Page 122

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10. Input Wiring Procedures DESIGN PRECAUTIONS •

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

DESIGN PRECAUTIONS •

•

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.

WIRING PRECAUTIONS • • •

116

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

Page 123

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

1 Introduction

WIRING PRECAUTIONS • •

• •

•

3

4 Specifications

•

2

Product Introduction

• wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Features and Part Names

•

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a

5 Version and Peripheral Devices

6 System Configuration

7 Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

117

Page 124

FX3G Series Programmable Controllers User's Manual - Hardware Edition

10.1

10 Input Wiring Procedures 10.1 Before Starting Input Wiring

Before Starting Input Wiring

10.1.1 Sink and source input The input terminals (X) of the main unit are common to sink/source input of 24V DC internal power. FX2N Series input/output powered extension units/blocks have input terminals common to sink/source input or only for sink input.

1. Differences between the sink input circuit and the source input circuit • Sink input [-common] Sink input means a DC input signal with current-flow from the input (X) terminal. When a sensor with a transistor output is connected, NPN open collector transistor output can be used.

L N 24V 0V S/S X

• Source input [+common] Source input means a DC input signal with current-flow into the input (X) terminal. When a sensor with a transistor output is connected, PNP open collector transistor output can be used.

L N 24V 0V S/S X

2. Method of switching between sink/source input To switch the input type to sink or source input, wire the S/S terminal to the 0V or 24V terminal. - Sink input: [24V] terminal and [S/S] terminal are connected. - Source input: [0V] terminal and [S/S] terminal are connected. → Refer to Subsection 10.2.3 and Subsection 10.2.4 for wiring examples.

3. Instructions for using • Concurrent use of sink/source input It is possible to set all input terminals (X) of the main unit to the sink input mode or the source input mode. However, sink and source input terminals cannot be used concurrently. - The main unit and input/output powered extension units are individually set to the sink or source input mode. - The input mode of an input/output extension block is determined according to the selection of the sink or source input mode on the powered extension unit (power source). • Caution in selecting model A type common to sink/source input and a type only for sink input are both available. Select a proper type. Differences from FX1N PLCs in input specifications (reference) FX1N PLCs only for sink input (manuals in Japanese are supplied) and those common to sink/source input (manuals in English are supplied) have different model names. • In FX1N PLCs only for sink input, the S/S terminal and the 24V terminal are connected unlike in FX3G PLCs. • FX1N PLCs common to sink/source input are switched to the sink or source input mode by external wiring like FX3G PLCs.

118

Page 125

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

1

24V DC input (Sink and source input type) This section explains handling of 24V DC inputs in the main unit, precautions on input device connection, and external wiring examples. → For the input specifications, refer to Section 4.3

1. Input terminals L N S/S 0V 24V

*

Fuse

3

100 to 240V AC

Product Introduction

Sink input When a no-voltage contact or NPN open collector transistor output is connected between an input (X) terminal and the 0V terminal and the circuit is closed, the input (X) turns on. Then, the input display LED lights.

X000 X001

4 * Input impedance

L N

*

Fuse

5 100 to 240V AC

Version and Peripheral Devices

S/S 0V 24V X000 X001

6 * Input impedance

X000 to X007 in the FX3G-14M main unit, and X000 to X015 in the FX3G-24M main unit → For the functions of the RUN terminals, refer to Subsection 14.2.1.

2. Input circuit

Input filter value when 0 is specified

X000, X001, X003, X004

10 s

X002, X005, X006, X007

50 s

10 Input Wiring

Input number

9 Preparation and Power Supply Wiring

Change of filter time X000 to X007 have digital filters, and the filter time can be changed in increments of 1ms in the range from 0 to 15ms through special data register (D8020). When 0 is specified for the time, the input filter values are set as shown in the following table.

8 Installation

Function of input circuit The primary and secondary circuits for input are insulated with a photocoupler, and the second circuit is provided with a C-R filter. The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from the input line. There is a delay of approx. 10ms in response to input-switching from ON to OFF and from OFF to ON.

7 Input/Output Nos., Unit Nos.

RUN terminal setting X000 to X017 (up to the largest input number in the main unit*1) of the main unit can be used as RUN input terminals by setting parameters.

System Configuration

X007

*1.

Specifications

X007

Source input When a no-voltage contact or PNP open collector transistor output is connected between an input (X) terminal and the 24V terminal and the circuit is closed, the input (X) turns on. Then, the input display LED lights.

