FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 6. Examination of System Configuration, pages 75 to 80

Pages 75 to 80 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 75

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.6 Expansion of FX2N Series I/O Powered Extension Unit

1

Determine the number of analog special function blocks (FX2N-2AD and FX2N-2DA) to be connected to the input/output powered extension unit by the following method.

2

• When connecting to FX2N-32E

50mA

Features and Part Names

Total current consumption

Analog special function block FX2N-2AD

FX2N-2DA units

+

85mA units

= mA

190mA

3 Product Introduction

• When connecting to FX2N-48E Total current consumption

Analog special function block FX2N-2AD

4

FX2N-2DA units

+

85mA units

= mA

Specifications

50mA

300mA

4 Determine whether the devices can be added to the input/output powered

5 Version and Peripheral Devices extension unit.

Calculate the current to confirm whether the selected extension devices can be connected. 1. Calculate the current consumption of the built-in 24V DC power supply (24V DC service power supply).

Capacity of 24V DC power supply

Current consumption

Input/output powered extension unit

Total of current consumed by extension devices

2 -3 mA

= mA

7

0mA

Input/Output Nos., Unit Nos.

mA

-

Calculation result

2. Calculate the current consumption of the built-in 5V DC power supply. Current consumption

Input/output powered extension unit

Total of current consumed by extension devices

1 -2 mA

-

2 -2 mA

Calculation result

= mA

8 Installation

Capacity of 5V DC power supply

6 System Configuration

The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24V DC service power supply, and the capacity can be used for external loads.

1 -3

Introduction

3 Determine whether FX2N-2AD and FX2N-2DA can be added.

0mA

9 Preparation and Power Supply Wiring

If the calculation results for the current consumption of the 24V DC power supply and 5V DC power supply are negative values, the current consumption exceeds the capacity of the built-in power supply. Reconfigure the system, adding input/output powered extension units or extension power supply units.

10 Input Wiring

69

Page 76

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.7

6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)

Expansion of Extension Power Supply Unit (FX3U-1PSU-5V) If the selected devices in Section 6.5 are not connectable due to the built-in 5V DC power shortage, add an extension power supply unit.

1 Enter the current supply specification of the extension power supply unit. The output current of the extension power supply unit is proportional to the ambient temperature as shown by the derating curve below. Enter the output current value, based on this derating curve. Also verify that the number of occupied input/output points from input/output extension block(s) connected to the extension power supply unit is less than 32. Derating curve Output current [A] 5V DC 1.0 0.8 24V DC 0.3 0.2 40 55 Ambient temperature [°C]

0

Power supply classification

Classification

Capacity of built-in power supply

Number of connected units

Type

5V DC power supply [mA]

Power supply for internal 24V DC [mA]

3 -1

3 -2

3 With built-in power supply

D1

Extension power supply unit

-

FX3U-1PSU-5V

Connectable I/O occupied points [points]

3 -3

32

2 Enter the specifications for the products to be added. Enter the data on the input/output extension blocks and special function units/blocks to be connected to the input/output powered extension unit, and calculate the current. → For the data on the number of input/output occupied points and current consumption of each type, refer to Section 6.8. Power supply classification

Classification

Number of connected units

B2

Input/output extension Enter the products connected to the extension power supply unit

4 70

- block*2

C

Special function unit/block

8*3

Capacity of built-in power supply Type

5V DC power supply [mA]

FX2N-

-

FX2N-

-

FX2N-

-

FX2N-

-

Number of I/O occupied points*1 {points]

FX2N/FX3U-

-

FX2N/FX3U-

-

FX2N/FX3U-

-

FX2N/FX3U-

-

FX2N/FX3U-

-

FX2N/FX3U-

-

FX2N/FX3U-

-

FX2N/FX3U-

-

4 -1 Calculate the totals

Power supply for internal 24V DC [mA]

4 -2

4 -3

Page 77

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

1

Input/output occupied points by special function blocks are excluded.

*2.

*3.

