FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 11. Use of High-speed Counters

Pages 136 to 145 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 136

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11.1 Outline

11. Use of High-speed Counters 11.1

Outline High-speed counters use input terminals X000 to X007 of the main unit for inputs, and offer counting up to 60kHz (1 phase). Input terminals not used for high-speed counters are available for general-purpose inputs. → For the input specifications for X000 to X007 of the main unit, refer to Section 10.2.

11.2

Types of Counting and Operations The main unit has built-in 32-bit high speed bi-directional counters (1-phase 1-count input, 1-phase 2-count input and 2-phase 2-count input). For some high-speed counters, external reset input terminals or external start input terminals (start of counting) can be selected.

11.2.1 Types and input signal forms The types and input signals (waveforms) of high-speed counters (1-phase 1-count input, 1-phase 2-count input and 2-phase 2-count input) are shown below. Counter type

Input signal form

1-phase 1-count input

UP/ DOWN

1-phase 2-count input

UP

Counting direction Down-count or up-count is specified by turning on or off M8235 to M8245. ON:Down-counting OFF:Up-counting

+1

+1 -1

Up-count or down-count The counting direction can be checked with M8246 to M8250. ON:Down-counting OFF:Up-counting

-1

DOWN Phase A 2-phase 2-count input

+1

+1

-1

-1

Phase B Up-counting

Down-counting

Automatic up-count or down-count according to change in input status of phase A/B The counting direction can be checked with M8251 to M8255. ON:Down-counting OFF:Up-counting

11.2.2 High-speed counter device notations The input terminal assignments for FX 3G PLC high-speed counters can be switched when used in combination with a special auxiliary relay. This section classifies these high-speed counter devices under the following notations. Note that an "(OP)" input cannot be programmed. Standard Device Numbers

Switched Device Numbers

C248

C248(OP)

C253

C253(OP)

C254

C254(OP)

11.2.3 Cautions in connecting mating device Encoders with the output forms in the following table can be connected to the input terminals. (The encoders may not function correctly depending on electrical compatibility. Check the specifications in advance.) Voltage output type encoders and absolute encoders cannot be connected to the high-speed counter input terminals. Terminals for connecting Input terminals of main unit

130

Output form that can be directly connected Open collector transistor output form (applicable to 24V DC)

Page 137

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11

List of Device Numbers and Functions → For details on the counter number (OP), refer to Subsection 11.2.2 Counter type

Device No. (counter)

C236 C237 C238 C239

10

C241

60

C249 C250

10

C252 C253 C254 C255

Provided

Provided

14

None

None

Provided

None

Provided

Provided

None

None

Provided

None

Provided

Provided

15

5

32-bit bi-directional counter

When using multiple high-speed counters, make sure that the sum of used frequency does not exceed the overall frequency. → For details on the overall frequency, refer to Section 11.7.

16 Input/Output Extension Blocks

*1.

32-bit bi-directional counter

30

C254(OP) 2-phase 2-count input

None

Input/Output Powered Extension Units

C251 C253(OP)

Provided

Test Run, Maintenance, Troubleshooting

C247 C248

60

12

13

10

C245

1-phase 2-count input

None

32-bit bi-directional counter

C242

C246 C248(OP)

None

60 10

C244

External start input terminal

60

C240

C243

External reset input terminal

Wiring for Various Uses

1-phase 1-count input

Data length

Output Wiring

C235

Response Frequency*1 (kHz)

High-Speed Counters

11.3

11.3 List of Device Numbers and Functions

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

131

Page 138

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11.4

11.4 Allocation of Device Numbers to Input Numbers

Allocation of Device Numbers to Input Numbers The high-speed counter numbers are allocated to the input terminals X000 to X007 as shown in the following table. The input terminals not allocated for high-speed counters can be used as general input terminals.

11.4.1 Allocation table U: Up-count input R: External reset input Counter type

D: Down-count input S: External start input

Counter No. C235

A: A-phase input Input allocation

X000

X001

X002

X003

C236

U/D U/D U/D

R

C242

U/D

R

C243

U/D U/D

S U/D

C246

U

D

C247

U

D

R

S

R

C248

U

D

U

D

U

D

R

C253

A

B

R

C253(OP)*1

A

B

C248(OP)*1 U

D

C251

A

B

C252

A

B

C254

A

B

R

R

C250

2-phase 2-count input

R

R

C245

C249

S S

R

R

S A

C254(OP)*1 C255

*1.

X007

U/D

C240

C244

X006

U/D

C239 C241

X005

U/D

C238

1-phase 2-count input

X004

U/D

C237

1-phase 1-count input

B: B-phase input

A

B

R

B S

When a special auxiliary relay is driven in a program, the input terminals and their associated functions are switched. → For the function switching method, refer to Subsection 11.8.2.