2 Features and Part Names

10.2.1 Handling of 24V DC input

Introduction

10.2

10.2 24V DC input (Sink and source input type)

119

Page 126

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.2 24V DC input (Sink and source input type)

3. Input sensitivity The PLC input current and input sensitivity are shown in the following table. When there is a series diode or resistance at the input contact or there is a parallel resistance or leakage current at the input contact, wire the terminals in accordance with the following table. → For the instructions for connecting input devices, refer to Subsection 10.2.2. Item

X000 to X007

Input voltage

X010 to max input number of the main unit 24V DC 10%

Input current Input sensitivity current

7mA

5mA

ON

4.5mA or more

3.5mA or more

OFF

1.5mA or less

1.5mA or less

10.2.2 Instructions for connecting input devices 1. In the case of no-voltage contact The input current of this PLC is 7mA/24V DC. (5mA/24V DC in X010 or later) Use input devices applicable to this minute current. If no-voltage contacts (switches) for large current are used, contact failure may occur. Input number

Input current

X000 to X007

7mA/24V DC

X010 or more

5mA/24V DC

<Example> Products of OMRON Type

Model name

Type

Model name

Microswitch

Models Z, V and D2RV

Operation switch

Model A3P

Proximity switch

Model TL

Photoelectric switch

Model E3S

2. In the case of input device with built-in series diode The voltage drop of the series diode should be approx. 4V or less. When lead switches with a series LED are used, up to two switches can be connected in series. Also make sure that the input current is over the input-sensing level while the switches are ON.

24V

0V

S/S PLC (sink input)

S/S LED

X

0V *1 *1 In the case of a type only for sink input, connect the device to the COM terminal.

120

PLC (source input)

LED X

24V

Page 127

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.2 24V DC input (Sink and source input type)

1 Use a device having a parallel resistance, Rp, of 15k or more. If the resistance is less than 15k , connect a bleeder resistance, Rb, obtained by the following formula as shown in the following figure.

2

4Rp (k ) 15-Rp 24V

Bleeder resistance

0V

S/S

Rb

S/S PLC (source input)

X 15k or more

0V *1

Bleeder resistance

3

Rb

Product Introduction

PLC (sink input)

Features and Part Names

Rb

X 15k or more

Rp 24V

Rp

4 Specifications

*1 In the case of a type only for sink input, connect the device to the COM terminal.

4. In the case of 2-wire proximity switch

6 (k ) I -1.5

5 Version and Peripheral Devices

Use a two-wire proximity switch whose leakage current, I is 1.5 mA or less when the switch is off. When the current is 1.5mA or more, connect a bleeder resistance, Rb, determined by the following formula as shown in the following figure.

Rb

Introduction

3. In the case of input device with built-in parallel resistance

6 0V

Bleeder resistance

S/S

2-wire Rb proximity sensor

S/S

2-wire Rb proximity sensor

I X

I X

7 Input/Output Nos., Unit Nos.

0V *1

PLC (source input)

System Configuration

PLC (sink input)

24V

Bleeder resistance

24V

*1 In the case of a type only for sink input, connect the device to the COM terminal.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

121

Page 128

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.2 24V DC input (Sink and source input type)

10.2.3 Examples of external wiring (sink input) Sink and source input type Main unit

Fuse

L N

*1

Class D grounding

S/S

*3

*4 0V *4 24V X0

5V 0V 24V

Input impedance

X1 Input terminal

0V

Input extension block

Threewire sensor

24V

S/S X0 *2

Sink and source input type 5V 0V 24V

X1 Input terminal

Two-wire proximity sensor

Input / output powered extension unit

L N S/S

Class D grounding

*3

*4 0V *4 24V X0 5V 0V 24V

Input extension block

X1 Input terminal 0V

24V

S/S X0 5V 0V 24V

*1 *2 *3 *4

122

X1 Input terminal

Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required. In the case of sink input wiring,short-circuit the terminals of the extension units as well as the S/S terminal and the 24V terminal of the main unit. The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.

Page 129

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.2 24V DC input (Sink and source input type)

1 Introduction

Use of input/output extension units/blocks of sink input type Main unit

Fuse

L

2 Features and Part Names

N

*1

Class D grounding

S/S

*3

*4 0V *4 24V

Sink and source input type

3 Product Introduction

X0

5V 0V 24V

X1 Input Input terminal impedance

4 Specifications

0V

Input extension block

Threewire sensor

24V

24+ X0 *2 X1 Input terminal

5

Two-wire proximity sensor

Version and Peripheral Devices

5V 0V 24V

Input / output powered extension unit

L

6

N

System Configuration

Class D grounding

Sink input type COM

24+

7

X0

Input extension block

X1 Input terminal 0V 24+

Input/Output Nos., Unit Nos.

