Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 14 of 49

FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 8. Installation In Enclosure, pages 87 to 94

Pages 87 to 94 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 87

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

1 Introduction

8.

Installation In Enclosure

2 Features and Part Names

DESIGN PRECAUTIONS •

•

INSTALLATION PRECAUTIONS •

6 System Configuration

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.

5 Version and Peripheral Devices

•

4 Specifications

DESIGN PRECAUTIONS

3 Product Introduction

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that the output current of the 24V DC service power supply varies depending on the model and the absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the PLC are disabled, and all outputs are turned off. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

7

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock.

Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

81

Page 88

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

INSTALLATION PRECAUTIONS •

• •

• •

• • •

• •

Use the product within the generic environment specifications described in Section 4.1 of this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions. Install the product securely using a DIN rail or mounting screws. Terminal block

DIN rail only

Main unit, FX2N Series I/O extension unit/block, and FX2N/FX3U Series special extension block/special adapter

DIN rail or direct mounting

Install the product on a flat surface. If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities. Make sure to affix the expansion board with tapping screws. Tightening torque: 0.3 to 0.6 N•m Loose connections may cause malfunctions. When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Be sure to remove the dust proof sheet from the PLC’s ventilation port when installation work is completed. Failure to do so may cause fire, equipment failures or malfunctions. Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely to their designated connectors. Loose connections may cause malfunctions. Connect the memory cassette, and expansion board board securely to their designated connectors. Loose connections may cause malfunctions. Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause device failures or malfunctions. - Peripheral devices, expansion boards, and special adapters - Extension units/blocks and the FX Series terminal block - Battery and memory cassette

WIRING PRECAUTIONS • • •

82

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

Page 89

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

1 Introduction

WIRING PRECAUTIONS • •

• •

•

3

4 Specifications

•

2

Product Introduction

• wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Features and Part Names

•

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a

5 Version and Peripheral Devices

6 System Configuration

7 Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

83

Page 90

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

8.1

8.1 Installation location

Installation location Use the PLC under the environmental conditions complying with the generic specifications (Chapter 4). Notes • • •

8.1.1

84

Keep a space of 50 mm (1.97") away between the unit main body and other devices and structure. Install the unit as far away as possible from high-voltage lines, high-voltage devices and power equipment. To prevent temperature rise, do not install the PLC on a floor or a ceiling or in the vertical direction. Install it horizontally on a wall as shown below. Arrange the extension cable in such a way that the left connectors of the input/output powered extension units/blocks or special function units/blocks are connected on the side closer to the main unit.

Installation location in enclosure

Page 91

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

1

Spaces in enclosure

Introduction

8.1.2

8.2 Layout in Enclosure

Extension devices can be connected on the left and right sides of the main unit of the PLC. If you intend to add extension devices, keep necessary spaces on the left and right sides.

1. Configuration without extension cable

2 Features and Part Names

FX3G Series main unit

A

A

A

3 Product Introduction

FX2N-16EX

A

FX2N-16EYT

A

50mm (1.97")

2. Configuration in 2 stages with extension cable

4 Specifications

FX3G Series main unit

A

FX2N-16EYT

A

5

FX2N16CCL-M

FX2N-16EX

Input/output powered extension unit

Extension cable ·FX0N-65EC ·FX0N-30EC

A

Other equipment

A

Other equipment

50mm (1.97")

7 Input/Output Nos., Unit Nos.

8.2

6

A

System Configuration

A

FX2N-CNVBC

A

Version and Peripheral Devices

FX3U-4ADADP FX3G-CNVADP

Other equipment

A

Layout in Enclosure The PLC components can be laid out in one stage or in two stages, upper and lower. The connecting procedures in each case are explained below.

Installation

8.2.1

1-stage layout Special adapter

Connector conversion adapter

For the dimensions of each product, refer to the external dimensions.

9 Preparation and Power Supply Wiring

Extension block

Input/output powered extension units

Extension block

Extension block

FX3G Series main unit

Input/output powered extension units/blocks Special function blocks Extension block

A

8

A

A

50mm (1.97")

10 Input Wiring

85

Page 92

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

8.2.2

8.2 Layout in Enclosure

2-stage layout In the case of a 2-stage layout, connect the first stage and the second stage with the extension cable. When an extension block is connected at the top of the second stage, FX2N-CNV-BC (connector conversion adapter) is necessary.

