Page 67
FX3G Series Programmable Controllers User's Manual - Hardware Edition
6.5 Expansion of Main Unit
1
Expansion of Main Unit The allowable extension to the main unit varies depending on used extension blocks as described below.
1. When connecting only the input/output extension block
2 Features and Part Names
Input/output extension blocks of up to 32 points can be connected. However, when the extension power supply unit (FX3U-1PSU-5V) is used and the main unit is the nearest upstream unit to the extension power supply unit, make sure that the number of points including the input extension block (including the FX2N-8ER-ES/UL and FX2N-8ER) extended to the extension power supply unit does not exceed 32.
Introduction
6.5
6 Examination of System Configuration
3
Input/output extension blocks of up to 16 points can be connected. However, when the extension power supply unit (FX3U-1PSU-5V) is used and the main unit is the nearest upstream unit to the extension power supply unit, make sure that the number of points including the input extension block (including the FX2N-8ER-ES/UL and FX2N-8ER) extended to the extension power supply unit does not exceed 16.
Product Introduction
2. When connecting the input/output extension block and special function block
4 Specifications
Only 1 special function block can be connected.
3. When connecting only the special function block
5
When further extension is required, judge whether extension is possible using one of the following methods: • Using the 24V DC service power supply (400mA) of the main unit
Version and Peripheral Devices
Up to 2 special function blocks can be connected.
6
• Using an input/output powered extension unit
System Configuration
• Using an extension power supply unit For details, refer to the following. → Refer to 6.5.1 When adding input/output extension blocks using the 24V DC service power supply of the main unit. → Refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit. → Refer to 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V).
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
61
Page 68
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
6.5.1
6.5 Expansion of Main Unit
When adding input/output extension blocks using the 24V DC service power supply of the main unit If extension is not allowed due to restrictions in connection to the main unit described in the preceding subsection, extension blocks can be added using the 24V DC service power supply of the main unit. For adding extension blocks using the 24V DC service power supply, it is necessary to examine again whether extension is possible for all of extension blocks selected in the preceding subsection and extension blocks to be selected in this subsection. Note that only up to two network-related special function blocks can be connected including extension to the main unit.
1 Confirm the priority of all extension blocks to be connected to the main unit. The priority is set to each extension block to be connected, and required to judge the possibility of extension to the main unit. The priority is determined by the extension block type without regard to the connection position. When the extension power supply unit (FX3U-1PSU-5V) is used and the nearest upstream unit to the extension power supply unit is the main unit, the priority should be considered also for input extension blocks (including the FX2N-8ER-ES/UL and FX2N-8ER) extended to the extension power supply unit. <Priority> Priority High Special function block Priority 1
Output extension block
>
Priority 2
>
FX2N-8ER-ES/UL FX2N-8ER Priority 3
>
Priority Low Input extension block Priority 4
2 Judge whether extension to the main unit is possible. Judge the possibility of extension to the main unit for all extension blocks in turn, starting from the extension block having the highest priority confirmed in step 1. Consider that 16 input/output points are provided in each of the FX2N-8ER-ES/UL and FX2N-8ER. Eight output points have higher priority over 8 input points. Refer to the preceding subsection for judgment about the possibility of extension to the main unit.
3 Check whether extension from the 24V DC service power supply is possible. Check using the quick reference matrix shown below whether the number of points whose extension is judged as impossible in step 2 can be added using the 24V DC service power supply. A special function block is handled in the same way as 16 output points. Number of added points
Output
(Example) 16 100
0
8 250 150
50
0 400 300 200 100 0
0
8 16 24 32 Number of added points Input
Example: When 8 input points and 8 output points are connected, the current of the 24V DC service power supply becomes 150mA or less.
62
Page 69
FX3G Series Programmable Controllers User's Manual - Hardware Edition
6 Examination of System Configuration 6.5 Expansion of Main Unit value shown in the quick reference matrix.
→ Refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit.
2 Features and Part Names
This remaining power supply capacity (current) can be used as power supply for external loads (such as sensors) by the user. If it is not possible to connect input/output extension blocks even using the 24V DC service power supply of the main unit, consider adding an input/output powered extension unit to the system.
Introduction
4 Confirm the current capacity of the 24V DC service power supply from the
1
3 Product Introduction
4 Specifications
5 Version and Peripheral Devices
6 System Configuration
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
63
Page 70
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
6.5.2
6.5 Expansion of Main Unit
Selection example 1 using the 24V DC service power supply of the main unit This subsection explains an example in which 8 input points and 16 output points are added to the following system configuration using the 24V DC service power supply of the main unit. <Example of configuration> Input extension block 8 points
Main unit
Special function block FX3U-64CCL
Output extension block 8 points
Range extendible to main unit (Special function block 1unit + Input/output 16 points)
Output extension block 16 points
Input extension block 8 points
Extension blocks to be added (Input 8 points + Output 16 points)
1 Confirm the priority of all extension blocks to be connected to the main unit. The priority is determined by the extension block type without regard to the connection position from the main unit as shown below. <Priority> Main unit
Input extension block 8 points
Special function block FX3U-64CCL
Priority 3
Priority 1
Output extension block 8 points
Output extension block 16 points
Priority 2
Input extension block 8 points
Priority 3
2 Judge whether extension to the main unit is possible. Judge the possibility of extension to the main unit for all extension blocks in turn, starting from a block having the highest priority confirmed in step 1. In this example, due to the restriction "one special extension block and 16 points in input/output extension block", the only FX3U-64CCL (priority 1) and 16 points of the output extension block (priority 2) can be connected to the main unit.
