The text of a manual · part 15 of 49
FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 8. Installation In Enclosure, pages 95 to 102
Pages 95 to 102 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]
The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Mitsubishi FX-16EYR
Page 95
FX3G Series Programmable Controllers User's Manual - Hardware Edition
8.4 Procedures for Installing on and Detaching from DIN Rail
1
Procedures for Installing on and Detaching from DIN Rail
Introduction
8.4
8 Installation In Enclosure
The main unit can be installed on a DIN46277 rail (35 mm (1.38") wide).
8.4.1
Preparation for installation
2 Features and Part Names
1. Connecting extension devices Some extension devices must be mounted on the main unit before the unit is installed in the enclosure. • Mount the special adapter or connector conversion adapter (FX3G-CNV-ADP) on the main unit before installing the main unit to the enclosure.
• The expansion boards/memory cassette and the display module can be fitted to the main unit after it is installed.
2. Affixing The Dust Proof Sheet The dust proof sheet should be affixed to the ventilation port before beginning the installation and wiring work. → For the affixing procedure, refer to the instructions on the dust proof sheet.
5 Version and Peripheral Devices
Be sure to remove the dust proof sheet when the installation and wiring work is completed.
4 Specifications
• The battery can be replaced while the main unit is installed in the enclosure. However, when the expansion board, display module, memory cassette or connector conversion adapter is attached, remove the respective device. → For the replacement method, refer to Chapter 22.
3 Product Introduction
• Mount the input/output powered extension units/blocks and the special function blocks in the enclosure after installing the main unit in the enclosure.
6 System Configuration
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
89
Page 96
FX3G Series Programmable Controllers User's Manual - Hardware Edition
8.4.2
8 Installation In Enclosure 8.4 Procedures for Installing on and Detaching from DIN Rail
Installation of main unit The main unit must be installed before installing a special adapter or connector conversion adapter on the enclosure. → For the connection procedure, refer to Subsection 8.6.3 and Subsection 8.6.4.
1 Push out all DIN rail mounting hooks (A in the right figure).
C
1
1
A
2 Fit the upper edge of the DIN rail mounting groove (C in the right figure) onto the DIN rail. C
3 Lock the DIN rail mounting hooks (D in the following figure) while pressing the PLC against the DIN rail.
D
D 3
90
3
Page 97
FX3G Series Programmable Controllers User's Manual - Hardware Edition
8.4 Procedures for Installing on and Detaching from DIN Rail
Installation of input/output powered extension unit/block and special function block
1 Push out the DIN rail mounting hook (A in the right fig-
Rear panel
Rear panel ure) of the input/output extension block.
2 Features and Part Names
1
• For input/output powered extension units, 8-point type input/output extension blocks and special extension units/blocks, this operation is unnecessary.
3
A
Product Introduction
2 Fit the upper edge of the DIN rail mounting groove (B in the right figure) onto the DIN rail.
3 Push the product against the DIN rail.
B
4 Specifications
• Keep a gap of 1 to 2 mm (0.04" to 0.08") between the products.
1 Introduction
8.4.3
8 Installation In Enclosure
3
4 Connect the extension cable.
→ For the procedures on connecting the extension cable, refer to Subsection 8.6.5.
5 Version and Peripheral Devices
6 System Configuration
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
91
Page 98
FX3G Series Programmable Controllers User's Manual - Hardware Edition
8.4.4
8 Installation In Enclosure 8.4 Procedures for Installing on and Detaching from DIN Rail
Removal of main unit
1 Open the terminal block cover, and remove the
B lower terminal block cover (A in the right figure).
2 Gradually loosen the left and right terminal block mounting screws (B in the right figure), and remove the terminal blocks.
→ For anchoring of the terminal block, refer to Subsection 9.1.2. B
A
3 Disconnect the extension cables and the connecting cables (including expansion board and special adapters).
4 Insert the tip of a flathead screwdriver into the hole of the DIN rail mounting hook (C in the right figure). • This step also applies for the DIN rail mounting hooks of the special adapters.
5 Move the flathead screwdriver as shown in the
6
D right figure to draw out the DIN rail mounting hooks of all devices.
