FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 9. Preparation for Wiring and Power Supply Wiring Procedures

Pages 109 to 121 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 109

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

1 Introduction

9.

Preparation for Wiring and Power Supply Wiring Procedures

2 Features and Part Names

DESIGN PRECAUTIONS •

•

7 Input/Output Nos., Unit Nos.

•

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

6 System Configuration

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.

WIRING PRECAUTIONS •

5 Version and Peripheral Devices

•

4 Specifications

DESIGN PRECAUTIONS •

3 Product Introduction

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

103

Page 110

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

WIRING PRECAUTIONS • •

• • • •

•

•

104

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Page 111

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

Preparation for Wiring

9.1.1

Wiring procedures

1 Introduction

9.1

9.1 Preparation for Wiring

2

Before starting wiring work, make sure that the main power is off.

Features and Part Names

1 Prepare the parts for wiring. Prepare the solderless terminals and cables necessary for wiring. → For details, refer to Section 9.2.

Connect the power supply to the terminals [L] and [N]. Provide the power supply circuit with the protection circuit shown in this subsection. → For details, refer to Section 9.4.

] at a grounding resistance of 100 or less

(Class D).

Connect a class D ground wire to the terminal. → For details, refer to Section 9.3 and Section 9.4.

For a type (24V DC input type) common to sink/source input, select sink or source input by the following connection. • For sink input, connect the [24V] and [S/S] terminals.

6

• For source input, connect the [0V] and [S/S] terminals. → For details, refer to Chapter 10.

5 Wire the output [Y] terminals.

System Configuration

Connect sensors and switches to the terminals.

7 → For details, refer to Chapter 12.

Removal and installation of quick-release terminal block Removal

8 Installation

Unscrew the terminal block mounting screws [both right and left screws] evenly, and remove the terminal block. Installation Place the terminal block in the specified position, and tighten the terminal block mounting screws evenly [both right and left screws]. Tightening torque 0.4 to 0.5 N•m *Pay attention so that the center of the terminal block is not lifted.

Input/Output Nos., Unit Nos.

Connect loads to the terminals.

9.1.2

5 Version and Peripheral Devices

4 Wire the input [X] terminals.

4 Specifications

3 Wire the ground terminal [

3 Product Introduction

2 Wire the power supply terminals.

9 Preparation and Power Supply Wiring

10 Input Wiring

105

Page 112

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.2

9.2 Cable Connecting Procedures

Cable Connecting Procedures For cable connection, a terminal block or a connector is used.The cable connecting procedures are explained below.

9.2.1

Input/output terminal block (power supply and input/output wiring) For the main unit, FX2N Series input/output powered extension units/blocks and FX2N/FX3U Series special function blocks, an M3 or M3.5 screw terminal block is used.

1. Applicable products Product type

Model name

Main unit

All models of FX3G Series main units

Input/output powered extension unit

All models of FX2N Series input/output powered extension units

Input/output extension block

All models of FX2N Series input/output extension blocks (except FX2N-16EX-C, FX2N-16EXL-C and FX2N-16EYT-C)

Extension power supply unit

FX3U-1PSU-5V

Special function block

Refer to the manual for each special function block

FX Series terminal block

All models

Power supply unit

FX2N-20PSU

2. Terminal block screw size The size of the terminal screws for each product is shown below. For the solderless terminals, refer to the following page. Product Main unit FX3U Series special function block FX2N Series input/output powered extension units FX2N Series input/output extension blocks

Terminal screw

M3

FX2N Series special function block*1 FX Series terminal block

*1.

106

M3.5

M3.5 screws may be used for terminals. For details, refer to the manual for each special extension device.

Tightening torque

0.5 to 0.8N•m

Page 113

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.2 Cable Connecting Procedures

1 Introduction

3. Wire end treatment The solderless terminal size depends on the terminal screw size and wiring method. - Use solderless terminals of the following size. - Tighten the terminals to a torque of 0.5 N•m to 0.8 N•m.

