Page 103

FX3G Series Programmable Controllers User's Manual - Hardware Edition

8.6 Connecting Methods for Main Unit and Extension Devices

1

Connecting method A - connection of expansion board

Introduction

8.6.2

8 Installation In Enclosure

This subsection explains how to connect the expansion board to the main unit. The FX3G-40MT/ES is used as the main unit in this example.

1 Remove the top cover (A in the right

Features and Part Names figure) from the front face of the main unit.

2

A

Top cover(S) 1

3 Product Introduction

4 Specifications

2 Attach the provided side cover (B in the right

B figure) as shown in the right figure.

5

Caution

Version and Peripheral Devices

- Attachment of the side cover is not necessary when connecting the expansion board only under the top cover (S) of a 40/60-point type main unit. - FX3G-8AV-BD cannot attach in the top cover(S) side of a main unit.

6 connector (C in the right figure).

C

System Configuration

3 Connect the expansion board to the option 3

7 Input/Output Nos., Unit Nos.

8

4 Fix the expansion board (E in the right figure)

Installation with provided M3 tapping screws (D in the right figure) to the main unit.

D E

• Tightening torque : 0.3 to 0.6 N•m

9 Preparation and Power Supply Wiring

10 Input Wiring

97

Page 104

FX3G Series Programmable Controllers User's Manual - Hardware Edition

8.6.3

8 Installation In Enclosure 8.6 Connecting Methods for Main Unit and Extension Devices

Connecting method A - connection of connector conversion adapter 1. This paragraph explains how to connect the connector conversion adapter to the main unit. The FX3G-24MT/ES is used as the main unit in this example.

1 Remove the top cover (A in the right figure)

A B and peripheral device connector cover (B in the right figure) from the front face of the main unit.

2 Attach the provided side cover (C in the right

C figure) as shown in the right figure.

3 Connect the connector conversion adapter to the

E option connector (D in the right figure) as shown in the right figure, and fix it with provided M3 tapping screws (E in the right figure).

D

• Tightening torque : 0.3 to 0.6 N•m

4 Fix the connector conversion adapter (F in the right figure) with provided M3 tapping screws (E in the right figure) to the main unit.

F

• Tightening torque : 0.3 to 0.6 N•m

E

98

Page 105

FX3G Series Programmable Controllers User's Manual - Hardware Edition

8 Installation In Enclosure 8.6 Connecting Methods for Main Unit and Extension Devices

The FX3G-40MT/ES is used as the main unit in this example.

1 Remove the top cover (A in the right figure) and

1 Introduction

2. This paragraph explains how to connect the connector conversion adapter to the main unit.

A B peripheral device connector cover (B in the right figure) from the front face of the main unit.

2 Features and Part Names

3 Product Introduction

2 Connect the connector conversion adapter to

D the option connector (C in the right figure) as shown in the right figure, and fix it with provided M3 tapping screws (D in the right figure).

4 Specifications

C

• Tightening torque : 0.3 to 0.6 N•m

5 Version and Peripheral Devices

3 Fix the connector conversion adapter (E in the

6 System Configuration right figure) with provided M3 tapping screws (D in the right figure) to the main unit.

E

• Tightening torque : 0.3 to 0.6 N•m

7

D

Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

99

Page 106

FX3G Series Programmable Controllers User's Manual - Hardware Edition

8.6.4

8 Installation In Enclosure 8.6 Connecting Methods for Main Unit and Extension Devices

Connecting method C - connection of special adapter When connecting the special adapter, it is necessary to attach the connector conversion adapter before the special adapter using the method described in the preceding subsection.

1 Slide the special adapter connecting hooks (A in the right figure) of the main unit.

• When adding a special adapter to the special adapter that has been connected to the connector conversion adapter, read "connector conversion adapter" as "special adapter." (This applies to the following steps.)

1 A 1 A

2 Connect the special adapter (B in the right figure) to the connector conversion adapter as shown in the right figure.

3 Slide the special adapter connecting

A B hooks (A in the right figure) of the connector conversion adapter to secure the special adapter (B in the right figure).

