FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10. Input Wiring Procedures DESIGN PRECAUTIONS •
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS •
•
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.
WIRING PRECAUTIONS • • •
116
Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.
Page 123
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
1 Introduction
WIRING PRECAUTIONS • •
• •
•
3
4 Specifications
•
2
Product Introduction
• wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.
Features and Part Names
•
Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a
5 Version and Peripheral Devices
6 System Configuration
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
117
Page 124
FX3G Series Programmable Controllers User's Manual - Hardware Edition
10.1
10 Input Wiring Procedures 10.1 Before Starting Input Wiring
Before Starting Input Wiring
10.1.1 Sink and source input The input terminals (X) of the main unit are common to sink/source input of 24V DC internal power. FX2N Series input/output powered extension units/blocks have input terminals common to sink/source input or only for sink input.
1. Differences between the sink input circuit and the source input circuit • Sink input [-common] Sink input means a DC input signal with current-flow from the input (X) terminal. When a sensor with a transistor output is connected, NPN open collector transistor output can be used.
L N 24V 0V S/S X
• Source input [+common] Source input means a DC input signal with current-flow into the input (X) terminal. When a sensor with a transistor output is connected, PNP open collector transistor output can be used.
L N 24V 0V S/S X
2. Method of switching between sink/source input To switch the input type to sink or source input, wire the S/S terminal to the 0V or 24V terminal. - Sink input: [24V] terminal and [S/S] terminal are connected. - Source input: [0V] terminal and [S/S] terminal are connected. → Refer to Subsection 10.2.3 and Subsection 10.2.4 for wiring examples.
3. Instructions for using • Concurrent use of sink/source input It is possible to set all input terminals (X) of the main unit to the sink input mode or the source input mode. However, sink and source input terminals cannot be used concurrently. - The main unit and input/output powered extension units are individually set to the sink or source input mode. - The input mode of an input/output extension block is determined according to the selection of the sink or source input mode on the powered extension unit (power source). • Caution in selecting model A type common to sink/source input and a type only for sink input are both available. Select a proper type. Differences from FX1N PLCs in input specifications (reference) FX1N PLCs only for sink input (manuals in Japanese are supplied) and those common to sink/source input (manuals in English are supplied) have different model names. • In FX1N PLCs only for sink input, the S/S terminal and the 24V terminal are connected unlike in FX3G PLCs. • FX1N PLCs common to sink/source input are switched to the sink or source input mode by external wiring like FX3G PLCs.
118
Page 125
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
1
24V DC input (Sink and source input type) This section explains handling of 24V DC inputs in the main unit, precautions on input device connection, and external wiring examples. → For the input specifications, refer to Section 4.3
1. Input terminals L N S/S 0V 24V
*
Fuse
3
100 to 240V AC
Product Introduction
Sink input When a no-voltage contact or NPN open collector transistor output is connected between an input (X) terminal and the 0V terminal and the circuit is closed, the input (X) turns on. Then, the input display LED lights.
X000 X001
4 * Input impedance
L N
*
Fuse
5 100 to 240V AC
Version and Peripheral Devices
S/S 0V 24V X000 X001
6 * Input impedance
X000 to X007 in the FX3G-14M main unit, and X000 to X015 in the FX3G-24M main unit → For the functions of the RUN terminals, refer to Subsection 14.2.1.
2. Input circuit
Input filter value when 0 is specified
X000, X001, X003, X004
10 s
X002, X005, X006, X007
50 s
10 Input Wiring
Input number
9 Preparation and Power Supply Wiring
Change of filter time X000 to X007 have digital filters, and the filter time can be changed in increments of 1ms in the range from 0 to 15ms through special data register (D8020). When 0 is specified for the time, the input filter values are set as shown in the following table.
8 Installation
Function of input circuit The primary and secondary circuits for input are insulated with a photocoupler, and the second circuit is provided with a C-R filter. The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from the input line. There is a delay of approx. 10ms in response to input-switching from ON to OFF and from OFF to ON.
7 Input/Output Nos., Unit Nos.
RUN terminal setting X000 to X017 (up to the largest input number in the main unit*1) of the main unit can be used as RUN input terminals by setting parameters.
System Configuration
X007
*1.
Specifications
X007
Source input When a no-voltage contact or PNP open collector transistor output is connected between an input (X) terminal and the 24V terminal and the circuit is closed, the input (X) turns on. Then, the input display LED lights.