2 Features and Part Names

In the case of M3 terminal screw Main unit, input/output powered extension unit/block and special function block • When one wire is connected to one terminal

3.2(0.13")

Terminal Crimp screw terminal

6.2mm(0.24") or less

3 Product Introduction

3.2(0.13") 6.2mm(0.24") or less

Terminal

• When two wires are connected to one terminal

4

3.2(0.13") Terminal Crimp screw terminal

Specifications

6.2mm(0.24") or less

6.3mm(0.25") or more 3.2(0.13")

5

Terminal

Version and Peripheral Devices

6.2mm(0.24") or less

6.3mm(0.25") or more

In the case of M3.5 terminal screw FX Series terminal block, FX2N-20PSU, FX2N-8AD

6

3.7(0.15")

System Configuration

• When one wire is connected to one terminal Terminal Crimp screw terminal

6.8mm(0.27") or less

7

3.7(0.15") 6.8mm(0.27") or less

Input/Output Nos., Unit Nos.

Terminal

• When two wires are connected to one terminal

3.7(0.15")

8

Terminal Crimp screw terminal

Installation

6.8mm(0.27") or less

6.0mm(0.24") or more 3.7(0.15")

6.8mm(0.27") or less

9

Terminal

Preparation and Power Supply Wiring

6.0mm(0.24") or more

10 Input Wiring

107

Page 114

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.2.2

9.2 Cable Connecting Procedures

Input/output connectors (FX2N input/output extension blocks) The input/output connectors of FX2N Series input/output extension blocks (connector type) conform to MIL-C83503. Prepare the input/output cables, referring to the following tables.

1. Applicable products Classification

Model names

Input/output extension blocks

FX2N-16EX-C, FX2N-16EXL-C, FX2N-16EYT-C

2. Preparation of input/output connectors 1) Compliant connectors (commercially available connectors) Use 20-pin (1-key) sockets conforming to MIL-C-83503. In advance, make sure that no interference is caused with peripheral parts, such as the connector cover. 2) Input/output cables (our options) Input/output cables with attached connectors are available. Model names FX-16E-500CAB-S FX-16E-150CAB

Length

Description

5m(10’4") General-purpose input/output cable

Shape • •

1.5m(4’11")

FX-16E-500CAB-R

• 3m(9’10") Cables for connecting FX Series terminal block • and input/output connector 5m(10’4") For the connection with FX Series terminal block, 1.5m(4’11") refer to the following chapter. • → [20. Terminal Block] 3m(9’10") • 5m(10’4")

FX-A32E-150CAB

1.5m(4’11")

FX-A32E-300CAB

3m(9’10")

FX-16E-300CAB FX-16E-500CAB FX-16E-150CAB-R FX-16E-300CAB-R

FX-A32E-500CAB

Single wire (Wire color: red) PLC side: A 20-pin connector Flat cables (with tube) A 20-pin connector at both ends

Round multicore cables A 20-pin connector at both ends

• •

Flat cables (with tube) PLC side: Two 20-pin connectors in 16point units. Terminal block side: A dedicated connector One common terminal covers 32 input/ output terminals.

Cables for connecting A Series Model A6TBXY36 connector/terminal block conversion unit and • 5m(10’4") input/output connector type •

3) Connectors for making input/output cables by users (our options) The users should prepare the electric wires and pressure bonding tool. Model name and composition of input/output connector Details of part (made by DDK Ltd.)

Our model name

Applicable electric wire (UL-1061 are recommended) and tool Electric wire size

Pressure bonding tool (made by DDK Ltd.)

