Page 146
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12. Output Wiring Procedures
DESIGN PRECAUTIONS •
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that the output current of the 24V DC service power supply varies depending on the model and the absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the PLC are disabled, and all outputs are turned off. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS •
•
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.
WIRING PRECAUTIONS • • •
140
Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.
Page 147
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
11 High-Speed Counters
WIRING PRECAUTIONS • •
• •
•
13
14 Test Run, Maintenance, Troubleshooting
•
12
Wiring for Various Uses
• wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.
Output Wiring
•
Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a
15 Input/Output Powered Extension Units
16 Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
141
Page 148
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.1
12.1 External Wiring for Relay Output Type
External Wiring for Relay Output Type This section explains relay outputs and external wiring. • There are not relay output type of main units. Select from the input/output powered extension units/blocks. • For the relay output specifications, refer to the following. → For the specifications on the input/output powered extension unit, refer to Chapter 15. → For the specifications on the input/output extension block, refer to Chapter 16.
12.1.1 Product life of relay contacts → For product life of relay contacts, refer to Subsection 14.4.3.
12.1.2 Handling of relay output 1. Output terminal One common terminal is used for 4 or 8 relay output points. The common terminal blocks can drive loads of different circuit voltage systems (for example,100V AC and 24V DC).
Load Y Y Fuse
0 1
24V DC COM1 Load Y Y
Fuse
4 5
100V AC COM2
PLC
2. External power supply Use an external power supply of 30V DC or less or 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards) for loads.
3. Circuit insulation The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and contact. The common terminal blocks are separated from one another.
4. Display of operation When power is applied to the output relay coil, the LED is lit, and the output contact is turned on.
5. Response time The response time of the output relay from when the power is applied to the coil until the output contact is turned on and from when the coil is shut off until the output contact is turned off is approx. 10ms.
6. Output current At a circuit voltage of 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards), a resistance load of 2A per point or an inductive load of 80VA or less (100V AC or 200V AC) can be driven. → For the life of the contact for switching an inductive load, refer to Subsection 14.4.3. When an inductive load is switched, connect a diode (for commutation) or a surge absorber in parallel with this load. DC circuit
Diode (for commutation)
AC circuit
Surge absorber
7. Open circuit leakage current Because there is no leakage current even while output contacts are OFF, the neon ball, etc. can be driven directly.
142
Page 149
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.1 External Wiring for Relay Output Type
11 High-Speed Counters
12.1.3 External wiring precautions 1. Protection circuit for load short-circuiting A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.
12
Load Y
0
Output Wiring
Fuse COM1 PLC
2. Contact protection circuit for inductive loads
1) DC circuit Connect a diode in parallel with the load. The diode (for commutation) must comply with the following specifications.
14 Inductive load PLC output contact
Guide
Reverse voltage
5 to 10 times the load voltage
Forward current
Load current or more
Test Run, Maintenance, Troubleshooting
Item
Diode (for commutation)
Surge absorber
Static electricity capacity Approx. 0.1 F Resistance value
16 Input/Output Extension Blocks
PLC output contact
Standard
15 Input/Output Powered Extension Units
2) AC circuit Connect the surge absorber (combined CR components such as a surge killer and spark killer, etc.) parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table below for other Inductive load specifications. Item
13 Wiring for Various Uses
An internal protection circuit for the relays is not provided for the relay output circuit in the extension blocks. It is recommended to use inductive loads with built-in protection circuits. When using loads without built-in protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product life.
Approx. 100 to 200
Reference Manufacturer
Model name
Manufacturer
Model name
Rubycon Corporation
250MCRA104100M B0325
3. Interlock Inter- Limit of normal lock rotation PLC output contact Limit of reverse rotation
PLC output contact
Normal rotation Reverse rotation
4. In-phase
18 Other Extension Units and Options
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC’s internal programs as shown to the right.
17 Extension Power Supply Unit
Okaya Electric Industries Co., Ltd. CR-10201
19 Bad
Display Module
PLC output contacts (*) should be used in an "in-phase" manner. * *
20
*
Terminal Block
Good
*
143
Page 150
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.1 External Wiring for Relay Output Type
12.1.4 Example of external wiring AC power supply 100 to 240V Main unit transistor output (sink) COM0
Breaker
Y0
Power ON
PL MC
For the transistor output (sink) wiring of the main unit, refer to Subsection 12.2.4 "Transistor Output".