6 Remove the product from the DIN rail (D in the
5
C
4 right figure).
7 Push in the DIN rail mounting hooks (E in the right figure).
• For input/output powered extension units, 8-point type input/output extension blocks and special function blocks, this operation is unnecessary. 7
92
E
7
Page 99
FX3G Series Programmable Controllers
8 Installation In Enclosure
User's Manual - Hardware Edition
1
Procedures for Installing Directly (with M4 Screws)
Introduction
8.5
8.5 Procedures for Installing Directly (with M4 Screws)
The product can be installed directly in the enclosure (with screws). Point
2
Hole pitches for direct mounting The product mounting hole pitches are shown below. For the pitch that varies depending on the product, refer to the table.
3 Unit: mm (inches) Model name
4(0.16")
82 (3.23")
FX3G-24MT/ES
82 (3.23")
FX3G-40MT/ES
122 (4.81")
FX3G-60MT/ES
167 (6.58")
4
4(0.16")
A
Mounting hole pitch(W)
FX3G-14MT/ES
Specifications
A
90 (3.55")
W
82 (3.23")
4(0.16")
5 Unit: mm (inches) Model name
105 (4.14")
B
FX3U-4AD-ADP FX3U-4DA-ADP FX3U-4AD-PT-ADP FX3U-4AD-PTW-ADP FX3U-4AD-PNK-ADP FX3U-4AD-TC-ADP FX3U-232ADP(-MB) FX3U-485ADP(-MB)
Mounting hole pitch(W)
6 Refer to the figure shown left.
7
Unit: mm (inches) Model name
5 (0.2")
C
80 (3.15") 90 (3.55")
C
5 (0.2")
W
FX2N-48ER-ES/UL FX2N-48ET-ESS/UL FX2N-48ER FX2N-48ET
172 (6.78")
FX2N-48ER-UA1/UL
210 (8.27")
9
10 Input Wiring
D
5 (0.2")
140 (5.52")
8
Preparation and Power Supply Wiring
D
Mounting hole pitch(W)
FX2N-32ER-ES/UL FX2N-32ET-ESS/UL FX2N-32ER FX2N-32ET FX2N-32ES
Installation
W
Input/Output Nos., Unit Nos.
3. Input/output powered extension unit(C or D) 5 (0.2")
System Configuration
98 (3.86")
2.5 15.1 (0.1") (0.6")
Version and Peripheral Devices
2. Special adapter (B)
B
Product Introduction
1. Main unit (A)
80 (3.15") 90 (3.55")
8.5.1
Features and Part Names
Position the holes so that there is a gap of 1 to 2 mm (0.04" to 0.08") between the products.
93
Page 100
FX3G Series Programmable Controllers
8 Installation In Enclosure
User's Manual - Hardware Edition
8.5 Procedures for Installing Directly (with M4 Screws)
4. Input/output extension block (E or F) Unit: mm (inches) 4 (0.16") W 80 (3.15") 90 (3.55")
E
Model name
E
39 (1.54")
F
FX2N-16EX-ES/UL FX2N-16EX FX2N-16EX-C FX2N-16EXL-C FX2N-16EYR-ES/UL FX2N-16EYR FX2N-16EYT-ESS/UL FX2N-16EYT FX2N-16EYT-C FX2N-16EYS
Refer to the figure shown left.
80 (3.15") 90 (3.55")
20 20 (0.87") (0.87")
F
Mounting hole pitch(W)
FX2N-8ER-ES/UL FX2N-8ER FX2N-8EX-ES/UL FX2N-8EX FX2N-8EX-UA1/UL FX2N-8EYR-ES/UL FX2N-8EYT-ESS/UL FX2N-8EYR FX2N-8EYT FX2N-8EYT-H
5. Special function unit/block (G, H or I) Unit: mm (inches)
4 (0.16")
H I
Mounting hole pitch(W)
FX2N-2AD FX2N-2DA FX2N-64CL-M FX2N-32CCL
39 (1.54")
FX3U-4AD FX3U-4DA FX2N-4AD FX2N-4DA FX2N-4AD-PT FX2N-4AD-TC FX2N-5A FX2N-2LC FX3U-64CCL FX3U-1PSU-5V
51 (2.01")
FX2N-16CCL-M
Refer to the figure shown left.