FX2C-I/O-CON for flat cable

10-piece AWG28 (0.1mm2), 357J-4674D: Main body Solderless connector FRC2-A020-30S set 1.27 pitch, 20-core 357J-4664N: Attachment

FX2C-I/O-CON-S for bulk wire

5-piece set

Housing HU-200S2-001 Solderless contact HU-411S

AWG22 (0.3mm2) 357J-5538

FX2C-I/O-CON-SA for bulk wire

5-piece set

Housing HU-200S2-001 Solderless contact HU-411SA

AWG20 (0.5mm2) 357J-13963

4) Certified connectors (commercially available connectors) Connectors made by DDK Ltd. shown in Item (3) described in the previous page and connectors made by Matsushita Electric Works, Ltd. shown in the following table Model name of connector

108

Housing

AXW1204A

Contact

AXW7221

Semi-cover

AXW62001A

Compliant electric wires (UL-1061 is recommended) AWG22 (0.3mm2) AWG24 (0.2mm2)

Pressure bonding tool AXY52000

Page 115

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

1

Terminal block (for europe) [expansion board and special adapters]

Introduction

9.2.3

9.2 Cable Connecting Procedures

The expansion board and special adapters of a terminal block type have terminal blocks for Europe.

1. Applicable products Classification

2

Model names FX3G-485-BD, FX3G-2AD-BD, FX3G-1DA-BD

Special Adapters

FX3U-485ADP(-MB), FX3U-4AD-ADP, FX3U-4DA-ADP, FX3U-4AD-PT-ADP, FX3U-4AD-PTW-ADP, FX3U-4AD-PNK-ADP, FX3U-4AD-TC-ADP

Features and Part Names

Expansion Board

2. Electric wires Compliant electric wires and tightening torque

One electric wire

3

Tightening torque

End treatment •

0.3mm2 to 0.5mm2 (AWG22 to 20)

•

Two electric wires 0.3mm2 (AWG22) 0.22 to 0.25N•m

•

•

4

Bar terminal with insulating sleeve (recommended product) AI 0.5-8WH : Phoenix Contact Caulking tool CRIMPFOX ZA 3 : Phoenix Contact (CRIMPFOX UD 6 : Phoenix Contact)

Specifications

0.3 mm2 to 0.5 mm2 Bar terminal with (AWG22 to 20) insulating sleeve (Refer to the following outline drawing of bar terminal.)

Remove the coating of the stranded wire, twist the core wires, and connect the wires directly. Remove the coating from the solid wire, and connect the wire directly.

3. Treatment of electric wire ends Treat the ends of stranded wires and solid wires without coating or using bar terminals with insulating sleeve.

Manufacturer Phoenix Contact

Model names

Caulking tool

AI 0.5-8WH

CRIMPFOX ZA 3 (CRIMPFOX UD 6)

Stranded wire/solid wire

9mm (0.36") Insulating sleeve

2.6mm (0.11")

• For tightening the terminal, use a commercially available small screwdriver having a straight form that is not widened toward the end as shown right.

8mm (0.32")

7

14mm(0.56")

With straight tip 0.4mm (0.02")

8

2.5mm (0.1")

Installation

Manufacturer Phoenix Contact

Contact area (Crimp area)

Input/Output Nos., Unit Nos.

4. Tool

Caution : If the diameter of screwdriver grip is too small, tightening torque will not be able to be achieved. Use the following recommended screwdriver or an appropriate replacement (grip diameter: approximately 25mm (0.98") ).

6

Bar terminal with insulating sleeve

System Configuration

• Treatment using bar terminal with insulating sleeve It may be difficult to insert the electric wire into the insulating sleeve depending on the thickness of the electric wire sheath. Select the electric wire referring to the outline drawing.

5 Version and Peripheral Devices

• Treatment of stranded wires and solid wires without coating - Twist the ends of stranded wires tightly so that loose wires will not stick out. - Do not solder-plate the electric wire ends.

Product Introduction

Electric wire size (stranded wire/solid wire)

Model names

9

SZS 0.4 x 2.5

Preparation and Power Supply Wiring

10 Input Wiring

109

Page 116

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.3

9.3 Grounding

Grounding Ground the PLC as stated below. • Perform class D grounding. (Grounding resistance: 100 or less)

• Ground the PLC independently if possible. If it cannot be grounded independently, ground it jointly as shown below. PLC

Other equipment

Independent grounding Best condition

PLC

Other equipment

Shared grounding Good condition

PLC

Other equipment

Common grounding Not allowed

Extension devices of PLC (except expansion board and special adapter) PLC Special adapter

Expansion board

Main unit

Input/output extension unit

Special extension

Independent grounding Class D grounding (grounding resistance : 100

Other equipment or less)

• Use ground wires thicker than AWG14 (2 mm2). • Position the grounding point as close to the PLC as possible to decrease the length of the ground wire.