MC Emergency stop
MC
COM2
Y2 COM4
Y10
MC
*2
Fuse*1
Output extension block relay output
COM1
Y0
DC power supply
Y7 Load Fuse*1
*2
COM2
Y0 Y7 Load
Fuse *1
*2
Input/output powered extension unit relay output
COM1
Y0 Y1 Y2 Y3 Load Fuse*1
*2
COM5
Y0 Y7 Load
*2
Power supply for load connected to PLC output For details on emergency stop operation, refer to "DESIGN PRECAUTIONS" at "Safety Precautions" field. *1. The output circuit of this PLC does not have a built-in fuse. Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short-circuiting. *2. " " represents vacant terminals.
WIRING PRECAUTIONS •
144
Do not wire the vacant terminals externally. Doing so may damage the product.
Page 151
FX3G Series Programmable Controllers User's Manual - Hardware Edition
12.2 External Wiring of Transistor Output (Sink/Source)
11
External Wiring of Transistor Output (Sink/Source) Type
High-Speed Counters
12.2
12 Output Wiring Procedures
This section explains the procedures for handling transistor output and external wiring. • There are not transistor output source type of main units. Select from the input/output powered extension units/blocks.
12.2.1 Transistor Output Sink and Source
13
1. Differences in circuit
Y
Test Run, Maintenance, Troubleshooting
COM
15 Input/Output Powered Extension Units
• Source output [+common] Output to make load current flow out of the output (Y) terminal is called source output.
14
Load
Fuse DC power supply
Wiring for Various Uses
FX2N Series input/output extension units/blocks of transistor sink output type and of transistor source output type are available. FX3G Series main units provide only sink outputs.
• Sink output [-common] Output to make load current flow into the output (Y) terminal is called sink output.
12 Output Wiring
• For the transistor output specifications, refer to the following. → For the specifications on the main unit, refer to Subsection 4.4.1. → For the specifications on the input/output powered extension unit, refer to Chapter 15. → For the specifications on the input/output extension block, refer to Chapter 16.
Load Y
16 Input/Output Extension Blocks
Fuse DC power supply
+V
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
145
Page 152
FX3G Series Programmable Controllers User's Manual - Hardware Edition
12 Output Wiring Procedures 12.2 External Wiring of Transistor Output (Sink/Source)
12.2.2 Handling of transistor output 1. Output terminals One, 4 or 8 transistor output points are covered by one common terminal. Sink output Load current flows into the output (Y) terminals. Connect each COM (number) terminal to the minus side of the load power supply. The COM terminals are not connected internally.
Sink output type Load power Fuse DC supply
Y Y
0 1
COM1 Load power Fuse DC supply
Y Y
4 5
COM2
Source output Load current flows out of the output (Y) terminals. Connect each +V (number) terminal to the plus side of the load power supply. The +V terminals are not connected internally.
PLC
Source output type Load power Fuse DC supply
Y Y
0 1
+V0 Load power Fuse DC supply
Y Y
4 5
+V1
PLC
2. External power supply For driving the load, use a smoothing power supply of 5 to 30V DC that can output current two or more times the rated current of the fuse connected to the load circuit.
3. Insulation of circuit The internal circuit of the PLC and the output transistor are insulated with a photocoupler. The common blocks are separated from one another.
4. Display of operation Operation indicator LEDs are built into the main unit and output extension blocks, and turn ON when photocouplers are actuated.
146
Page 153
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.2 External Wiring of Transistor Output (Sink/Source)
11
The time from when the PLC drives (or shuts down) the photocoupler until the transistor is turned on (or off) is shown in the following table. Response time
Classification
Main unit 40/60 point type
5 to 24V DC 10mA or more
When using an instruction related to pulse train output or positioning, make sure to set the load current to 10 to 100mA (5 to 24V DC).
5 s or less
Y002 or more
0.2ms or less 24V DC 200 mA or more *1
Y000 to Y002
5 s or less
Y003 or more
0.2ms or less 24V DC 200mA or more *1
5 to 24V DC 10mA or more
When using an instruction related to pulse train output or positioning, make sure to set the load current to 10 to 100mA (5 to 24V DC).
Input/output powered extension unit 0.2ms or less 24V DC 200mA *1 Output extension block
*1.
