FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 13. Examples of Wiring for Various Uses

Pages 159 to 169 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 159

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

11 High-Speed Counters

13. Examples of Wiring for Various Uses

12 •

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

17 Extension Power Supply Unit

•

16 Input/Output Extension Blocks

•

Input/Output Powered Extension Units

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.

WIRING PRECAUTIONS •

Test Run, Maintenance, Troubleshooting

•

14

15

DESIGN PRECAUTIONS •

13 Wiring for Various Uses

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

Output Wiring

DESIGN PRECAUTIONS

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

153

Page 160

FX3G Series Programmable Controllers User's Manual - Hardware Edition

13 Examples of Wiring for Various Uses 13.1 Notes about Examples of Wiring

WIRING PRECAUTIONS • •

• • • •

•

•

13.1

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a wire 2 mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Do not wire vacant terminals externally. Doing so may damage the product. Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m. Make sure to properly wire to the European terminal board in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.22 and 0.25 N•m. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Notes about Examples of Wiring The examples of wiring are given under the following conditions. → For the example of positioning wiring, refer to the Positioning Control Edition. • The input/output numbers are the actual numbers on the program. (They may differ from the numbers shown on the product terminals.) • Product input/output specifications Check the product input/output specifications when using any example of wiring. - Products only for sink input and products both for sink input and for source input are available. • The examples of programming (applied instructions) are given based on the allocation of the input/output numbers for wiring. → For the applied instructions, refer to the Programming Manual.

154

Page 161

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

Digital Switch [DSW Instructions (FNC72)/BIN Instructions (FNC19)]

13.2.1 When DSW instructions are used Examples of wiring for capturing values from a 4-digit digital switch to the data register D100 are given below.

Example of program M8000

X010

Y010

D100

13

K1

1) In the case of sink wiring When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit

101

102

103

0.1A 50V diode is necessary.

15 Input/Output Powered Extension Units

1 2 4 8 S/S X010 X011 X012 X013

16

Main unit (Ex: FX3G-40MT/ES)

Input/Output Extension Blocks

0V

14 Test Run, Maintenance, Troubleshooting

100

Wiring for Various Uses

Example of wiring

Digital switch of BCD

12 Output Wiring

1. Main unit

DSW

11 High-Speed Counters

13.2

13.2 Digital Switch [DSW Instructions (FNC72)/BIN

24V COM4 Y010 Y011 Y012 Y013 100 101 102 103

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

155

Page 162

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.2 Digital Switch [DSW Instructions (FNC72)/BIN

2. Main unit + input/output powered extension unit/block Example of program M8000

DSW

X010

Y030

D100

K1

Example of wiring 1) In the case of sink wiring When the main unit and a transistor output (sink) type input/output powered extension unit/block are used

Digital switch of BCD

100

101

102

103

0.1A 50V diode is necessary. *1 1 2 4 8 S/S X010 X011 X012 X013

Input/output powered extension unit Output extension block Transistor output (sink)

Main unit 0V

*2 X

COM 24+

24V

COM1 Y030 Y031 Y032 Y033

100

101

102

103

*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line. *2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX 2N-32ET). Output extension blocks do not have the terminals.

3. Input/output powered extension unit Example of program M8000

DSW

X060

Y050

D100

K1

Example of wiring 1) In the case of sink wiring When inputs are used for sink only and outputs are the transistor sink type in the used input/output powered extension unit

Digital switch of BCD

100

101

102

103

0.1A 50V diode is necessary. 1 2 4 8 COM X060 X061 X062 X063 First input group Transistor output (sink) COM1 Y050 Y051 Y052 Y053

100

156

101

102

103

X064 X065 X066 X067 Input/output powered extension unit FX2N-32ET FX2N-48ET

Page 163

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.2 Digital Switch [DSW Instructions (FNC72)/BIN

11

Examples of wiring for capturing values from a 2-digit digital switch to the data register D102 are given below. Example of program M8000

BIN

K2X010

12

D102

1) In the case of sink wiring When inputs are used for both sink and source in the used main unit or input/output powered extension unit

14 Test Run, Maintenance, Troubleshooting

1 2 4 8 1 2 4 8 S/S X010 X011 X012 X013 X014 X015 X016 X017

Main unit,Input/output powered extension unit 0V

24V

15 Input/Output Powered Extension Units

2) In the case of sink wiring When inputs are used for sink only in the used input/output powered extension unit 100