3 2 3 2 A 2

8.6.5

Connecting method D - connection of powered extension units/blocks to main unit The procedures for connecting an powered extension unit/block to the main unit are explained below.

1 Remove the extension device connector

A cover (A in the right figure) on the right side of the main unit.

3 1

B

2 Connect the extension cable (B in the right figure) from the extension block to be connected (right side) to the extension device connector of the main unit.

• When connecting FX2N Series input/output powered extension unit or FX3U-1PSU-5V, connect the unit to be added (right side) and the existing unit (main unit) with the supplied extension cable.

3 Fit the extension device connector cover (A in the right figure).

100

Page 107

FX3G Series Programmable Controllers User's Manual - Hardware Edition

8.6 Connecting Methods for Main Unit and Extension Devices

1

Connecting method E - connection of powered extension units/blocks This subsection explains the procedures for connecting FX2N Series input/output powered extension units/ blocks or FX2N/FX3U Series special function blocks.

1 Remove the top cover (B in the right figure)

Introduction

8.6.6

8 Installation In Enclosure

2

B 1

Features and Part Names of the existing unit/block (left side) (A in the right figure).

3 C

• When connecting FX3U-1PSU-5V, remove the top cover of FX3U-1PSU-5V.

A

3 Product Introduction

2 Connect the extension cable (C in the above figure) of the block to be con• When FX2N Series input/output powered extension units or FX3U-1PSU-5V units are connected, connect the unit to be added (right side) and the existing unit (left side) with the supplied extension cable.

8.6.7

Connecting method F - connection of extension cable and FX2N-CNV-BC

1 Separate the case of FX2N-CNV-BC into two pairs as shown right.

7 Input/Output Nos., Unit Nos.

B

A A

A

2 Connect the extension cable on the

1

8

A

Installation upstream side (C in the right figure).

1 4

3 Connect the extension cable on the down-

4 E

9 stream side (D in the right figure).

C FX0N-30EC FX0N-65EC

2 3 D

10 Input Wiring and the lower cover (F in the right figure), and press down the upper cover until it is hooked.

Preparation and Power Supply Wiring

4 Fit the upper cover (E in the right figure)

6 System Configuration

This subsection explains the procedures for connecting an extension cable and FX 2N -CNV-BC to the extension cable of the powered extension unit/block.

To separate the case, use a precision flathead screwdriver. Slightly insert the tip of the screwdriver into the part A shown in the right figure, and the hook (B in the right figure) will come off (4 places).

5 Version and Peripheral Devices

3 Fit the top cover (B in the above figure)

Specifications nected (right side) to the existing unit/block (A in the above figure).

4

F

101

Page 108

FX3G Series Programmable Controllers User's Manual - Hardware Edition

8.6.8

8 Installation In Enclosure 8.6 Connecting Methods for Main Unit and Extension Devices

Connecting method G - connection of input/output powered extension unit This subsection explains the procedures for connecting an input/output powered extension unit.

1 Remove the top cover (A in the right figure)

A on the left side of the input/output powered extension unit.

2 Connect the connector of the provided

1 B 4 extension cable (B in the right figure) to the extension connector of the unit/block on the upstream side (left side).

3 Connect the connector of the extension cable (supplied) (B in the right figure) to the extension connector of the input/output powered extension unit to be added.

4 Fit the top cover (A in the right figure). 8.6.9

Connecting method H - connection of extension block to input/output powered extension unit This subsection explains the procedures for connecting an extension block to an input/output powered extension unit.

1 Remove the extension connector cover (A in

A the right figure) on the right side of the input/ output powered extension unit.

B

2

2 Connect the extension cable (B in the right figure) from the extension block to be added (right side) to the extension connector of the input/output powered extension unit. • When connecting FX3U-1PSU-5V, read "input/output powered extension unit" as the unit.

• When connecting FX2N Series input/output powered extension unit FX3U-1PSU-5V, connect the unit to be added (right side) and the existing unit (main unit) with the supplied extension cable or the optional extension cable.

3 Fit the extension connector cover (A in the right figure). 102