2 Features and Part Names
10.2.1 Handling of 24V DC input
Introduction
10.2
10.2 24V DC input (Sink and source input type)
119
Page 126
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.2 24V DC input (Sink and source input type)
3. Input sensitivity The PLC input current and input sensitivity are shown in the following table. When there is a series diode or resistance at the input contact or there is a parallel resistance or leakage current at the input contact, wire the terminals in accordance with the following table. → For the instructions for connecting input devices, refer to Subsection 10.2.2. Item
X000 to X007
Input voltage
X010 to max input number of the main unit 24V DC 10%
Input current Input sensitivity current
7mA
5mA
ON
4.5mA or more
3.5mA or more
OFF
1.5mA or less
1.5mA or less
10.2.2 Instructions for connecting input devices 1. In the case of no-voltage contact The input current of this PLC is 7mA/24V DC. (5mA/24V DC in X010 or later) Use input devices applicable to this minute current. If no-voltage contacts (switches) for large current are used, contact failure may occur. Input number
Input current
X000 to X007
7mA/24V DC
X010 or more
5mA/24V DC
<Example> Products of OMRON Type
Model name
Type
Model name
Microswitch
Models Z, V and D2RV
Operation switch
Model A3P
Proximity switch
Model TL
Photoelectric switch
Model E3S
2. In the case of input device with built-in series diode The voltage drop of the series diode should be approx. 4V or less. When lead switches with a series LED are used, up to two switches can be connected in series. Also make sure that the input current is over the input-sensing level while the switches are ON.
24V
0V
S/S PLC (sink input)
S/S LED
X
0V *1 *1 In the case of a type only for sink input, connect the device to the COM terminal.
120
PLC (source input)
LED X
24V
Page 127
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.2 24V DC input (Sink and source input type)
1 Use a device having a parallel resistance, Rp, of 15k or more. If the resistance is less than 15k , connect a bleeder resistance, Rb, obtained by the following formula as shown in the following figure.
2
4Rp (k ) 15-Rp 24V
Bleeder resistance
0V
S/S
Rb
S/S PLC (source input)
X 15k or more
0V *1
Bleeder resistance
3
Rb
Product Introduction
PLC (sink input)
Features and Part Names
Rb
X 15k or more
Rp 24V
Rp
4 Specifications
*1 In the case of a type only for sink input, connect the device to the COM terminal.
4. In the case of 2-wire proximity switch
6 (k ) I -1.5
5 Version and Peripheral Devices
Use a two-wire proximity switch whose leakage current, I is 1.5 mA or less when the switch is off. When the current is 1.5mA or more, connect a bleeder resistance, Rb, determined by the following formula as shown in the following figure.
Rb
Introduction
3. In the case of input device with built-in parallel resistance
6 0V
Bleeder resistance
S/S
2-wire Rb proximity sensor
S/S
2-wire Rb proximity sensor
I X
I X
7 Input/Output Nos., Unit Nos.
0V *1
PLC (source input)
System Configuration
PLC (sink input)
24V
Bleeder resistance
24V
*1 In the case of a type only for sink input, connect the device to the COM terminal.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
121
Page 128
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.2 24V DC input (Sink and source input type)
10.2.3 Examples of external wiring (sink input) Sink and source input type Main unit
Fuse
L N
*1
Class D grounding
S/S
*3
*4 0V *4 24V X0
5V 0V 24V
Input impedance
X1 Input terminal
0V
Input extension block
Threewire sensor
24V
S/S X0 *2
Sink and source input type 5V 0V 24V
X1 Input terminal
Two-wire proximity sensor
Input / output powered extension unit
L N S/S
Class D grounding
*3
*4 0V *4 24V X0 5V 0V 24V
Input extension block
X1 Input terminal 0V
24V
S/S X0 5V 0V 24V
*1 *2 *3 *4
122
X1 Input terminal
Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required. In the case of sink input wiring,short-circuit the terminals of the extension units as well as the S/S terminal and the 24V terminal of the main unit. The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.
Page 129
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.2 24V DC input (Sink and source input type)
1 Introduction
Use of input/output extension units/blocks of sink input type Main unit
Fuse
L
2 Features and Part Names
N
*1
Class D grounding
S/S
*3
*4 0V *4 24V
Sink and source input type
3 Product Introduction
X0
5V 0V 24V
X1 Input Input terminal impedance
4 Specifications
0V
Input extension block
Threewire sensor
24V
24+ X0 *2 X1 Input terminal
5
Two-wire proximity sensor
Version and Peripheral Devices
5V 0V 24V
Input / output powered extension unit
L
6
N
System Configuration
Class D grounding
Sink input type COM
24+
7
X0
Input extension block
X1 Input terminal 0V 24+
Input/Output Nos., Unit Nos.