1. When an input/output powered extension unit is connected at the top of the 2nd stage

A

For the dimensions of each product, refer to the external dimensions.

Extension block

Extension block

Input/output powered extension units*1

Extension block

Extension cable ·FX0N-65EC (650mm(25.59")) ·FX0N-30EC (300mm(11.81"))

Extension block

FX3G Series main unit

Extension block

A

Input/output powered extension units/blocks Special function blocks

Connector conversion adapter

Special adapter

A

For the dimensions of each product, refer to the external dimensions.

A

50mm (1.97")

*1. Include FX3U-1PSU-5V

2. When an input/output extension block or a special function block is connected at the top of the 2nd stage Special adapter

Extension block

FX3G Series main unit

Extension block

A

Input/output powered extension units/blocks Special function blocks

Connector conversion adapter

For the dimensions of each product, refer to the external dimensions. A

86

Extension block

*1.Except FX2N-8AD

Input/output powered extension units

Extension block

Extension cable ·FX0N-65EC (650mm(25.59")) ·FX0N-30EC (300mm(11.81"))

Extension block*1

FX2N-CNV-BC

For the dimensions of each product, refer to the external dimensions.

A

A

50mm (1.97")

Page 93

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

1

Examination for Installing Method in Enclosure Examine the installation location of PLC in consideration of the environmental conditions (generic specifications).

8.3.1

Introduction

8.3

8.3 Examination for Installing Method in Enclosure

2

Installing methods

Features and Part Names

The PLC can be installed by the following two methods.

1. Installing on DIN rail • The PLC can be installed on a DIN46277 rail (35 mm (1.38") wide).

3

• The PLC can be easily moved and removed.

Product Introduction

• The PLC is installed higher by the height of the DIN rail. → For details on the procedures on mounting and removing the DIN rail, refer to Section 8.4.

2. Direct installing (with screws) • The PLC can be installed directly in the enclosure with M4 screws. → For the mounting hole pitch, refer to Section 8.5.

Cautions in examining installing method → Refer to Section 8.2.

1. Cautions when FX2N-8AD is used

8.3.3

Examples of installation

6 System Configuration

1. Example of installation on DIN rail 1 to 2mm (0.04" to 0.08")

FX3G Series main unit

FX2N16EX

FX2N16EYT

7 Input/Output Nos., Unit Nos.

DIN rail 1 to 2mm (0.04" to 0.08") FX2N-CNV-BC*1 FX2N64CL-M

Extension cable ·FX0N-65EC ·FX0N-30EC

8

DIN rail

Installation

FX2N16EX

(+ indicates an M4 screw.)

*1.

5 Version and Peripheral Devices

When the system is laid out in two stages, do not mount FX2N-8AD at the top of the second stage, or FX2NCNV-BC cannot be installed directly.

Specifications

8.3.2

4

FX2N-CNV-BC can be installed directly in the enclosure but cannot be installed on the DIN rail.

9 Preparation and Power Supply Wiring

10 Input Wiring

87

Page 94

FX3G Series Programmable Controllers

8 Installation In Enclosure

User's Manual - Hardware Edition

8.3 Examination for Installing Method in Enclosure

2. Example of direct installation 1 to 2mm (0.04" to 0.08")

FX3G Series main unit

FX2N16EX

FX2N16EYT

1 to 2mm (0.04" to 0.08")

4

FX2N-CNV-BC FX2N16EX

Extension cable ·FX0N-65EC ·FX0N-30EC

FX2N64CL-M (+ indicates an M4 screw.)

3. Example of combination of installation on DIN rail and direct installation As shown in the following example, when the main unit is installed on the DIN rail, the extension devices connected with the extension cable can be installed directly in the enclosure. 1 to 2mm (0.04" to 0.08")

FX3G Series main unit

FX2N16EX

FX2N16EYT

DIN rail 1 to 2mm (0.04" to 0.08") *1

FX2N-CNV-BC

FX2N16EX

Extension cable ·FX0N-65EC ·FX0N-30EC

FX2N64CL-M (+ indicates an M4 screw.)

*1.

88

FX2N-CNV-BC can be installed directly in the enclosure but cannot be installed on the DIN rail.