3 Check whether extension from the 24V DC service power supply is possible. Check using the quick reference matrix whether 16 input points and 8 output points whose extension is judged as impossible in step 2 can be added. Number of added points
Output
16 100
0
8 250 150
50
0 400 300 200 100
0
0
8 16 24 32 Number of added points Input
After 16 input points and 8 output points are connected, the remaining current of the 24V DC service power supply is 50mA or less. Accordingly, it is possible to add 16 input points and 8 output points. The remaining power supply capacity (50mA) can be used as power supply for external loads (such as sensors) by the user.
64
Page 71
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
1
Selection example 2 using the 24V DC service power supply of the main unit This subsection explains an example in which FX2N -2AD and 8 output points are added to the following system configuration using the 24V DC service power supply of the main unit. <Example of configuration> Special function block FX3U-64CCL
Output extension block 8 points
Range extendible to main unit (Special function block 1unit + Input/output 16 points)
Special function block FX2N-2AD
Output extension block 8 points
Extension blocks to be added (Special function block 1unit + output 8 points)
The priority is determined by the extension block type without regard to the connection position from the main unit as shown below.
4
<Priority> Input extension block 8 points
Special function block FX3U-64CCL
Output extension block 8 points
Special function block FX2N-2AD
Output extension block 8 points
Priority 3
Priority 1
Priority 2
Priority 1
Priority 2
5
Judge the possibility of extension to the main unit for all extension blocks in turn, starting from a block having the highest priority confirmed in step 1. In this example, due to the restriction "two special function blocks", only the FX3U-64CCL (priority 1) and FX2N-2AD (priority 1) can be connected to the main unit.
Check using the quick reference matrix whether 8 input points and 16 output points whose extension is judged as impossible in step 2 can be added. Output
8
50 0
8 16 24 32 Number of added points Input
After 8 input points and 16 output points are connected, the remaining current of the 24V DC service power supply is 50mA or less. Accordingly, it is possible to add 8 input points and 16 output points.
Installation
0 400 300 200 100
0
7 Input/Output Nos., Unit Nos.
0
8 250 150
6 System Configuration
3 Check whether extension from the 24V DC service power supply is possible.
Version and Peripheral Devices
2 Judge whether extension to the main unit is possible.
16 100
Specifications
Main unit
Number of added points
3 Product Introduction
1 Confirm the priority of all extension blocks to be connected to the main unit.
2 Features and Part Names
Input extension block 8 points
Main unit
Introduction
6.5.3
6.5 Expansion of Main Unit
9 Preparation and Power Supply Wiring
10 Input Wiring
65
Page 72
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
6.6
6.6 Expansion of FX2N Series I/O Powered Extension Unit
Expansion of FX2N Series I/O Powered Extension Unit When extension is not possible due to the main unit connection restrictions described in the preceding section and extension of input/output is required, select the input/output powered extension unit. Since input/output powered extension units have built-in input/output terminals, reexamine the input/output devices connected to the main unit to ensure the required number of points. Range to be covered by main unit
Range exceeding power supply capacity
Before selection
Main unit
Input/output Input extension Special Special Output extension extension block function block function block block (16 points) block (16 points)
After selection
Main unit
Input/output Input/output powered Special Special extension extension unit function block function block block (32 points) Replaced with input/output powered extension unit
Determine whether extension devices can be connected to the input/output powered extension unit by the following method. • When only input/output extension devices are added, use the quick reference matrix. → Refer to 6.6.1 Quick reference matrix (when only input/output devices are added). • When also special extension devices are added, calculate the current consumption to ensure that the total current to be consumed by the added extension devices can be supplied by the built-in power supply. → Refer to 6.6.2 When special extension devices are also added (calculation of current consumption).
6.6.1
Quick reference matrix (when only input/output devices are added) In the following quick reference matrix, the value at the intersection of the number of input points to be added (horizontal axis) with the number of output points to be added (vertical axis) indicates the remaining power supply capacity.
