <Configuration example 2> When connecting the 40-point type main unit and two FX3G-422-BD units FX3G-422-BD + GT1020LBL (5V DC type) FX3G-422-BD + GT1020LBL (5V DC type) Avoid continuous use of two GT1020LBL (5V DC type) units. - It is not allowable to connect a device (such as GOT) which consumes an internal 5V DC to each of the RS-422 port in the (40-point/60-point type) main unit and two FX3G-422-BD units (3 channels in total) at the same time.

56

Page 63

FX3G Series Programmable Controllers User's Manual - Hardware Edition

6 Examination of System Configuration 6.3 Number of Input/Output Points and Maximum Number of Input/Output

Number of Input/Output Points and Maximum Number of Input/Output Points

6.3.1

Calculation of number of input/output points

2

1 Total the number of input/output points on the main unit and the number of To obtain the total number of input/output points, count the input points (X000 and more) and output points (Y000 and more) of the main unit and input/output powered extension units/blocks. The number of input/output points of each type of device is shown on the list below. → The list of numbers of input/output points is shown in Section 6.8.

64CL-M network.

Add the number of remote I/O points to the number of input/output points from the main unit and input/output powered extension units/blocks calculated in the above step. → For the remote I/O point calculation method, refer to the FX2N-64CL-M manual.

The number of occupied input/output points per unit is 8. The number of occupied input/output points of each type of device can be obtained by the following formula or from the list shown below.

units

Number of occupied input/output points points

7

8 points Each special function block used for FROM/TO instructions occupies eight input or output points.

Input/Output Nos., Unit Nos.

Number of special function blocks

Number of points per unit number of = Total occupied input/ output points

Observe the following instructions when using the following products.

FX3U-64CCL Only one FX3U-64CCL unit can be connected to a single PLC main unit

8 Installation

• FX2N-16CCL-M(CC-Link master) When more than one master station is connected, a remote I/O station cannot be connected to the 2nd and following master stations. •

6 System Configuration

→ For a list of occupied input/output points, refer to Section 6.8.

5 Version and Peripheral Devices

3 Count the number of input/output occupied points of special function blocks.

4 Specifications

2 Count the input/output points of the remote I/O stations connected on FX2N-

3 Product Introduction those on the input/output powered extension units/blocks.

Features and Part Names

To obtain the total number of input/output points, count the input/output points of input/output powered extension units/blocks and the input/output occupied points of special function blocks. The number of remote I/O points on CC-Link network must be excluded.

Number of special function blocks

Introduction

6.3

1

9 Preparation and Power Supply Wiring

10 Input Wiring

57

Page 64

FX3G Series Programmable Controllers User's Manual - Hardware Edition

6 Examination of System Configuration 6.3 Number of Input/Output Points and Maximum Number of Input/Output

4 Calculate the total number of input/output points. Total the number of points counted in Steps 1, 2 and 3, and check that it does not exceed 128 points (maximum number of input/output points). Maximum number of input/output points

128 points Maximum number of points controllable on system

Number of input/output occupied points

Number of input/output points

(A) +

(D)

+

(B)

+

(C)

(E)

units

8 points

+ Each special function unit/block used for FROM/TO instructions Total number of input/output points of input/ occupies eight input or output output powered extension units and input/output points. extension blocks (A) : Number of input/output points of main unit (D) : Number of remote I/O points of FX 2N-64CL-M (E) : Number of special function blocks (B) : Number of input/output points of input/ output powered extension units (C) : Number of input/output points of input/ output extension blocks

5 When CC-Link master is used, count the remote I/O points. When CC-Link is used, the total number of input/output points of the remote I/O stations connected on the network and the number of input/output points calculated in the previous step are 256 or less. 1. FX2N-16CCL-M (CC-Link master) Calculate the number of remote I/O points connected on the network in the following step.

58

Page 65

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

1

Maximum number of input/output points when CC-Link master is used

Introduction

6.3.2

6.3 Number of Input/Output Points and Maximum Number of Input/Output

1. Calculation of maximum number of input/output points When CC-Link master block is used, the following maximum number of input/output points can be connected. Number of input/ output points

256 points

(A)(B)(C)(D)

(E)

Total number of input/output points

8 points units

2

CC-Link remote I/O

(F) stations

32 points number of points obtained by + Number of points occupied by + Total formula "number of remote I/O special function blocks stations 32 points" (The number is multiplied by 32 points regardless of the number of remote I/O points.)