11.4.2 Restriction of redundant use of input numbers The input terminals X000 to X007 can be used for high-speed counters, input interruption, pulse catch, SPD, ZRN and DSZR instructions and general-purpose inputs. Take care not to overlap the input numbers. For example, when C251 is used, X000 and X001 are occupied. Therefore, it is impossible to use C235, C236, C241, C244, C246, C247, C249, C252 and C254, input interruption pointers I000 and I101, pulse catch contacts M8170 and M8171 and SPD, ZRN and DSZR instructions at the same time.

132

Page 139

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11

Handling of High-speed Counters

High-Speed Counters

11.5

11.5 Handling of High-speed Counters

11.5.1 1-phase 1-count input

12 • C235 counts the number of times the input terminal X000 switches from OFF to ON while X012 is on.

Output Wiring

Examples of program

• While X011 is on, the counter resets when RST instruction is executed.

13

1) For C235 X010 M8235

Down-count/ up-count

X011 RST

Reset

C235

C235

K-5

Wiring for Various Uses

• The counters C235 to C245 switch to the down-count or up-count mode by turning on or off M8235 to M8245.

X012

Count input

14

X000

2) For C244 X010

Down-count/ up-count

RST

C244

• C244 starts counting immediately when the input terminal X006 turns on while X012 is on. The count input terminal is X000. The setting for this example is the data of the indirectly designated data register (D1,D0).

X011 Reset

X012 C244

D0(D1) The setting is (D1,D0).

External reset input

External start input

X001

X006

X000

• C244 can be reset by X011 on the sequence. For C244, X001 is allocated as the external reset input. The counter resets immediately when X001 turns on. • The counters C235 to C245 switch to the down-count or up-count mode by turning on or off M8235 to M8245.

16 Input/Output Extension Blocks

Count input

17

Main unit

Extension Power Supply Unit

Example of operation The above counter C235 operates as shown below. X010

Up-count

X011

Reset input

X012

Start input

Up-count

Down-count

18 Other Extension Units and Options

X000 Count input

4

5

4

3

2

1

0 -1

When output has operated

19

0 -2

-3

-4

-5

-4 -6

-7

-8

-7

-6

Display Module

C235 2 Current 1 0 value

3

15 Input/Output Powered Extension Units

M8244

Test Run, Maintenance, Troubleshooting

Main unit

-3

-5

20

C235 output contact

Terminal Block

133

Page 140

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11.5 Handling of High-speed Counters

C235 is set to the up-count or down-count mode through interruption by the count input X000. • When the current value increases from -6 to -5, the output contact is set, and when the value decreases from -5 to -6, it is reset. • The current value increases and decreases regardless of the operation of the output contact. However, when the counter’s value increments from 2,147,483,647, it changes to -2,147,483,648. In the same manner, when it decrements from -2,147,483,648, it changes to 2,147,483,647. (This type of counter is called a ring counter.) • When RST instruction is executed after the reset input X011 turns on, the current counter's value resets to 0, and the output contact is restored. • The current value, output contact operation and reset status of counters are backed up (kept) even if the power is turned off.

11.5.2 1-phase 2-count input These counters are 32-bit up-count/down-count binary counters. The operations of the output contact according to the current value are the same as those of the abovementioned 1-phase 1-count input high-speed counters. Examples of program 1) For C246 • While X012 is on, C246 increments the value when the input terminal X000 switches from OFF to ON and decrements the value when the input terminal X001 switches from OFF to ON.

X011 RST

C246

X012 C246

• The down-count/up-count operations of C246 to C250 can be monitored through the ON/OFF operations of M8246 to M8250.

D2(D3)

The setting is (D3,D2) Up-counting Down-counting input input X000

ON: Down-counting OFF: Up-counting

X001

Main unit

2) For C249 • While X012 is on, C249 starts counting immediately when the input terminal X006 turns on. The up-counting input terminal is X000, and the downcounting input terminal is X001.

X011 RST

C249

X012 C249

K1234

• C249 can be reset on the sequence by X011. For C249, X002 is allocated as reset input. When X002 turns External start on, C249 is immediately reset. input

Down-counting input External Up-counting reset input input X000

X001

X002

Main unit

134

X006

• The down-count/up-count operations of C246 to C250 can be monitored through the ON/OFF operations of M8246 to M8250. ON: Down-counting OFF: Up-counting

Page 141

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11.5 Handling of High-speed Counters

11

These counters are 32-bit up-count/down-count binary counters. The operations of the output contact according to the current value are the same as those of the abovementioned 1-phase 1-count input high-speed counters. Examples of program

RST

• While X012 is on, C251 counts the operation of the input terminals X000 (A-phase) and X001 (B-phase) through interruption.

