FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 12. Output Wiring Procedures

Pages 146 to 158 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 146

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12. Output Wiring Procedures

DESIGN PRECAUTIONS •

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that the output current of the 24V DC service power supply varies depending on the model and the absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the PLC are disabled, and all outputs are turned off. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

DESIGN PRECAUTIONS •

•

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.

WIRING PRECAUTIONS • • •

140

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

Page 147

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

11 High-Speed Counters

WIRING PRECAUTIONS • •

• •

•

13

14 Test Run, Maintenance, Troubleshooting

•

12

Wiring for Various Uses

• wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Output Wiring

•

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a

15 Input/Output Powered Extension Units

16 Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

141

Page 148

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.1

12.1 External Wiring for Relay Output Type

External Wiring for Relay Output Type This section explains relay outputs and external wiring. • There are not relay output type of main units. Select from the input/output powered extension units/blocks. • For the relay output specifications, refer to the following. → For the specifications on the input/output powered extension unit, refer to Chapter 15. → For the specifications on the input/output extension block, refer to Chapter 16.

12.1.1 Product life of relay contacts → For product life of relay contacts, refer to Subsection 14.4.3.

12.1.2 Handling of relay output 1. Output terminal One common terminal is used for 4 or 8 relay output points. The common terminal blocks can drive loads of different circuit voltage systems (for example,100V AC and 24V DC).

Load Y Y Fuse

0 1

24V DC COM1 Load Y Y

Fuse

4 5

100V AC COM2

PLC

2. External power supply Use an external power supply of 30V DC or less or 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards) for loads.

3. Circuit insulation The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and contact. The common terminal blocks are separated from one another.

4. Display of operation When power is applied to the output relay coil, the LED is lit, and the output contact is turned on.

5. Response time The response time of the output relay from when the power is applied to the coil until the output contact is turned on and from when the coil is shut off until the output contact is turned off is approx. 10ms.

6. Output current At a circuit voltage of 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards), a resistance load of 2A per point or an inductive load of 80VA or less (100V AC or 200V AC) can be driven. → For the life of the contact for switching an inductive load, refer to Subsection 14.4.3. When an inductive load is switched, connect a diode (for commutation) or a surge absorber in parallel with this load. DC circuit

Diode (for commutation)

AC circuit

Surge absorber

7. Open circuit leakage current Because there is no leakage current even while output contacts are OFF, the neon ball, etc. can be driven directly.

142

Page 149

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.1 External Wiring for Relay Output Type

11 High-Speed Counters

12.1.3 External wiring precautions 1. Protection circuit for load short-circuiting A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.

12

Load Y

0

Output Wiring

Fuse COM1 PLC

2. Contact protection circuit for inductive loads

1) DC circuit Connect a diode in parallel with the load. The diode (for commutation) must comply with the following specifications.

14 Inductive load PLC output contact

Guide

Reverse voltage

5 to 10 times the load voltage

Forward current

Load current or more

Test Run, Maintenance, Troubleshooting

Item

Diode (for commutation)

Surge absorber

Static electricity capacity Approx. 0.1 F Resistance value

16 Input/Output Extension Blocks

PLC output contact

Standard

15 Input/Output Powered Extension Units

2) AC circuit Connect the surge absorber (combined CR components such as a surge killer and spark killer, etc.) parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table below for other Inductive load specifications. Item

13 Wiring for Various Uses

An internal protection circuit for the relays is not provided for the relay output circuit in the extension blocks. It is recommended to use inductive loads with built-in protection circuits. When using loads without built-in protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product life.

Approx. 100 to 200

Reference Manufacturer

Model name

Manufacturer

Model name

Rubycon Corporation

250MCRA104100M B0325

3. Interlock Inter- Limit of normal lock rotation PLC output contact Limit of reverse rotation

PLC output contact

Normal rotation Reverse rotation

4. In-phase

18 Other Extension Units and Options

For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC’s internal programs as shown to the right.

17 Extension Power Supply Unit

Okaya Electric Industries Co., Ltd. CR-10201

19 Bad

Display Module

PLC output contacts (*) should be used in an "in-phase" manner. * *

20

*

Terminal Block

Good

*

143

Page 150

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.1 External Wiring for Relay Output Type

12.1.4 Example of external wiring AC power supply 100 to 240V Main unit transistor output (sink) COM0

Breaker

Y0

Power ON

PL MC

For the transistor output (sink) wiring of the main unit, refer to Subsection 12.2.4 "Transistor Output".

