Page 81

FX3G Series Programmable Controllers

7 Assignment of Input/Output Numbers and Unit Numbers

User's Manual - Hardware Edition

7.1 Assignment of Input/Output Numbers (X/Y)

1

Assignment of Input/Output Numbers and Unit Numbers

7.1

Assignment of Input/Output Numbers (X/Y)

2

Concept of assigning

1. Input/output numbers (X/Y) are octal. Octal numbers are assigned as input/output numbers (X/Y) as shown below. - X000 to X007, X010 to X017, X020 to X027......, X070 to X077, X100 to X107... - Y000 to Y007, Y010 to Y017, Y020 to Y027......, Y070 to Y077, Y100 to Y107...

5

Note that unused numbers (which cause the difference between the number of occupied points and the number of effective points) are generated when the following products are used. - Main units (FX3G-14M , FX3G-24M , FX3G-60M ) - input/output extension blocks (FX2N-8ER-ES/UL, FX2N-8ER)

6

• In the case of FX3G-24M (X016,X017: Unused numbers)

X010 to X027

Y000 to Y005

Y010 to Y027

(Y006,Y007: Unused numbers)

Main unit FX3G-24MT/ES

Input/output powered extension unit FX2N-32ER

Y000 to Y011

Y020 to Y037

8

(Y012 to Y017: Unused numbers)

9

• In the case of FX3G-60M

Preparation and Power Supply Wiring

• In the case of FX3G-40M

X020 to X037

Installation

Input/output powered Main unit extension unit FX3G-14MT/ES FX2N-32ER

X000 to X015

(X044 to X047: Unused numbers) X030 to X047

X000 to X043

X050 to X067

Main unit FX3G-40MT/ES

Input/output powered extension unit FX2N-32ER

Main unit FX3G-60MT/ES

Input/output powered extension unit FX2N-32ER

Y000 to Y017

Y020 to Y037

Y000 to Y027

Y030 to Y047

10 Input Wiring

X000 to X027

7 Input/Output Nos., Unit Nos.

To an added input/output powered extension unit/block, input numbers and output numbers following the input numbers and output numbers given to the preceding device are assigned. The last digit of the assigned numbers must begin with 0. When the input/output powered extension unit is connected to the main unit, input/output numbers are assigned as follows.

System Configuration

3. Numbers for added input/output unit/block

X000 to X007

Version and Peripheral Devices

2. Unused numbers

• In the case of FX3G-14M

4 Specifications

When the power is turned on, input/output numbers (X/Y) are assigned in accordance with the following rules. In the FX2N-64CL-M, input/output numbers are assigned to connected remote input/output stations. For details on assignment, refer to the FX2N-64CL-M manual.

3 Product Introduction

• FX2N-64CL-M

Features and Part Names

If input/output powered extension units/blocks have been connected when the power is turned on, the main unit automatically assigns the input/output numbers (X/Y) (octal) to the units/blocks. Therefore, it is unnecessary to specify the input/output numbers with parameters. Accordingly, it is not necessary to specify input/output numbers using parameters. It is necessary to assign input and output numbers in the following special function blocks.

7.1.1

Introduction

7.

75

Page 82

FX3G Series Programmable Controllers

7 Assignment of Input/Output Numbers and Unit Numbers

User's Manual - Hardware Edition

7.1.2

7.1 Assignment of Input/Output Numbers (X/Y)

Example of assigning An example of assignment of input/output numbers (X/Y) is shown below.

1. Example of configuration Special adapter FX3U-4AD-ADP

Connector Input/output Special function Main unit conversion extension block block FX3G-24MT/ES adapter FX2N-8ER FX2N-16CCL-M FX3G-CNV-ADP Input/output powered extension unit FX2N-32ET

Input extension block FX2N-8EX

2. Assignment of input/output numbers Input/output numbers are assigned to the above example configuration as shown below. (X016, X017: (X024 to X027: Unused numbers) Unused numbers) -

-

X000 to X015

X020 to X023

-

Connector Input/output Special function Special adapter conversion Main unit extension block block FX3U-4AD-ADP adapter FX3G-24MT/ES FX2N-8ER FX2N-16CCL-M FX3G-CNV-ADP Y000 to Y011

Y020 to Y023

-

(Y012 to Y017: (Y024 to Y027: Unused numbers) Unused numbers)

X030 to X047

X050 to X057

Input/output powered extension unit FX2N-32ET

Input extension block FX2N-8EX

Y030 to Y047

7.1.3

Application of I/O number label The input/output powered extension units/blocks come with an I/O number label. Apply the I/O number label to spaces on the enclosure (see the following figure) so that the input/output numbers can be identified.

For X050

For Y040

76

Page 83

FX3G Series Programmable Controllers

7 Assignment of Input/Output Numbers and Unit Numbers

User's Manual - Hardware Edition

7.2 Unit Numbers of Special Function Blocks

Unit Numbers of Special Function Blocks

7.2.1

Concept of assigning

Introduction

7.2

1

1. Special function blocks connected to main unit

2 Features and Part Names

When power is turned on, the main unit (CPU) automatically assigns the numbers 0 to 7 to special function blocks starting from the one closest to the main unit. Unit numbers are not given to input/output powered extension units/blocks. The numbers 0 to 7 are assigned to the special function blocks starting from the one closest to the main unit.