C251

X012 C251

• When the current value exceeds the setting, Y002 turns on, and when the current value becomes lower than the setting, Y002 turns off.

Y002 M8251 Y003

• Y003 turns on (down-count) or off (up-count) according to the counting direction.

A-phase input B-phase input

2) For C254 RST

C254

X012 C254

D0(D1)

Y004

The setting is (D1,D0).

C254

Y005

External start input B-phase input External reset A-phase input input

• Y005 turns on (down-count) or off (up-count) according to the counting direction.

17

X006

Main unit

• A 2-phase encoder generates A-phase output and B-phase output between which there is a 90 phase difference. The high-speed counter automatically counts up or down according to the output as shown below. +1

-1

-1

Phase B Up-counting

18 Other Extension Units and Options

Phase A +1

16

Extension Power Supply Unit

X002

• When the current value exceeds the setting (D1,D0), Y004 operates, and when the current value becomes lower than the setting, Y004 turns off.

Input/Output Extension Blocks

M8254

• C254 is reset by X011 on the sequence, and it is reset immediately when X002 is turned on.

15 Input/Output Powered Extension Units

• C254 starts counting immediately when the input terminal X006 is turned on while X012 is on. The count input terminals are X000 (A-phase) and X001 (B-phase).

X011

X001

14 Test Run, Maintenance, Troubleshooting

X001

Main unit

X000

Wiring for Various Uses

C251

X000

13

• While X011 is turned on, the counter is reset when RST instruction is executed.

K1234

12 Output Wiring

1) For C251 X011

High-Speed Counters

11.5.3 2-phase 2-count input

Down-counting

19 Display Module

• The down-count/up-count operations of C251 to C255 can be monitored through the ON/OFF operations of M8251 to M8255. ON: Down-counting OFF: Up-counting

20 Terminal Block

135

Page 142

FX3G Series Programmable Controllers User's Manual - Hardware Edition

11.6

11 Use of High-speed Counters 11.6 Timing of Updating of Current Value and Comparison of Current Value

Timing of Updating of Current Value and Comparison of Current Value

11.6.1 Timing of updating of current value When pulses are input to an input terminal for a high-speed counter, the high-speed counter executes upcounting or down-counting. The current values of devices are updated when counting is input.

11.6.2 Comparison of current value To compare and output the current value of a high-speed counter, the following two methods are available.

1. Use of comparison instruction (CMP), band comparison instruction (ZCP) or contact comparison instruction Use the comparison instruction (CMP), band comparison instruction (ZCP) or contact comparison instruction if the comparison result is necessary at counting. Use these instructions only when high-speed processing is not required because these instructions are processed in the operation cycle of the PLC, and operation delay is generated before the comparison output result is obtained. Use the comparison instructions for high-speed counters (HSCS, HSCR and HSZ) described below if it is necessary to execute comparison and change the output contact (Y) at the same time when the current values of high-speed counters change.

2. Use of Comparison instruction for high-speed counters (HSCS/HSCR/HSZ instruction) Comparison instructions for high-speed counters (HSCS, HSCR and HSZ instructions) perform comparison and output the comparison results with the relevant high-speed counting operation. These instructions have limitations on the number of times of use as shown in the following table. When the output relay (Y) has been designated for comparison results, the ON/OFF status of the output is affected directly until the END instruction output is refreshed. When the PLC is a relay output type, a mechanical delay in operation (approx. 10ms) is caused. Therefore, it is best to use a transistor output type PLC. Applied instruction

Limitation on number of times of use of instruction

HSCS*1 HSCR*1

Up to 6 times

HSZ*1

*1.

136

The overall frequency changes when the HSCS, HSCR or HSZ instruction is used. → For details on the overall frequency, refer to Section 11.7.

Page 143

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11

Response Frequency and Overall Frequency

High-Speed Counters

11.7

11.7 Response Frequency and Overall Frequency

1. Response Frequency and Overall Frequency

• When two or more high speed counters are used. • When the HSCS, HSCR, HSZ, PLSY, PLSR, DSZR, TBL, ZRN, PLSV, DRVI or DRVA instruction is used. • When the pulse width/cycle measurement function is used. When HSCS, HSCR or HSZ instruction is not used

When HSCS, HSCR or HSZ instruction is used

200kHz

60kHz

- (Number of positioned axes*1 + Number of pulse width/cycle measurement inputs) x 40kHz

- (Number of positioned axes*1 x 5kHz) - (Number of pulse width/cycle measurement inputs x 20kHz)

60kHz

14

10kHz 60kHz

C251, C253(OP) 2-phase 2count input C252, C253, C254, C254(OP), C255

30kHz

10kHz

5kHz

Test Run, Maintenance, Troubleshooting

C246, C248(OP) 1-phase 2count input C247, C248, C249, C250

15

Number of axes used in the following positioning instructions: PLSY(FNC57), PLSR(FNC59), DSZR(FNC150), TBL(FNC152), ZRN(FNC156), PLSV(FNC157), DRVI(FNC158), DRVA(FNC159)

Input/Output Powered Extension Units

*1.