110

Page 117

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.4 Examples of External Wiring

1

Examples of External Wiring

9.4.1

Example of input/output wiring with 24V DC service power supply

Introduction

9.4

2

24V DC service power supply of the main unit can be used as a power supply for loads. AC power supply of 100 to 240V

Features and Part Names

Breaker

3

PL

In the case of sink input wiring Main unit

MC

MC Emergency stop

4

Class D grounding

N

MC

MC

Specifications

*1 L

Product Introduction

Power ON

S/S *2

0V 24V

X0

5

Power supply for loads connected to sequencer output terminals As for the details of emergency stop, see "DESIGN PRECAUTIONS" at "Safety Precautions" field.

X1

X7 Input impedance

S/S 0V 24V

COM0

0V 24V

7 Input/Output Nos., Unit Nos.

Y0 Fuse COM2 5V 0V 24V

5V 0V 24V

Y2 Load

8

*3 S/S

Installation

Input extension block

6 System Configuration

In the case of source input wiring

Version and Peripheral Devices

0V *2 24V

X0

9

*1 Connect the AC power supply to the L and N terminals (in any case of 100V AC system and 200V AC system).

Preparation and Power Supply Wiring

As for the details, see "WIRING PRECAUTIONS" at "Safety Precautions" field. *2 The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7. *3 Connect the 24V terminal (in the case of sink input) or the 0V terminal (in the case of source input) to the S/S terminal on the input extension block.

10 Input Wiring

111

Page 118

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.4.2

9.4 Examples of External Wiring

Example of sink input [-common] wiring An example of sink input [-common] wiring is given below. When connecting input/output powered extension units/blocks, carefully check the signal names on the terminal block because the sink and source input type units/blocks and the sink input type units/blocks vary in signal names on the terminal block.

Sink and source input type 5V 0V 24V

Special adapter 24+

AC power supply of 100 to 240V

Class D grounding

Breaker

24Main unit

Class D *1 grounding L

Power supply ON PL

Sink and source input type

5V 0V 24V

N S/S

MC

*7 0V *7 24V *2,3 Input extension S/S block 5V 0V 24V

*5 24V DC service power supply output

MC

DC power supply

24-

Class D Input / output powered extension unit *1 grounding L

Sink and source input type

5V 0V 24V

Emergency stop

MC

Class D *4 Special function 24+ grounding block 5V 0V 24V

MC

DC

Power supply for loads to be connected to PLC output terminals

N S/S 0V 24V *5

24V DC service power supply output

*2,3 Input extension S/S block

AC

As for the details of emergency stop operation, see "DESIGN PRECAUTIONS" at "Safety Precautions" field.

Sink input type

5V 0V 24V

Class D

*6 grounding Special function 24+ block 5V 0V 24V

24-

24V DC service power supply output

COM

24+ *5

*4 Some special function units/blocks do not have the power supply terminal. When using an external power supply, turn it ON at the Output extension same time with the main unit or earlier than the main unit. block When turning OFF the power, confirm the safety of the 5V 0V 24V system, and then turn OFF the power of the PLC (including special extension equipment) at the same time. *1 Connect the AC power supply to the L and N terminals (in *5 Do not connect the 24V terminals (24V DC service power any case of 100V AC system and 200V AC system). supply) of the main unit and the input/output extension unit Make sure that the power is turned ON at the same time in with each other. Connect the 0V terminal. the main unit and extension units or earlier in extension *6 Some special extension units/blocks do not have power units than the main unit. terminals. For the details, refer to "WIRING PRECAUTIONS" in When using an external power supply, turn it ON at the "Safety Precautions". same time with the extension unit or earlier than the As for the details, see "WIRING PRECAUTIONS" at extension unit. "Safety Precautions" field. When turning OFF the power, confirm the safety of the *2 Connect the 24V terminal of the main unit or the input/ system, and then turn OFF the power of the PLC (including output extension unit to the S/S terminal of the input special extension equipment) at the same time. extension block. *7 The "24V" and "0V" terminals are located on the output terminal *3 In the case of the sink input type, the S/S terminal is used side. as the 24+ terminal. For details on the terminal layout, refer to Section 4.7.