The transistor OFF time is longer under lighter loads. For example, under a load of 24V DC 40mA, the response time is approx. 0.3ms. When response performance is required under light loads, provide a dummy resistor as shown below to increase the load current. Sink output type
Fuse Load
•
Dummy resistance Y
Source output type
PLC Fuse Load
Dummy resistance Y
15
+V0
6. Output current
Output current
17
Limitation
FX3G-24MT/ES FX3G-40MT/ES FX3G-60MT/ES FX2N-32ET-ESS/UL FX2N-48ET-ESS/UL FX2N-32ET
0.5A/point
FX2N-48ET
For FX2N-16EYT-C: 16 points/common: 1.6A or less
FX2N-16EYT-ESS/UL FX2N-8EYT-ESS/UL Output extension block
For FX2N-8EYT-H: 4 points/common: 2A or less
FX2N-16EYT
19
1A/point
FX2N-16EYT-C
0.3A/point
Display Module
FX2N-8EYT FX2N-8EYT-H
18 Other Extension Units and Options
Input/output powered extension units
The total load current of resistance loads per common terminal should be the following value. 1 point/common: 0.5A or less 4 points/common: 0.8A or less 8 points/common: 1.6A or less
Extension Power Supply Unit
FX3G-14MT/ES Main units
16 Input/Output Extension Blocks
The maximum resistance loads for the input/output powered extension units and output extension blocks are shown in the following table. The ON voltage of the output transistor is approx. 1.5V. When driving a semiconductor element, carefully check the input voltage characteristics of the applied element. Model
14
Input/Output Powered Extension Units
COM1
PLC
13
Test Run, Maintenance, Troubleshooting
•
12
Wiring for Various Uses
Y000, Y001
Output Wiring
Main unit 14/24 point type
Load current
High-Speed Counters
5. Response time
7. Open circuit leakage current
20
0.1mA or less
Terminal Block
147
Page 154
FX3G Series Programmable Controllers User's Manual - Hardware Edition
12 Output Wiring Procedures 12.2 External Wiring of Transistor Output (Sink/Source)
12.2.3 External wiring precautions 1. Protection circuit for load short-circuits A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output. Use a load power supply capacity that is at least 2 times larger than the total rated fuse capacity.
Sink output type Load
Y
Fuse COM1 PLC Source output type Load
Y
Fuse +V0 PLC
2. Contact protection circuit for inductive loads When an inductive load is connected, connect a diode (for commutation) in parallel with the load as necessary. The diode (for commutation) must comply with the following specifications.
Sink output type Inductive load
Y
Fuse Item
Guide
Reverse voltage 5 to 10 times of the load voltage
COM1
Forward current Load current or more
PLC
Source output type Inductive load
Y
Fuse
+V0 PLC
3. Interlock For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs, as shown to the right.
Interlock Limit of normal rotation Limit of reverse rotation Interlock Limit of normal rotation Limit of reverse rotation
148
Normal rotation Reverse PLC output rotation element
Normal rotation Reverse PLC output rotation element
Page 155
FX3G Series Programmable Controllers User's Manual - Hardware Edition
12 Output Wiring Procedures 12.2 External Wiring of Transistor Output (Sink/Source)
11 High-Speed Counters
12.2.4 Example of external wiring 1. Transistor output (Sink) AC power supply 100 to 240V
12 Output Wiring
Main unit transistor output (sink)
*1
Fuse
COM0
Y0
Breaker
Load COM2
Power ON
Y2 PL
MC Emergency stop
Load
COM4
Wiring for Various Uses
MC
13
*1
Fuse
Y10
MC
*2
MC
Test Run, Maintenance, Troubleshooting
Fuse *1
14
Output extension block transistor output (sink) COM1
Y0
DC power supply
Y7
15
*2
Input/Output Powered Extension Units
Load Fuse *1
COM2
Y0 Y7 Load
16 Input/Output Extension Blocks
Fuse*1
*2
Input/output powered extension unit COM1 transistor output (sink)
Y0
17
Y7
Power supply for load connected to PLC output
COM2
Y0 Y7 Load
18
*2
Other Extension Units and Options
For details on emergency stop operation, refer to "DESIGN PRECAUTIONS" at "Safety Precautions" field.
*2
Extension Power Supply Unit
Load Fuse*1
*1. The output circuit of this PLC does not have a built-in fuse. Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short-circuiting. *2. " " represents vacant terminals.
19 Display Module
WIRING PRECAUTIONS •
Do not wire the vacant terminals externally. Doing so may damage the product.
20 Terminal Block
149
Page 156
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.3
12.3 External Wiring for Triac (SSR) Output Type
External Wiring for Triac (SSR) Output Type This section explains the procedures for handling triac output and external wiring. • There are not triac output type of main units. Select from the input/output powered extension units/blocks. • For the triac output specifications, refer to the following. → For the specifications on the input/output powered extension unit, refer to Chapter 15. → For the specifications on the input/output extension block, refer to Chapter 16.