Wiring for Various Uses

C235, C236, C238, 1-phase 1- C239, C241 count input C237, C240, C242, C243, C244, C245

13

Overall frequency determined by condition of used instruction

Response Frequency

Counter type

12 Output Wiring

When any of the following functions/instructions is used, the overall frequency is restricted without regard to the operand of the instruction. Consider this restriction when examining the system or creating programs, and observe the specified overall frequency range.

2. Calculation of overall frequency Obtain the overall frequency using the following expression:

16

Overall frequency phase counters)]

Input/Output Extension Blocks

[(Sum of used frequency of 1-phase counters) + (Sum of used frequency of 2-

3. Example of calculation

Overall frequency : 200kHz - (2 axes x 40kHz) = 120kHz <Contents of use>

C235(1-phase 1-count input):

50kHz is input.

C236(1-phase 1-count input):

50kHz is input.

C237(1-phase 1-count input):

10kHz is input.

C253(2-phase 2-count input):

5kHz is input. Total

115kHz

18 Other Extension Units and Options

<Counter No.>

120kHz (Overall frequency)

Overall frequency : 200 kHz - [(1 axes + 1 input) x 40 kHz] = 120 kHz

C235(1-phase 1-counting):

50kHz is input.

C236(1-phase 1-counting):

20 Terminal Block

<Contents of use> 50kHz is input. Total

100kHz

19 Display Module

Example2: When HSCS, HSCR or HSZ instruction is not used, and instructions related to positioning (DRVI instruction [Y000]) are used, Number of pulse width/cycle measurement inputs(X003)

<Counter No.>

17 Extension Power Supply Unit

Example1: When HSCS, HSCR or HSZ instruction is not used, and instructions related to positioning (DRVI instruction [Y000] and DRVA instruction [Y001]) are used

120kHz (Overall frequency)

137

Page 144

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11.8

11.8 Related Devices and Function Switching Procedures

Related Devices and Function Switching Procedures

11.8.1 Related devices 1. For switching 1-phase 1-count input counter mode to up-count or down-count Counter type

1-phase 1-count input

Counter No.

Specifying device

C235

M8235

C236

M8236

C237

M8237

C238

M8238

C239

M8239

C240

M8240

C241

M8241

C242

M8242

C243

M8243

C244

M8244

C245

M8245

Up-counting

Down-counting

OFF

ON

2. For monitoring of up-count/down-count counting direction of 1-phase 2-count input and 2phase 2-count input counters Counter type

1-phase 2-count input

2-phase 2-count input

Counter No.

Monitoring device

C246

M8246

C247

M8247

C248

M8248

C249

M8249

C250

M8250

C251

M8251

C252

M8252

C253

M8253

C254

M8254

C255

M8255

OFF

ON

Up-counting

Down-counting

3. For switching high-speed counter function Device No. M8388

138

Name

Description

Contact for changing high-speed counter Changes the function of high-speed counter function

Reference -

M8392

Function switching devices

Switches the function of C248 and C253

Subsection 11.8.2

M8395

Function switching devices

Switches the function of C254

Subsection 11.8.2

Page 145

FX3G Series Programmable Controllers

11 Use of High-speed Counters

User's Manual - Hardware Edition

11.8 Related Devices and Function Switching Procedures

11

When the counters C248, C253 and C254 are combined with the following special auxiliary relays, the allocation of the input terminals and functions are changed. Program the special auxiliary relays just before the counters. Counter No.

Function switching method

Details of change

M8392 •

Reset input is not given.

C248 K

13 Wiring for Various Uses

M8388 M8392 C253(OP)

•

Reset input is not given.

C253 K

M8395

14 •

C254(OP)

C254 K

• •

Test Run, Maintenance, Troubleshooting

M8388

12 Output Wiring

M8388 C248(OP)

High-Speed Counters

11.8.2 [Function switching] switching of allocation and functions of input terminals

The input count (2-phase 2-count) changes as follows Phase A : Changes from X000 to X006. Phase B : Changes from X001 to X007. Reset input is not given. Start input is not given.

15 Input/Output Powered Extension Units

16 Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

139