5V 0V 24V
24V
8 Installation
X0
5V 0V 24V
Input terminal
*2
Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
*3
In the case of sink input wiring, short-circuit the S/S terminal and the 24V terminal of the main unit.
*4
The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.
9 Preparation and Power Supply Wiring
*1
X1
10 Input Wiring
123
Page 130
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.2 24V DC input (Sink and source input type)
10.2.4 Examples of external wiring (source input) Sink and source input type Main unit
Fuse
L N
*1
Class D grounding
S/S
*3
*4 0V *4 24V X0
5V 0V 24V
Threewire sensor
X1 Input Input terminal impedance 0V
24V
Input extension block S/S Two-wire proximity sensor
X0 Sink and source input type
5V 0V 24V
X1 Input terminal
*2
Input / output powered extension unit
L N S/S
Class D grounding
*3
0V 24V X0 5V 0V 24V
X1 Input terminal
Input extension block S/S
0V
24V
X0 5V 0V 24V
*1 *2
X1 Input terminal
Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
*3
In the case of source input wiring, short-circuit the terminals of the extension units as well as the S/S terminal and the 0V terminal of the main unit
*4
The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.
124
Page 131
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
1
100V AC Input
Introduction
10.3
10.3 100V AC Input
10.3.1 Input specifications
10.3.2 Handling of 100V AC Input
3
2. Input circuit The primary input circuit and the secondary input circuit are insulated with a photocoupler. There is a delay of approx. 25 to 30ms in response to input switching from ON to OFF and from OFF to ON.
L N
Fuse
100 to 240V AC COM *
100 to 120V AC Fuse
X000 X001
X007
3. Input sensitivity The input current and input sensitivity of these PLCs are shown in the following table. Specifications
Input voltage
100 to 120V AC +10%, -15% 50/60Hz
Input current
6.2 mA/110V 60Hz 4.7 mA/100V 50Hz ON
3.8mA/80V AC
OFF
1.7mA/30V AC
6
Percentage of simultaneous power-on: 70% or less
System Configuration
Input sensitivity
5 Version and Peripheral Devices
* Input impedance
4 Specifications
When voltage of 100 to 120V AC is applied between the input terminal and COM terminal, the input terminal is turned on. The input display LED lights. Do not connect the COM terminal of an AC input type input/ output powered extension unit/block with the COM terminal of a DC system.
Product Introduction
1. Input terminal
Item
2 Features and Part Names
Main units of a 100V AC input type are not available. Select the input for the input/output powered extension units/blocks. → For the specifications on input/output powered extension units, refer to Chapter 15. → For the specifications on input/output extension blocks, refer to Chapter 16.
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
125
Page 132
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.3 100V AC Input
10.3.3 Examples of external wiring (100V AC input) Main unit
Fuse
L
*1
N Class D grounding
S/S *4 0V *4 24V
24V DC input type (Sink wiring)
X000 X001
5V 0V 24V
Threewire sensor
Input terminal
Input impedance
0V
Input extension block
24V
S/S X0 *2 5V 0V 24V
X1 Input terminal
Two-wire proximity sensor
Input / output powered extension unit
FX2N-48ER-UA1/UL L N Class D grounding COM COM
100V AC input type
X0
5V 0V 24V
X1 Input terminal
Input extension block COM
MC
*3
X0
5V 0V 24V
X1
*1 Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." *2 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required *3 Do not take input signals from loads generating surge. *4 The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.
126
Page 133
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
1
Input Interruption (I00 to I50 ) The PLC (main unit) is provided with an input interruption function and has six interruption input points. Make sure that the ON duration or OFF duration of interruption input signals is 10 s or more (X000, X001, X003 and X004) or 50 s or more (X002 and X005). → For details on programming, refer to the programming manual.