MC Emergency stop

MC

COM2

Y2 COM4

Y10

MC

*2

Fuse*1

Output extension block relay output

COM1

Y0

DC power supply

Y7 Load Fuse*1

*2

COM2

Y0 Y7 Load

Fuse *1

*2

Input/output powered extension unit relay output

COM1

Y0 Y1 Y2 Y3 Load Fuse*1

*2

COM5

Y0 Y7 Load

*2

Power supply for load connected to PLC output For details on emergency stop operation, refer to "DESIGN PRECAUTIONS" at "Safety Precautions" field. *1. The output circuit of this PLC does not have a built-in fuse. Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short-circuiting. *2. " " represents vacant terminals.

WIRING PRECAUTIONS •

144

Do not wire the vacant terminals externally. Doing so may damage the product.

Page 151

FX3G Series Programmable Controllers User's Manual - Hardware Edition

12.2 External Wiring of Transistor Output (Sink/Source)

11

External Wiring of Transistor Output (Sink/Source) Type

High-Speed Counters

12.2

12 Output Wiring Procedures

This section explains the procedures for handling transistor output and external wiring. • There are not transistor output source type of main units. Select from the input/output powered extension units/blocks.

12.2.1 Transistor Output Sink and Source

13

1. Differences in circuit

Y

Test Run, Maintenance, Troubleshooting

COM

15 Input/Output Powered Extension Units

• Source output [+common] Output to make load current flow out of the output (Y) terminal is called source output.

14

Load

Fuse DC power supply

Wiring for Various Uses

FX2N Series input/output extension units/blocks of transistor sink output type and of transistor source output type are available. FX3G Series main units provide only sink outputs.

• Sink output [-common] Output to make load current flow into the output (Y) terminal is called sink output.

12 Output Wiring

• For the transistor output specifications, refer to the following. → For the specifications on the main unit, refer to Subsection 4.4.1. → For the specifications on the input/output powered extension unit, refer to Chapter 15. → For the specifications on the input/output extension block, refer to Chapter 16.

Load Y

16 Input/Output Extension Blocks

Fuse DC power supply

+V

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

145

Page 152

FX3G Series Programmable Controllers User's Manual - Hardware Edition

12 Output Wiring Procedures 12.2 External Wiring of Transistor Output (Sink/Source)

12.2.2 Handling of transistor output 1. Output terminals One, 4 or 8 transistor output points are covered by one common terminal. Sink output Load current flows into the output (Y) terminals. Connect each COM (number) terminal to the minus side of the load power supply. The COM terminals are not connected internally.

Sink output type Load power Fuse DC supply

Y Y

0 1

COM1 Load power Fuse DC supply

Y Y

4 5

COM2

Source output Load current flows out of the output (Y) terminals. Connect each +V (number) terminal to the plus side of the load power supply. The +V terminals are not connected internally.

PLC

Source output type Load power Fuse DC supply

Y Y

0 1

+V0 Load power Fuse DC supply

Y Y

4 5

+V1

PLC

2. External power supply For driving the load, use a smoothing power supply of 5 to 30V DC that can output current two or more times the rated current of the fuse connected to the load circuit.

3. Insulation of circuit The internal circuit of the PLC and the output transistor are insulated with a photocoupler. The common blocks are separated from one another.

4. Display of operation Operation indicator LEDs are built into the main unit and output extension blocks, and turn ON when photocouplers are actuated.

146

Page 153

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.2 External Wiring of Transistor Output (Sink/Source)

11

The time from when the PLC drives (or shuts down) the photocoupler until the transistor is turned on (or off) is shown in the following table. Response time

Classification

Main unit 40/60 point type

5 to 24V DC 10mA or more

When using an instruction related to pulse train output or positioning, make sure to set the load current to 10 to 100mA (5 to 24V DC).

5 s or less

Y002 or more

0.2ms or less 24V DC 200 mA or more *1

Y000 to Y002

5 s or less

Y003 or more

0.2ms or less 24V DC 200mA or more *1

5 to 24V DC 10mA or more

When using an instruction related to pulse train output or positioning, make sure to set the load current to 10 to 100mA (5 to 24V DC).

Input/output powered extension unit 0.2ms or less 24V DC 200mA *1 Output extension block

*1.