For details, refer to Subsection 6.3.1.

*1.

2. Procedures for calculating number of input/output points based on example of system configuration For the main unit, input/output powered extension units/blocks and CC-Link remote I/O stations, the number of input/output points and the total number of points are restricted. Input/output powered extension unit

Input extension block

Input extension block

Y000 to Y017 Y020 to Y037 24/16=40 16/16=32 points points

16/0=16 points

8/0=8 points

Main unit

-

-

Special FX2N-16CCL-M function block 8 points

8 points

-

7 Input/Output Nos., Unit Nos.

CC-Link network Remote I/O (32 points)

Remote I/O (32 points)

Remote I/O (32 points)

8

96 112 Number of input/output points (96 points)

128

160

256 points

Number of remaining points

9 Number of remaining points

Preparation and Power Supply Wiring

Number of input/output points (excluding remote I/O points on CC-Link) + Number of input/output occupied points Up to 128 points

Installation

Number of input/output points occupied by special function blocks(16 points) 0 points

6 System Configuration

X000 to X027 X030 to X047 X050 to X067 X070 to X107

5 Version and Peripheral Devices

When four 32-point type remote I/O stations are used, the number of CC-Link remote I/O points reaches the maximum number. The number of CC-Link points is calculated by the formula "32 points number of stations" even when remote I/O stations having less than 32 points are used. For details, refer to FX2N-16CCL-M User's Manual.

4 Specifications

(D) : Number of remote I/O points of FX 2N-64CL-M (A) : Number of input/output points of main unit (B) : Number of input/output points of input/output (E) : Number of input/output points occupied by special function blocks powered extension units (F) : Number of remote I/O stations (units) connected to CC-Link (C) : Number of input/output points of input/output master extension blocks

3 Product Introduction

Maximum number of points controllable on system

Number of input/output occupied points

Features and Part Names

Maximum number of input/output points

32 points 3 units = 96 points

10

Number of CC-Link input/output points

Input Wiring

128 points or less in total 256 points or less in total

59

Page 66

FX3G Series Programmable Controllers User's Manual - Hardware Edition

6 Examination of System Configuration 6.4 Number of Connected Extension Devices (Including Extension Cable)

6.4

Number of Connected Extension Devices (Including Extension Cable)

6.4.1

Number of connectable expansion boards and special adapters The number of connectable expansion boards and special adapters varies depending on the number of points in the main unit. The connector conversion adapter (FX3G-CNV-ADP) is required to connect the special adapter. → For assignment of communication channels, refer to Section 7.3. • In the case of Main units (40/60 point type) Use of expansion board

Number of connectable expansion boards

When expansion board is not used

0

When expansion board is used

1 unit

Number of connectable special adapters of each type Communication special adapters

Analog special adapters

2 units

2 units

1 unit

2 units

Communication expansion board*1 Analog expansion board 2 units*2

2 units

1 unit

Cannot be connected.

Cannot be connected.

*1.

FX3G-8AV-BD included.

*2.

Only one FX3G-8AV-BD can be connected to a single PLC main unit.

• In the case of Main units (14/24 point type) Use of expansion board

Number of connectable expansion boards

When expansion board is not used When expansion board is used

6.4.2

Number of connectable special adapters of each type Communication special adapters

Analog special adapters

0

1 unit

1 unit

1 unit

Cannot be connected.

Cannot be connected.

Input/output powered extension units Up to 2 input/output powered extension units can be connected in one system.

6.4.3

Extension Power Supply Unit Only one extension power supply unit (FX3U-1PSU-5V) unit can be connected to a single PLC main unit.

6.4.4

Special function blocks Up to 8 special function units/blocks can be connected in one system. When connecting the following products, take into consideration the combination, number of units/blocks and connecting order. Type

6.4.5

Limitations

FX3U-64CCL

Only one FX3U-64CCL unit can be connected to a single PLC main unit.

FX2N-16CCL-M

When some units are used, a remote I/O station cannot be connected to the second and following master stations.

FX2N-2AD FX2N-2DA

When any of these products is connected to a FX2N Series input/output powered extension unit, the current consumption is restricted. The total current consumption of FX2N-2AD and FX2N-2DA must be the following value or less. - FX2N-32E : 190mA or less - FX2N-48E : 300mA or less

Extension cable One extension cable can be used in a system. The FX2N-CNV-BC is required when the extension block is connected. • FX0N-65EC(650mm(25.59")) • FX0N-30EC(300mm(11.81"))

60