112

Page 119

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

1

Example of source input [+common] wiring

Introduction

9.4.3

9.4 Examples of External Wiring

An example of source input [+common] wiring is shown below.

Sink and source input type Special adapter 24+ 24Main unit

Breaker

Class D *1 grounding L

Power supply ON PL

N S/S

5V 0V 24V

*6 0V *6 24V

5V 0V 24V

*4 24V DC service power supply output

MC

4

MC

DC power supply

Class D *3 grounding Special function 24+ block

5

24-

5V 0V 24V

24V DC service power supply output

6

As for the details of emergency stop operation, see "DESIGN PRECAUTIONS" at "Safety Precautions" field.

System Configuration

*4 *2 Input extension S/S block

AC

Power supply for loads to be connected to PLC output terminals

N S/S 0V 24V

5V 0V 24V

Version and Peripheral Devices

DC

Class D Input / output powered extension unit *1 grounding L

Sink and source input type

Emergency stop

Specifications

*2 Input extension S/S block

MC

3

MC

Product Introduction

Sink and source input type

2 Features and Part Names

5V 0V 24V

AC power supply of 100 to 240V

Class D grounding

7

5V 0V 24V

Input/Output Nos., Unit Nos.

Class D *5 grounding Special function 24+ block 24-

5V 0V 24V

5V 0V 24V

113

10 Input Wiring

*2 Connect the 0V terminal of the main unit or extension unit to the S/S terminal of the input extension block.

9 Preparation and Power Supply Wiring

*1 Connect the AC power supply to the L and N terminals (in any case of 100V AC system and 200V AC system). Make sure that the power is turned ON at the same time in the main unit and extension units or earlier in extension units than the main unit. For the details, refer to "WIRING PRECAUTIONS" in "Safety Precautions". As for the details, see "WIRING PRECAUTIONS" at "Safety Precautions" field.

8 Installation

Output extension block

*3 Some special function units/blocks do not have the power supply terminal. When using an external power supply, turn it ON at the same time with the main unit or earlier than the main unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of the PLC (including special extension equipment) at the same time. *4 Do not connect the 24V terminals (24V DC service power supply) of the main unit and the input/output extension unit with each other. Connect the 0V terminal. *5 Some special extension units/blocks do not have power terminals. When using an external power supply, turn it ON at the same time with the extension unit or earlier than the extension unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of the PLC (including special extension equipment) at the same time. *6 The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.

Page 120

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

9.4.4

9.4 Examples of External Wiring

An external wiring example for the extension power supply unit (sink input [-common]) This example shows a sink input wiring (-common),including the extension power supply unit.When adding an input extension block,check the signal name on the terminal block since the sink/source type and sink type differ from each there.

Sink and source input type 5V0V 24V

Special adapter 24+

AC power supply of 100 to 240V

Class D grounding

Breaker

24Main unit

Sink and source input type

Class D *1 grounding L

Power supply ON PL

N S/S

5V0V 24V

MC

*6 0V *6 24V *2,3 Input extension S/S block 5V0V 24V

24V DC service power supply output

24-

Extension power supply unit

Class D *1 grounding L N

5V0V 24V

Class D *5 grounding Special function 24+ block 5V0V 24V Sink and source input type