3

2. Products to which unit numbers are not assigned

Product Introduction

• Input/output powered extension units: FX2N-32ER, FX2N-48ET, etc. FX2N-16EX, FX2N-16EYR, etc.

• Connector conversion adapter:

FX3G-CNV-ADP, FX2N-CNV-BC

• Expansion boards:

FX3G-232-BD, etc.

• Special adapters:

FX3U-232ADP(-MB), FX3U-4AD-ADP, etc.

• Extension power supply unit:

FX3U-1PSU-5V

4 Specifications

7.2.2

• Input/output extension blocks:

Example of assigning

1. Example of configuration Special adapter FX3U-4AD-ADP

Connector Main unit conversion FX3G-24MT/ES adapter FX3G-CNV-ADP

Special function block FX2N-16CCL-M

6 System Configuration

Input/output powered extension unit FX2N-32ET

Input extension block FX2N-8EX

Special function block FX3U-64CCL

7 Input/Output Nos., Unit Nos.

2. Assignment of Unit No. Unit numbers are assigned to the special function blocks in the above configuration as shown below. Unit No. No.0 Connector Main unit conversion FX3G-24MT/ES adapter FX3G-CNV-ADP

Input extension block FX2N-8EX

8

Special function block FX2N-16CCL-M

Installation

Special adapter FX3U-4AD-ADP

5 Version and Peripheral Devices

Unit numbers are assigned to the special function blocks in the following configuration. → For assignment of input/output numbers, refer to Section 7.1.

9

Input/output powered extension unit FX2N-32ET

Preparation and Power Supply Wiring

Unit No. No.1 Special function block FX3U-64CCL

10 Input Wiring

77

Page 84

FX3G Series Programmable Controllers

7 Assignment of Input/Output Numbers and Unit Numbers

User's Manual - Hardware Edition

7.2.3

7.2 Unit Numbers of Special Function Blocks

Application of unit number labels The special function units/blocks come with unit number labels. Apply the unit number labels to spaces on the enclosure (see the following figure) so that the unit numbers can be identified.

Y818D33101

No.0 No.1 No.2 No.3 No.4 No.5 No.6 No.7

78

No.0

Page 85

FX3G Series Programmable Controllers

7 Assignment of Input/Output Numbers and Unit Numbers

User's Manual - Hardware Edition

7.3 Assignment of Communication Channels

Assignment of Communication Channels

7.3.1

Assignment of communication channels

Introduction

7.3

1

• Main unit (40/60 point type) : Max 2ch • Main unit (14/24 point type) : Max 1ch

1. In the case of main unit (40/60 point type)

Only between the communication expansion board (FX3G-8AV-BD included) and the special communication adapter (which requires the connector conversion adapter) can be used.

4 Specifications

Main unit (40/60 point type)

ch2 ch1

BD1 connector ch1

BD2 connector ch2

5 Version and Peripheral Devices ch1 Communication special adapter

Communication expansion board (FX3G-8AV-BD included)

Or

6

Communication expansion board(BD1)

System Configuration

Connector conversion adapter(BD1)

Communication special adapter Only either one between the communication expansion board and the special communication adapter (which requires the connector conversion adapter) can be used.

7

"Ch1" is assigned to the communication expansion board (FX3G -8AV-BD included) connected to the BD connector or the special communication adapter connected to the connector conversion adapter. Main unit (14/24 point type)

Input/Output Nos., Unit Nos.

2. In the case of main unit (14/24 point type)

8 Installation ch1

3 Product Introduction

"Ch1" is assigned to the communication expansion board connected to the BD1 connector or the first special communication adapter connected to the connector conversion adapter. "Ch2" is assigned to the communication expansion board (FX3G-8AV-BD included) connected to the BD2 connector or the second special communication adapter connected to the connector conversion adapter.

2 Features and Part Names

When the communication expansion board or special communication adapter is used, the main unit (CPU) automatically assigns communication channels at the time of power ON. The number of available communication channels varies depending on the main unit type.

BD connector ch1

9 ch1

Or

Preparation and Power Supply Wiring

Connector conversion adapter(BD)

Communication expansion board(BD)

10

Communication special adapter

Input Wiring

Only either one between the communication expansion board (FX3G-8AV-BD included) and the special communication adapter (which requires the connector conversion adapter) can be used.

79

Page 86

FX3G Series Programmable Controllers

7 Assignment of Input/Output Numbers and Unit Numbers

User's Manual - Hardware Edition

7.4 "Station No." Label of Expansion Board (FX3G-485-BD)

7.4

"Station No." Label of Expansion Board (FX3G-485-BD) The "station No." label is packed together with the FX3G-485-BD. Place it in a position where it can be seen easily for simple reference (as shown in the figure below).

when the memory cassette is not used together

7.5 when the memory cassette is used together

Trimmer Layout Label of Expansion Board (FX3G-8AV-BD) The trimmer layout label is packed together with the FX3G-8AV-BD. Adhere it in a position where it can be seen easily for quick reference (as shown in the figure below).

80