12.3.1 Handling of triac output 1. Output terminals On the triac output type units/blocks, one common terminal is used for 8 points. Therefore, the common terminal blocks can drive loads of different circuit voltage systems (for example, 100V AC and 200V AC).
Example : FX2N-16EYS Load Y0 Y1
Fuse
U
100VAC COM1 Load Y0 Y1
Fuse
U
200VAC COM2
PLC
2. Circuit insulation The PLC internal circuit and the output element (triac) are insulated with a photo-thyristor. The common terminal blocks are separate from one another.
3. Display of operation When the photo-thyristor is driven, the LED is lit, and the output triac is turned on.
4. Response time The time from when the photo-thyristor is driven or shut down until the output triac is turned on and until it is turned off is 1ms or less and 10ms or less, respectively.
5. Output current The max current per output point is 0.3A. However, to restrict temperature rise, the max current per one output from four points should be 0.8A (average per point is 0.2A). When a load with high rush current is turned on and off frequently, the root-mean-square current should be 0.2A or less. <Example> 42 0.02 + 0.42 0.7 = 0.2A 0.02 + 0.7 + 10
0.4A
4A
0.02 sec
0.7 sec
10 sec
6. Open circuit leakage current A C-R absorber is connected for turn-off in parallel with the triac output terminal of this type of PLC. Therefore, when the circuit opens, a leakage current will be 1mA at 100V AC and 2mA at 200V AC. Since the triac output type devices leak current when the circuits are open, small-size relays and micro current loads having low rated operating current may keep operating even when the triac output is turned off. Therefore, use a load of 0.4VA or more at 100V AC or 1.6VA or more at 200V AC. If the load is less than this value, connect a surge absorber as stated below in parallel with the load. → For the connection of the surge absorber, refer to 12.3.2 External wiring precautions.
150
Page 157
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.3 External Wiring for Triac (SSR) Output Type
11 High-Speed Counters
12.3.2 External wiring precautions 1. Protection circuit for load short-circuits A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.
12
Load Y
COM1 PLC
2. Micro current load
13
Guide Approx. 0.1 F
Resistance value
Micro current load
Surge absorber
14 Test Run, Maintenance, Troubleshooting
Item
Wiring for Various Uses
The PLC's internal Triac output circuit is equipped with a turn-off C-R absorber. When connecting a very low current load of "0.4VA/100V AC or less, or 1.6VA/200V AC or less", please connect a surge absorber parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table below for other specifications. Static electricity capacity
Approx. 100 to 200
Reference Manufacturer
Model name
Okaya Electric Industries Co., Ltd. CR-10201
Output Wiring
Fuse
Manufacturer
Model name
Rubycon Corporation
250MCRA104100M B0325
Inter- Limit of normal lock rotation
Limit of reverse rotation
PLC output element
Normal rotation Reverse rotation
4. In-phase PLC output contacts (*) should be used in an "in-phase" manner.
17 Extension Power Supply Unit
*
Bad
*
*
18
*
Other Extension Units and Options
Good
16 Input/Output Extension Blocks
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs as shown to the right.
Input/Output Powered Extension Units
3. Interlock
15
19 Display Module
20 Terminal Block
151
Page 158
FX3G Series Programmable Controllers
12 Output Wiring Procedures
User's Manual - Hardware Edition
12.3 External Wiring for Triac (SSR) Output Type
12.3.3 Example of external wiring AC power supply 100 to 240V
Main unit transistor output (sink) COM0
Y0
Breaker Power ON PL MC
COM2
For the transistor output (sink) wiring of the main unit, refer to Subsection 12.2.4 "Transistor Output".
MC
Y2 COM4
Y10
Emergency stop
MC
*2
MC
Fuse
Output extension block triac output
*1
COM1
Y0
Y7 Load
*2
Power supply for load connected to PLC output For details on emergency stop operation, refer to "DESIGN PRECAUTIONS" at "Safety Precautions" field.
Input/output powered extension unit triac output
Fuse *1 COM1
Y0
Y3 Load
*2
*1. The output circuit of this PLC does not have a built-in fuse. Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by output element fracture due to load short-circuiting. *2. " " represents vacant terminals.
WIRING PRECAUTIONS •
152
Do not wire the vacant terminals externally. Doing so may damage the product.