FX2N-20PSU
52 (2.05")
FX2N-8AD
67 (2.64")
Example of mounting hole pitches 122 (4.81")
A
26 26 46 (1.03")(1.03") (1.82")
F
G
2* 2* (0.08") (0.08")
FX3U-232ADP FX3G-40MT/ES (-MB)
172 (6.78")
C
2 * (0.08")
FX2N-16EX FX2N-64CL-M FX2N-48ER
* The gap between products is 2 mm (0.08").
Unit:mm (inches)
80 (3.15") 98 (3.86")
B
FX3G-CNV-ADP
15.1 18.6 (0.6")(0.74")
94
G
4 (0.16")
I
8.5.2
H
98 (3.86") 105 (4.14")
W
80 (3.15") 90 (3.55")
G
Model name
4 (0.16")
4 (0.16") 75(2.96")
W
80 (3.15") 90 (3.55")
4 (0.16")
Page 101
FX3G Series Programmable Controllers User's Manual - Hardware Edition
8.5 Procedures for Installing Directly (with M4 Screws)
1
Installation of main unit Mount the special adapters and connector conversion adapter (FX3G-CNV-ADP) on the main unit before installing the unit in the enclosure. → For the connection procedure, refer to Subsection 8.6.3, Subsection 8.6.4.
according to the external dimensions diagram.
2 Fit the main unit (A in the right figure) based on
B
3 Product Introduction the holes, and secure it with M4 screws (B in the right figure). The positions and number of screws depend on the product. Refer to the external dimensions diagram. → For the external dimensions, refer to Section 4.6.
A
4
B
Installation of input/output powered extension unit/block and special function block
1 Make mounting holes in the mounting surface
Rear panel
5
Rear panel
Version and Peripheral Devices according to the external dimensions diagram.
2 Push in the DIN rail mounting hook (A in the right figure) of the input/output extension block.
6
For input/output powered extension units, 8-point type input/ output extension blocks and special function blocks, this operation is unnecessary.
System Configuration
If the DIN rail mounting hook is not pushed in, the screw hole is covered, and the block cannot be mounted. A 2
7 Input/Output Nos., Unit Nos.
3 Fit the input/output extension block (B in the right figure) based on the holes, and secure it with M4 screws (C in the right figure). The positions and number of screws depend on the product. Refer to the external dimensions diagram.
8 Installation
→ For the external dimensions of the input/output powered extension unit, refer to Chapter 15. → For the external dimensions of the input/output extension block, refer to Chapter 16. → For the external dimensions of the special function blocks, refer to Chapter 18.
Specifications
8.5.4
2 Features and Part Names
1 Make mounting holes in the mounting surface
Introduction
8.5.3
8 Installation In Enclosure
C
9
B
Preparation and Power Supply Wiring
C
10 Input Wiring
95
Page 102
FX3G Series Programmable Controllers
8 Installation In Enclosure
User's Manual - Hardware Edition
8.6
8.6 Connecting Methods for Main Unit and Extension Devices
Connecting Methods for Main Unit and Extension Devices This section explains the connecting methods for extension devices.
8.6.1
Connection of extension devices The connecting method varies depending on the combination of the products, i.e. the main unit, expansion board, special adapters, input/output extension blocks and special function blocks. The connecting methods are explained with the following configuration examples. Example of configuration Special adapter
Connector conversion Expansion board adapter
FX2N/FX3U Series extension blocks
FX3G Series main unit
Connecting method C
Connecting method B
Extension cable ·FX0N-65EC ·FX0N-30EC
Connecting method A
Connecting method D
FX2N/FX3U FX2N/FX3U FX2N Series input/output Series Series powered extension unit extension blocks extension blocks
FX2N CNV-BC
Connecting method F
96
Connecting method E
FX2N Series Input/output powered extension unit
Connecting method G
Connecting method H