A maximum of 8 special function units/blocks are connectable, including the main unit and the input/ output powered extension unit.

3 Determine whether the devices can be added to the extension power supply

3 Product Introduction unit.

2 Features and Part Names

For the input extension block (including the FX2N-8ER-ES/UL and FX2N-8ER), it is not necessary to calculate the current consumption of the internal 24V DC. Include the input extension block in calculation for the nearest main unit or input/output powered extension unit located on the upstream side to the extension power supply unit. → When the main unit is on the upstream side, refer to Subsection 6.5.1 and Subsection 6.5.2. → When the input/output powered extension unit is on the upstream side, refer to Subsection 6.6.1 and Subsection 6.6.2.

Introduction

*1.

6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)

Calculate the current to confirm whether the selected extension devices can be connected. 1. Calculate the current consumption of the built-in 5V DC power supply. Capacity of 5V DC power supply

Current consumption

Extension power supply unit

Total of current consumed by extension devices

3 -1

-

4 -1 mA

= mA

Specifications mA

4

Calculation result

0mA

5

Total of current consumed by extension devices

3 -2

-

Current consumption

4 -2 mA

Calculation result

= mA

6 mA

0mA

3. Calculate the available input/output occupied points (excluding the occupied input/output by special function blocks). Connectable I/O occupied points

Number of I/O occupied points

Extension power supply unit

Total of I/O occupied points by extension devices

3 -3

-

4 -3 points

7

Calculation result

= points

Input/Output Nos., Unit Nos.

points

System Configuration

Power supply capacity for internal 24V DC Extension power supply unit

Version and Peripheral Devices

2. Calculate the available current supply from the internal 24V DC power supply.

0points

8 Installation

If the calculation result for the 5V DC power supply is a negative value, the current consumption exceeds the power supply capacity. If the calculation result for the internal 24V DC is a negative value, the current consumption exceeds the power supply capacity. If the calculation result for the number of occupied input/output points is a negative value, the available number of input/output points is exceeded. Reconfigure the system with an input/output powered extension unit.

9 Preparation and Power Supply Wiring

10 Input Wiring

71

Page 78

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.8

6.8 Number of Input/Output (Occupied) Points and Current Consumption

Number of Input/Output (Occupied) Points and Current Consumption The following tables show the number of input/output points or the number of input/output occupied points for each type of device, along with the power supply type and current consumption values needed for selecting a product. • Number of input/output points or input/output occupied points on each type of device • Output current of 24V DC service power supply of main units • Output current of 5V DC power supply and 24V DC service power supply of input/output powered extension units • Current consumed by input/output extension blocks and special function blocks The current consumption is determined differently in the following cases. • In the input/output powered extension unit, 5V DC and internal 24V DC are supplied via extension cables.It is necessary to calculate the current consumption.Subtract the current consumption of the internal 24V DC from the 24V DC service power supply. • The special function units/blocks connected to the AC power type main unit or to the 24V DC service power supply terminal of the input/output powered extension unit consume the external 24V DC. Include the current in the calculation of current consumption. When the terminal is connected with an external power supply, the current is not included in the calculation of current consumption.

6.8.1

[A] Main units Input/output

A No.

Type

Number of input/ output points [points]

Output current (mA)

Input/output [points]

24V DC service power supply

AC power supply/24V DC input/transistor output type

A1 *1.

6.8.2

FX3G-14MT/ES

14(16)*1

8/6(8)

FX3G-24MT/ES

24(32)*1

14(16)/10(16)

FX3G-40MT/ES

40

24/16

FX3G-60MT/ES

60(64)*1

36(40)/24

400

Each number inside ( ) indicates the number of occupied points. Use numbers inside ( ) when calculating the total number of input/output points.

[B] Input/output powered extension units/blocks 1. Input/output powered extension units Input/output

B No.