5V 0V 24V

24V

8 Installation

X0

5V 0V 24V

Input terminal

*2

Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.

*3

In the case of sink input wiring, short-circuit the S/S terminal and the 24V terminal of the main unit.

*4

The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.

9 Preparation and Power Supply Wiring

*1

X1

10 Input Wiring

123

Page 130

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.2 24V DC input (Sink and source input type)

10.2.4 Examples of external wiring (source input) Sink and source input type Main unit

Fuse

L N

*1

Class D grounding

S/S

*3

*4 0V *4 24V X0

5V 0V 24V

Threewire sensor

X1 Input Input terminal impedance 0V

24V

Input extension block S/S Two-wire proximity sensor

X0 Sink and source input type

5V 0V 24V

X1 Input terminal

*2

Input / output powered extension unit

L N S/S

Class D grounding

*3

0V 24V X0 5V 0V 24V

X1 Input terminal

Input extension block S/S

0V

24V

X0 5V 0V 24V

*1 *2

X1 Input terminal

Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.

*3

In the case of source input wiring, short-circuit the terminals of the extension units as well as the S/S terminal and the 0V terminal of the main unit

*4

The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.

124

Page 131

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

1

100V AC Input

Introduction

10.3

10.3 100V AC Input

10.3.1 Input specifications

10.3.2 Handling of 100V AC Input

3

2. Input circuit The primary input circuit and the secondary input circuit are insulated with a photocoupler. There is a delay of approx. 25 to 30ms in response to input switching from ON to OFF and from OFF to ON.

L N

Fuse

100 to 240V AC COM *

100 to 120V AC Fuse

X000 X001

X007

3. Input sensitivity The input current and input sensitivity of these PLCs are shown in the following table. Specifications

Input voltage

100 to 120V AC +10%, -15% 50/60Hz

Input current

6.2 mA/110V 60Hz 4.7 mA/100V 50Hz ON

3.8mA/80V AC

OFF

1.7mA/30V AC

6

Percentage of simultaneous power-on: 70% or less

System Configuration

Input sensitivity

5 Version and Peripheral Devices

* Input impedance

4 Specifications

When voltage of 100 to 120V AC is applied between the input terminal and COM terminal, the input terminal is turned on. The input display LED lights. Do not connect the COM terminal of an AC input type input/ output powered extension unit/block with the COM terminal of a DC system.

Product Introduction

1. Input terminal

Item

2 Features and Part Names

Main units of a 100V AC input type are not available. Select the input for the input/output powered extension units/blocks. → For the specifications on input/output powered extension units, refer to Chapter 15. → For the specifications on input/output extension blocks, refer to Chapter 16.

7 Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

125

Page 132

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.3 100V AC Input

10.3.3 Examples of external wiring (100V AC input) Main unit

Fuse

L

*1

N Class D grounding

S/S *4 0V *4 24V

24V DC input type (Sink wiring)

X000 X001

5V 0V 24V

Threewire sensor

Input terminal

Input impedance

0V

Input extension block

24V

S/S X0 *2 5V 0V 24V

X1 Input terminal

Two-wire proximity sensor

Input / output powered extension unit

FX2N-48ER-UA1/UL L N Class D grounding COM COM

100V AC input type

X0

5V 0V 24V

X1 Input terminal

Input extension block COM

MC

*3

X0

5V 0V 24V

X1

*1 Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and Power Supply Wiring Procedures." *2 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required *3 Do not take input signals from loads generating surge. *4 The "24V" and "0V" terminals are located on the output terminal side. For details on the terminal layout, refer to Section 4.7.

126

Page 133

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

1

Input Interruption (I00 to I50 ) The PLC (main unit) is provided with an input interruption function and has six interruption input points. Make sure that the ON duration or OFF duration of interruption input signals is 10 s or more (X000, X001, X003 and X004) or 50 s or more (X002 and X005). → For details on programming, refer to the programming manual.