The transistor OFF time is longer under lighter loads. For example, under a load of 24V DC 40mA, the response time is approx. 0.3ms. When response performance is required under light loads, provide a dummy resistor as shown below to increase the load current. Sink output type

Fuse Load

•

Dummy resistance Y

Source output type

PLC Fuse Load

Dummy resistance Y

15

+V0

6. Output current

Output current

17

Limitation

FX3G-24MT/ES FX3G-40MT/ES FX3G-60MT/ES FX2N-32ET-ESS/UL FX2N-48ET-ESS/UL FX2N-32ET

0.5A/point

FX2N-48ET

For FX2N-16EYT-C: 16 points/common: 1.6A or less

FX2N-16EYT-ESS/UL FX2N-8EYT-ESS/UL Output extension block

For FX2N-8EYT-H: 4 points/common: 2A or less

FX2N-16EYT

19

1A/point

FX2N-16EYT-C

0.3A/point

Display Module

FX2N-8EYT FX2N-8EYT-H

18 Other Extension Units and Options

Input/output powered extension units

The total load current of resistance loads per common terminal should be the following value. 1 point/common: 0.5A or less 4 points/common: 0.8A or less 8 points/common: 1.6A or less

Extension Power Supply Unit

FX3G-14MT/ES Main units

16 Input/Output Extension Blocks

The maximum resistance loads for the input/output powered extension units and output extension blocks are shown in the following table. The ON voltage of the output transistor is approx. 1.5V. When driving a semiconductor element, carefully check the input voltage characteristics of the applied element. Model

14

Input/Output Powered Extension Units

COM1

PLC

13

Test Run, Maintenance, Troubleshooting

•

12

Wiring for Various Uses

Y000, Y001

Output Wiring

Main unit 14/24 point type

Load current

High-Speed Counters

5. Response time

7. Open circuit leakage current

20

0.1mA or less

Terminal Block

147

Page 154

FX3G Series Programmable Controllers User's Manual - Hardware Edition

12 Output Wiring Procedures 12.2 External Wiring of Transistor Output (Sink/Source)

12.2.3 External wiring precautions 1. Protection circuit for load short-circuits A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output. Use a load power supply capacity that is at least 2 times larger than the total rated fuse capacity.

Sink output type Load

Y

Fuse COM1 PLC Source output type Load

Y

Fuse +V0 PLC

2. Contact protection circuit for inductive loads When an inductive load is connected, connect a diode (for commutation) in parallel with the load as necessary. The diode (for commutation) must comply with the following specifications.

Sink output type Inductive load

Y

Fuse Item

Guide

Reverse voltage 5 to 10 times of the load voltage

COM1

Forward current Load current or more

PLC

Source output type Inductive load

Y

Fuse

+V0 PLC

3. Interlock For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs, as shown to the right.

Interlock Limit of normal rotation Limit of reverse rotation Interlock Limit of normal rotation Limit of reverse rotation

148

Normal rotation Reverse PLC output rotation element

Normal rotation Reverse PLC output rotation element

Page 155

FX3G Series Programmable Controllers User's Manual - Hardware Edition

12 Output Wiring Procedures 12.2 External Wiring of Transistor Output (Sink/Source)

11 High-Speed Counters

12.2.4 Example of external wiring 1. Transistor output (Sink) AC power supply 100 to 240V

12 Output Wiring

Main unit transistor output (sink)

*1

Fuse

COM0

Y0

Breaker

Load COM2

Power ON

Y2 PL

MC Emergency stop

Load

COM4

Wiring for Various Uses

MC

13

*1

Fuse

Y10

MC

*2

MC

Test Run, Maintenance, Troubleshooting

Fuse *1

14

Output extension block transistor output (sink) COM1

Y0

DC power supply

Y7

15

*2

Input/Output Powered Extension Units

Load Fuse *1

COM2

Y0 Y7 Load

16 Input/Output Extension Blocks

Fuse*1

*2

Input/output powered extension unit COM1 transistor output (sink)

Y0

17

Y7

Power supply for load connected to PLC output

COM2

Y0 Y7 Load

18

*2

Other Extension Units and Options

For details on emergency stop operation, refer to "DESIGN PRECAUTIONS" at "Safety Precautions" field.

*2

Extension Power Supply Unit

Load Fuse*1

*1. The output circuit of this PLC does not have a built-in fuse. Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short-circuiting. *2. " " represents vacant terminals.

19 Display Module

WIRING PRECAUTIONS •

Do not wire the vacant terminals externally. Doing so may damage the product.