2 Features and Part Names
10.4.1 Allocation of pointers to input numbers (input signal ON/OFF duration) Input number
Introduction
10.4
10.4 Input Interruption (I00 to I50 )
Interrupt pointer Interruption on trailing edge
Interrupt disable control
X000
I001
I000
M8050
X001
I101
I100
M8051
X002
I201
I200
M8052
X003
I301
I300
M8053
X004
I401
I400
M8054
X005
I501
I500
M8055
3
ON or OFF duration of input signal
Product Introduction
Interruption on leading edge
10 s or more 50 s or more 10 s or more
4
50 s or more
Specifications
10.4.2 Cautions for input interruption 1. Non-overlap of input numbers
Example: When the input interrupt pointer "I001" is used, X000 is occupied. Therefore, it is impossible to use C235, C241, C244, C246, C247, C249, C252 and C254, input interruption pointer I000, pulse catch contact M8170 and SPD, ZRN and DSZR instructions at the same time.
5 Version and Peripheral Devices
The input terminals X000 to X005 can be used for high-speed counter, input interruption, pulse catch, SPD, ZRN and DSZR instructions and general-purpose inputs. Take care not to overlap the input numbers.
6 System Configuration
7 Input/Output Nos., Unit Nos.
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
127
Page 134
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
10.5
10.5 Pulse Catch (M8170 to M8175)
Pulse Catch (M8170 to M8175) The PLC (main unit) is provided with a pulse catch function and has 6 pulse catch input points. → For details on programming, refer to the programming manual.
10.5.1 Allocation of special memories to input numbers (ON duration of input signals) Input number
Contact on sequence program
X000
M8170
X001
M8171
X002
M8172
X003
M8173
X004
M8174
X005
M8175
ON duration of input signal 10 s or more 50 s or more 10 s or more 50 s or more
10.5.2 Cautions for pulse catch 1. Non-overlap of input numbers The input terminals X000 to X005 can be used for high-speed counter, input interruption, pulse catch, speed detection (SPD) instructions and general-purpose input. Take care not to overlap the input numbers. Example: When the C235, C241, C244, C246, C247, C249, C252 and C254 is used, X000 is occupied. Therefore, it is impossible to use pulse catch input contact M8170.
128
Page 135
FX3G Series Programmable Controllers
10 Input Wiring Procedures
User's Manual - Hardware Edition
1
Pulse width/Pulse period measurement function (Supported in Ver. 1.10 or later)
Introduction
10.6
10.6 Pulse width/Pulse period measurement function
Four input points in the PLC (main unit) can be used for the pulse width/period measurement function which enables measurement of the pulse width or pulse frequency in units of 10 s. → For details on programming, refer to the programming manual.
Features and Part Names
10.6.1 Allocation of special memories to input numbers Pulse period measurement
X000 X001
Ring counter value for Ring counter value for
Pulse width/ mode rising edge*1 [in units of 1/6 s] falling edge*1 [in units of 1/6 s]
Pulse period*1*2 (in units of 10 s)
M8076
M8080
D8075, D8074
D8077, D8076
D8079, D8078
M8077
M8081
D8081, D8080
D8083, D8082
D8085, D8084
X003
M8078
M8082
D8087, D8086
D8089, D8088
D8091, D8090
X004
M8079
M8083
D8093, D8092
D8095, D8094
D8097, D8096
3 Product Introduction
Pulse width/ Pulse period measurement flag
Input number
2
4
Cleared when PLC switches from STOP to RUN.
*2.
The pulse width which can be measured is a minimum of 10 s and a maximum of 100s. The pulse period which can be measured is a minimum of 20 s.
Specifications
*1.
10.6.2 Cautions for pulse width/period measurement function
5
The input terminals X000, X001, X003 and X004 can be used for high-speed counter, input interruption, pulse catch, speed detection (SPD) instructions and general-purpose input. Take care not to overlap the input numbers. However, overlap of input numbers is allowed for input interruptions.
2. When the pulse width/period measurement function and high-speed counters are used together, the overall frequency of high-speed counters is affected. 3. Make sure that the total frequency of four input channels is 50kHz or less when using the pulse width/period measurement function. → For details on programming, refer to the programming manual.
7 Input/Output Nos., Unit Nos.
→ For more details, refer to Section 11.7.
6 System Configuration
Example: When the pulse width/period measurement flag M8076 is used, X000 is occupied. Therefore, it is impossible to use C235, C241, C244, C246, C247, C249, C252 and C254, pulse catch contact M8170, SPD, ZRN and DSZR instructions at the same time.
Version and Peripheral Devices
1. Non-overlap of input numbers
8 Installation
9 Preparation and Power Supply Wiring
10 Input Wiring
129