B1

72

Type

Output current (mA)

Number of input/ output points [points]

Input/output [points] 16/16

FX2N-32ER-ES/UL

32

FX2N-32ET-ESS/UL

32

16/16

FX2N-32ER

32

16/16

FX2N-32ES

32

16/16

FX2N-32ET

32

16/16

FX2N-48ER-ES/UL

48

24/24

FX2N-48ET-ESS/UL

48

24/24

FX2N-48ER

48

24/24

FX2N-48ET

48

24/24

5V DC power supply

24V DC service power supply

250 690

460

Page 79

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.8 Number of Input/Output (Occupied) Points and Current Consumption

1

B

No.

Type

Number of input/ output points

Introduction

2. Input/output extension blocks Current consumed (mA) 5V DC

Internal 24V DC

Types for addition of input/output 16*1

-

62.5

FX2N-8ER

16*1

-

62.5

FX2N-8EX-ES/UL

8

-

50

FX2N-8EX

8

-

50

FX2N-8EX-UA1/UL

8

-

50

FX2N-16EX-ES/UL

16

-

100

FX2N-16EX

16

-

100

FX2N-16EX-C

16

-

100

FX2N-16EXL-C

16

-

100

FX2N-8EYR-ES/UL

8

-

75

FX2N-8EYT-ESS/UL

8

-

75

FX2N-8EYR

8

-

75

FX2N-8EYT

8

-

75

FX2N-8EYT-H

8

-

75

FX2N-16EYR-ES/UL

16

-

150

FX2N-16EYT-ESS/UL

16

-

150

FX2N-16EYR

16

-

150

FX2N-16EYS

16

-

150

FX2N-16EYT

16

-

150

FX2N-16EYT-C

16

-

150

2 Features and Part Names

FX2N-8ER-ES/UL

Types for addition of input

Types for addition of output

4 Specifications

5 Version and Peripheral Devices

*1.

Product Introduction

B2

3

Four inputs and four outputs are occupied as unused numbers.

6 System Configuration

7 Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

73

Page 80

FX3G Series Programmable Controllers

6 Examination of System Configuration

User's Manual - Hardware Edition

6.8.3

[C] Special function devices

C

Number of input/ occupied output points

5V DC

Internal 24V DC

External 24V DC

FX3U-4AD

8

110

0

90

FX2N-2AD

8

20

50

*3

0

FX2N-4AD

8

30

0

55

FX2N-8AD

8

50

0

80

FX2N-4AD-PT

8

30

0

50

FX2N-4AD-TC

8

30

0

50

FX3U-4DA

8

120

0

160

FX2N-2DA

8

30

85*3

0

FX2N-4DA

8

30

0

200

FX2N-5A

8

70

0

90

FX2N-2LC

8

70

0

55

FX3U-64CCL

8

0

0

220

FX2N-16CCL-M

8*1

0

0

150

FX2N-32CCL

8

130

0

50

No.

C1

Type

FX2N-64CL-M

Supplied from power supply for CC-Link/LT

190

The following number of points is added according to the products connected to the network. Number of remote I/O stations 32 points

*2.

The following number of points is added according to the products connected to the network. Total number of input/output points of remote I/O stations

*3.

When analog special function blocks (FX2N-2AD and FX2N-2DA) are connected to an input/output powered extension unit (FX2N -32E or FX2N-48E ), the following limitation must be taken into consideration. (When the blocks are connected to the main unit, this limitation is not applied.) The total current consumption of the analog special function blocks (FX2N-2AD and FX2N-2DA) should be less than the following current values. Total current consumption of blocks connected to FX2N-32E : 190 mA or less Total current consumption of blocks connected to FX2N-48E : 300 mA or less

[D] Extension Power Supply Unit

D

No.

Type

D1

FX3U-1PSU-5V

*1.

74

8*2

Current consumed (mA)

*1.

-

6.8.4

6.8 Number of Input/Output (Occupied) Points and Current Consumption

Number of input/ occupied output points

5V DC power supply

Internal 24V DC

-

1000

300

Current consumed (mA)*1

The ambient temperature restricts the output current. For details, refer to the derating curve in Section 6.7.