20 Terminal Block

149

Page 156

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.3

12.3 External Wiring for Triac (SSR) Output Type

External Wiring for Triac (SSR) Output Type This section explains the procedures for handling triac output and external wiring. • There are not triac output type of main units. Select from the input/output powered extension units/blocks. • For the triac output specifications, refer to the following. → For the specifications on the input/output powered extension unit, refer to Chapter 15. → For the specifications on the input/output extension block, refer to Chapter 16.

12.3.1 Handling of triac output 1. Output terminals On the triac output type units/blocks, one common terminal is used for 8 points. Therefore, the common terminal blocks can drive loads of different circuit voltage systems (for example, 100V AC and 200V AC).

Example : FX2N-16EYS Load Y0 Y1

Fuse

U

100VAC COM1 Load Y0 Y1

Fuse

U

200VAC COM2

PLC

2. Circuit insulation The PLC internal circuit and the output element (triac) are insulated with a photo-thyristor. The common terminal blocks are separate from one another.

3. Display of operation When the photo-thyristor is driven, the LED is lit, and the output triac is turned on.

4. Response time The time from when the photo-thyristor is driven or shut down until the output triac is turned on and until it is turned off is 1ms or less and 10ms or less, respectively.

5. Output current The max current per output point is 0.3A. However, to restrict temperature rise, the max current per one output from four points should be 0.8A (average per point is 0.2A). When a load with high rush current is turned on and off frequently, the root-mean-square current should be 0.2A or less. <Example> 42 0.02 + 0.42 0.7 = 0.2A 0.02 + 0.7 + 10

0.4A

4A

0.02 sec

0.7 sec

10 sec

6. Open circuit leakage current A C-R absorber is connected for turn-off in parallel with the triac output terminal of this type of PLC. Therefore, when the circuit opens, a leakage current will be 1mA at 100V AC and 2mA at 200V AC. Since the triac output type devices leak current when the circuits are open, small-size relays and micro current loads having low rated operating current may keep operating even when the triac output is turned off. Therefore, use a load of 0.4VA or more at 100V AC or 1.6VA or more at 200V AC. If the load is less than this value, connect a surge absorber as stated below in parallel with the load. → For the connection of the surge absorber, refer to 12.3.2 External wiring precautions.

150

Page 157

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.3 External Wiring for Triac (SSR) Output Type

11 High-Speed Counters

12.3.2 External wiring precautions 1. Protection circuit for load short-circuits A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.

12

Load Y

COM1 PLC

2. Micro current load

13

Guide Approx. 0.1 F

Resistance value

Micro current load

Surge absorber

14 Test Run, Maintenance, Troubleshooting

Item

Wiring for Various Uses

The PLC's internal Triac output circuit is equipped with a turn-off C-R absorber. When connecting a very low current load of "0.4VA/100V AC or less, or 1.6VA/200V AC or less", please connect a surge absorber parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table below for other specifications. Static electricity capacity

Approx. 100 to 200

Reference Manufacturer

Model name

Okaya Electric Industries Co., Ltd. CR-10201

Output Wiring

Fuse

Manufacturer

Model name

Rubycon Corporation

250MCRA104100M B0325

Inter- Limit of normal lock rotation

Limit of reverse rotation

PLC output element

Normal rotation Reverse rotation

4. In-phase PLC output contacts (*) should be used in an "in-phase" manner.

17 Extension Power Supply Unit

*

Bad

*

*

18

*

Other Extension Units and Options

Good

16 Input/Output Extension Blocks

For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs as shown to the right.

Input/Output Powered Extension Units

3. Interlock

15

19 Display Module

20 Terminal Block

151

Page 158

FX3G Series Programmable Controllers

12 Output Wiring Procedures

User's Manual - Hardware Edition

12.3 External Wiring for Triac (SSR) Output Type

12.3.3 Example of external wiring AC power supply 100 to 240V

Main unit transistor output (sink) COM0

Y0

Breaker Power ON PL MC

COM2

For the transistor output (sink) wiring of the main unit, refer to Subsection 12.2.4 "Transistor Output".

MC

Y2 COM4

Y10

Emergency stop

MC

*2

MC

Fuse

Output extension block triac output

*1

COM1

Y0

Y7 Load

*2

Power supply for load connected to PLC output For details on emergency stop operation, refer to "DESIGN PRECAUTIONS" at "Safety Precautions" field.

Input/output powered extension unit triac output

Fuse *1 COM1

Y0

Y3 Load

*2

*1. The output circuit of this PLC does not have a built-in fuse. Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short-circuiting. *2. " " represents vacant terminals.

WIRING PRECAUTIONS •

152

Do not wire the vacant terminals externally. Doing so may damage the product.