1 Select the input/output extension block (number of points) to be connected to the main unit.
Check that the number of input/output points can be added. When connecting the FX3U-1PSU-5V extension power supply unit to a system where the nearest upstream unit to the FX3U-1PSU-5V is an input/output powered extension unit, include the current consumption by the input extension blocks (including FX2N-8ER-ES/UL and FX2N-8ER) connected to the FX3U-1PSU-5V when calculating the total current consumption of the input/output powered extension unit. 1. AC power supply/DC input type 1) FX2N-32ER, FX2N-32ET, FX2N-32ES FX2N-32ER-ES/UL, FX2N-32ET-ESS/UL
FX2N-32E
Output
Number of added points
AC power supply DC input type
24
25
16 100
(Example) 50
0
8 175 125
75
25
0 250 200 150 100 0
50
8 16 24 32 Number of added points
Input
(Example) When a 16-input and 0-output point extension block is connected to FX2N-32E , the current of the 24V DC service power supply becomes 150mA or less.
66
Page 73
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
6.6 Expansion of FX2N Series I/O Powered Extension Unit
1
FX2N-48E
Output 48
10
40
85
(Example)
2
35
32 160 110
60
10
24 235 185 135
85
Features and Part Names
Number of added points
AC power supply DC input type
Introduction
2) FX2N-48ER, FX2N-48ET FX2N-48ER-ES/UL, FX2N-48ET-ESS/UL
35
16 310 260 210 160 110
60
10
8 385 335 285 235 185 135
85
35
0 460 410 360 310 260 210 160 110 8
16
24 32 40 48 56 Number of added points
64
3 Input
(Example) When a 32-input and 16-output point extension block is connected to FX2N-48E , the current of 24V DC service power supply becomes 110mA or less.
2. AC power supply/AC input type
4
Output (Example)
48
5
40 32
Version and Peripheral Devices
Number of added points
FX2N-48ER-UA1/UL
Specifications
1) FX2N-48ER-UA1/UL (24V DC service power supply is not provided.) AC power supply DC input type
Product Introduction
0
60
24 16 8 0 0
8
16
64
6
Input
(Example) When adding 24 inputs to FX2N-48ER-UA1/UL, a maximum of 32 outputs are expandable
2 Check the current capacity of the 24V DC service power supply based on the value shown in the quick reference matrix.
System Configuration
24 32 40 48 56 Number of added points
7
The remaining power supply capacity (current) can be used as a power supply to loads (sensors or the like). When special adapters and special function units/blocks are connected by external wiring, it is necessary to consider whether they can be covered by the remaining power supply capacity.
Input/Output Nos., Unit Nos.
1. In the case of AC power supply/DC input type
8
2. In the case of AC power supply/AC input type
3 When the power supply capacity is insufficient, connect another input/output
Installation
24V DC service power supply is not provided.
powered extension unit.
9 Preparation and Power Supply Wiring
When two input/output powered extension units or more are connected, calculate the power supply capacities of the input/output extension blocks and special function blocks connected to them, and check the capacity.
10 Input Wiring
67
Page 74
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
6.6.2
6.6 Expansion of FX2N Series I/O Powered Extension Unit
When special extension devices are also added (calculation of current consumption)
1 Select an input/output powered extension unit.
→ For the data on the number of input/output occupied points and current consumption of each type,refer to Section 6.8.
Power supply classification
1
With built-in power supply
Classification
Number of connected units
B1
Input/output powered extension unit
-
Example of entry
Type
Number of input/ output points [points]
Capacity of built-in power supply 5V DC power supply [mA]
24V DC service power supply [mA]
1 -1
1 -2
1 -3
48
690
460
FX2N-
FX2N-48ER-ES/UL
2 Enter the specifications for the products to be added. Enter the data for the input/output extension blocks and special function blocks to be connected to the input/output powered extension unit, and calculate the current. → For data on the number of input/output occupied points and current consumption of each type, refer to Section 6.8. Power supply classification
Classification
Number of connected units
B2
Input/output extension Enter the products connected to the input/ output powered extension unit
- block*1
Type
Number of input/ output points [points]
Calculation of current consumption of built-in power supply 5V DC power supply [mA]
FX2N-
-
FX2N-
-
FX2N-
-
FX2N-
-
FX2N-
-
FX2N-
-
FX2N-
-
FX2N-
-
24V DC power supply [mA]
FX2N/FX3UFX2N/FX3U-
C
Special function unit/block
FX2N/FX3U8*2
FX2N/FX3UFX2N/FX3UFX2N/FX3UFX2N/FX3U-
2
FX2N/FX3U-
2 -1
2 -2
2 -3
Calculate the totals
68
*1.
When connecting the FX3U-1PSU-5V extension power supply unit to a system where the nearest upstream unit to the FX3U-1PSU-5V is input/output powered extension unit, also enter the current consumption and number of occupied I/O points for the input extension blocks (including FX2N-8ERES/UL and FX2N-8ER) that are connected to the FX3U-1PSU-5V.
*2.
A maximum of 8 special function blocks are connectable, including the main unit and extension power supply unit.