24-

Emergency stop

MC

MC

DC power supply

*4 Class D Special function 24+ grounding block 5V 0V 24V

MC

DC

AC

Power supply for loads to be connected to PLC output terminals As for the details of emergency stop operation, see "DESIGN PRECAUTIONS" at "Safety Precautions" field. Wiring precaution: Grounding and power cables should be positioned to exit the unit from above as shown in the figure. Grounding and power cables

*2,3 Input extension S/S block 5V0V 24V

Output extension block 5V0V 24V *5 Some special function blocks do not have *1 Connect the AC power supply to the L and N terminals (in any case of 100V AC the power supply terminals. system and 200V AC system). When using an external power supply, Make sure that the power is turned ON at the same time in the main unit and turn it ON at the same time with the extension power supply units or earlier in extension power supply units than the extension power supply unit or earlier main unit. than the extension power supply unit. As for the details, see "WIRING PRECAUTIONS" at "Safety Precautions" field. *2 Connect the 24V terminal of the main unit to the S/S terminal of the input When turning OFF the power, confirm the extension block. safety of the system, and then turn OFF the power of the PLC (including special *3 In the case of the sink input type, the S/S terminal is used as the 24+ terminal. extension equipment) at the same time. *4 Some special function units/blocks do not have the power supply terminal. When using an external power supply, turn it ON at the same time with the *6 The "24V" and "0V" terminals are located main unit or earlier than the main unit. on the output terminal side. When turning OFF the power, confirm the safety of the system, and then turn For details on the terminal layout, refer to OFF the power of the PLC (including special extension equipment) at the same time. Section 4.7.

114

Page 121

FX3G Series Programmable Controllers

9 Preparation for Wiring and Power Supply Wiring

User's Manual - Hardware Edition

An external wiring example for the extension power supply unit (source input [+common]) This example shows a source input wiring (+common), including the extension power supply unit.

Sink and source input type Special adapter 24+ 24Main unit

Breaker

Class D *1 grounding L

Power supply ON PL

N S/S

5V 0V 24V

MC

*5 0V *5 24V

5V 0V 24V

MC

Extension power supply unit

*1 L

Class D grounding

N

AC

Power supply for loads to be connected to PLC output terminals

6

*2 Input extension S/S block

Wiring precaution: Grounding and power cables should be positioned to exit the unit from above as shown in the figure.

7 Input/Output Nos., Unit Nos.

Grounding and power cables

5V 0V 24V

Class D *4 grounding Special function 24+ block 24-

5V 0V 24V

8 Installation

Output extension block 5V 0V 24V

115

9

10 Input Wiring

When turning OFF the power, confirm the safety of the system, and then turn OFF the power of the PLC (including special extension equipment) at the same time. *4 Some special function blocks do not have the power supply terminals. When using an external power supply, turn it ON at the same time with the extension power supply unit or earlier than the extension power supply unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of the PLC (including special extension equipment) at the same time. *5 The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.

Preparation and Power Supply Wiring

*1 Connect the AC power supply to the L and N terminals (in any case of 100V AC system and 200V AC system). Make sure that the power is turned ON at the same time in the main unit and extension power supply units or earlier in extension power supply units than the main unit. As for the details, see "WIRING PRECAUTIONS" at "Safety Precautions" field. *2 Connect the 0V terminal of the main unit to the S/S terminal of the input extension block. *3 Some special function units/blocks do not have the power supply terminal. When using an external power supply, turn it ON at the same time with the main unit or earlier than the main unit.

System Configuration

As for the details of emergency stop operation, see "DESIGN PRECAUTIONS" at "Safety Precautions" field.

5V 0V 24V

Sink and source input type

DC

5 Version and Peripheral Devices

24-

4

MC

DC power supply

Class D *3 grounding Special function 24+ block 5V 0V 24V

Emergency stop

Specifications

24V DC service power supply output

*2 Input extension S/S block

3

MC

Product Introduction

Sink and source input type

2 Features and Part Names

5V 0V 24V

AC power supply of 100 to 240V

Class D grounding

1 Introduction

9.4.5

9.4 Examples of External Wiring