2 Features and Part Names

10.4.1 Allocation of pointers to input numbers (input signal ON/OFF duration) Input number

Introduction

10.4

10.4 Input Interruption (I00 to I50 )

Interrupt pointer Interruption on trailing edge

Interrupt disable control

X000

I001

I000

M8050

X001

I101

I100

M8051

X002

I201

I200

M8052

X003

I301

I300

M8053

X004

I401

I400

M8054

X005

I501

I500

M8055

3

ON or OFF duration of input signal

Product Introduction

Interruption on leading edge

10 s or more 50 s or more 10 s or more

4

50 s or more

Specifications

10.4.2 Cautions for input interruption 1. Non-overlap of input numbers

Example: When the input interrupt pointer "I001" is used, X000 is occupied. Therefore, it is impossible to use C235, C241, C244, C246, C247, C249, C252 and C254, input interruption pointer I000, pulse catch contact M8170 and SPD, ZRN and DSZR instructions at the same time.

5 Version and Peripheral Devices

The input terminals X000 to X005 can be used for high-speed counter, input interruption, pulse catch, SPD, ZRN and DSZR instructions and general-purpose inputs. Take care not to overlap the input numbers.

6 System Configuration

7 Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

127

Page 134

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

10.5

10.5 Pulse Catch (M8170 to M8175)

Pulse Catch (M8170 to M8175) The PLC (main unit) is provided with a pulse catch function and has 6 pulse catch input points. → For details on programming, refer to the programming manual.

10.5.1 Allocation of special memories to input numbers (ON duration of input signals) Input number

Contact on sequence program

X000

M8170

X001

M8171

X002

M8172

X003

M8173

X004

M8174

X005

M8175

ON duration of input signal 10 s or more 50 s or more 10 s or more 50 s or more

10.5.2 Cautions for pulse catch 1. Non-overlap of input numbers The input terminals X000 to X005 can be used for high-speed counter, input interruption, pulse catch, speed detection (SPD) instructions and general-purpose input. Take care not to overlap the input numbers. Example: When the C235, C241, C244, C246, C247, C249, C252 and C254 is used, X000 is occupied. Therefore, it is impossible to use pulse catch input contact M8170.

128

Page 135

FX3G Series Programmable Controllers

10 Input Wiring Procedures

User's Manual - Hardware Edition

1

Pulse width/Pulse period measurement function (Supported in Ver. 1.10 or later)

Introduction

10.6

10.6 Pulse width/Pulse period measurement function

Four input points in the PLC (main unit) can be used for the pulse width/period measurement function which enables measurement of the pulse width or pulse frequency in units of 10 s. → For details on programming, refer to the programming manual.

Features and Part Names

10.6.1 Allocation of special memories to input numbers Pulse period measurement

X000 X001

Ring counter value for Ring counter value for

Pulse width/ mode rising edge*1 [in units of 1/6 s] falling edge*1 [in units of 1/6 s]

Pulse period*1*2 (in units of 10 s)

M8076

M8080

D8075, D8074

D8077, D8076

D8079, D8078

M8077

M8081

D8081, D8080

D8083, D8082

D8085, D8084

X003

M8078

M8082

D8087, D8086

D8089, D8088

D8091, D8090

X004

M8079

M8083

D8093, D8092

D8095, D8094

D8097, D8096

3 Product Introduction

Pulse width/ Pulse period measurement flag

Input number

2

4

Cleared when PLC switches from STOP to RUN.

*2.

The pulse width which can be measured is a minimum of 10 s and a maximum of 100s. The pulse period which can be measured is a minimum of 20 s.

Specifications

*1.

10.6.2 Cautions for pulse width/period measurement function

5

The input terminals X000, X001, X003 and X004 can be used for high-speed counter, input interruption, pulse catch, speed detection (SPD) instructions and general-purpose input. Take care not to overlap the input numbers. However, overlap of input numbers is allowed for input interruptions.

2. When the pulse width/period measurement function and high-speed counters are used together, the overall frequency of high-speed counters is affected. 3. Make sure that the total frequency of four input channels is 50kHz or less when using the pulse width/period measurement function. → For details on programming, refer to the programming manual.

7 Input/Output Nos., Unit Nos.

→ For more details, refer to Section 11.7.

6 System Configuration

Example: When the pulse width/period measurement flag M8076 is used, X000 is occupied. Therefore, it is impossible to use C235, C241, C244, C246, C247, C249, C252 and C254, pulse catch contact M8170, SPD, ZRN and DSZR instructions at the same time.

Version and Peripheral Devices

1. Non-overlap of input numbers

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

129