13 Wiring for Various Uses

101

Output Wiring

Example of wiring

100

High-Speed Counters

13.2.2 When BIN instructions are used

101

16 Input/Output Extension Blocks

1 2 4 8 1 2 4 8 COM X010 X011 X012 X013 X014 X015 X016 X017

17

Input/output powered extension unit

100

0V

18 Other Extension Units and Options

S/S

101

Extension Power Supply Unit

3) In the case of source wiring When inputs are used for both sink and source in the used main unit or input/output powered extension unit

1 2 4 8 1 2 4 8 24V X010 X011 X012 X013 X014 X015 X016 X017

19 Display Module

Main unit, Input/output powered extension unit

20 Terminal Block

157

Page 164

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.3

13.3 Input Matrix [MTR Instructions (FNC 52)]

Input Matrix [MTR Instructions (FNC 52)] This section gives examples of wiring for capturing the ON/OFF status of 24 switches to M30 to M37, M40 to M47 and M50 to M57 using MTR instructions.

1. Main unit Example of program M8000

MTR

X020

Y010

M30

K3

Example of wiring

M57

M56

M55

M54

M53

M52

M51

0.1A 50V diode is necessary.

M50

1) In the case of sink wiring When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit

M47

M46

M45

M44

M43

M42

M41

M40

X021 X022 X023 X024 X025 X026 X027

M37

M36

M35

M34

M33

M32

M31

M30

X021 X022 X023 X024 X025 X026 X027

S/S X020 X021 X022 X023 X024 X025 X026 X027 Main unit (Ex: FX3G-40MT/ES) 0V

158

24V

COM4 Y010 Y011 Y012

Page 165

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.3 Input Matrix [MTR Instructions (FNC 52)]

11 High-Speed Counters

2. Main unit + input/output powered extension unit/block Example of program M8000

MTR

X020

Y050

M30

K3

12

Example of wiring

M57

M56

M55

M54

M53

M52

M51

M50

0.1A 50V diode is necessary.

13

M47

M46

M45

M44

M43

M42

M41

Wiring for Various Uses

M40

X021 X022 X023 X024 X025 X026 X027

M37

M36

M35

M34

M33

M32

M31

M30

X021 X022 X023 X024 X025 X026 X027

14

Main unit 24V

Transistor output (sink) COM1 Y050 Y051 Y052

15

*1 To use the input terminal (X) of the input/output powered extension unit, wire the terminal as shown by the dotted line. *2 The terminals in the shaded areas are provided on input/output powered extension units (ex.: FX2N -32ET). Output extension blocks do not have the terminals.

Example of program M8000

MTR

X060

Y050

M30

K3

17

Example of wiring

M57

M56

M55

M54

M53

M52

M51

X061 X062 X063 X064 X065 X066 X067

Other Extension Units and Options

M31

M50

18

19

M47 M37

M46 M36

M45 M35

M44 M34

M43 M33

M42 M32

M41

M40

X061 X062 X063 X064 X065 X066 X067

M30

Extension Power Supply Unit

1) In the case of sink wiring When inputs are used for sink only and outputs are the transistor sink type in the used input/output powered extension unit 0.1A 50V diode is necessary.

16 Input/Output Extension Blocks

3. Input/output powered extension unit

Input/Output Powered Extension Units

0V

*2 COM 24+ X Input/output powered extension unit/block

Test Run, Maintenance, Troubleshooting

*1 S/S X020 X021 X022 X023 X024 X025 X026 X027

Output Wiring

1) In the case of sink wiring When the main unit and a transistor output (sink) type input/output powered extension unit/block are used

Display Module

COM X060 X061 X062 X063 X064 X065 X066 X067 Input/output powered extension unit FX2N-32ET FX2N-48ET

20

Transistor output (sink)

Terminal Block

COM1 Y050 Y051 Y052 Y053 Y054 Y055 Y056 Y057

159

Page 166

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.4

13.4 Seven Segment with Latch [SEGL Instructions

Seven Segment with Latch [SEGL Instructions (FNC74)/BCD Instructions (FNC18)]

13.4.1 When SEGL instructions are used This subsection gives examples of wiring for displaying the current value of D100 on the 4-digit 7-segment display.

1. Main unit Example of program M8000

SEGL

D100

Y010

K1

Example of wiring 1) In the case of sink wiring When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit 7-segment display to be used for sink wiring (in the case of transistor output)

Main unit (Ex: FX3G-40MT/ES)

PLC

7-segment display +

Transistor output (sink) COM4 Y010

Y011

Y012

1

2

4

8

3

2

1 2 4 8

10

Y013 COM5 Y014

Y015

Y016

Y017

100

101

102

103

10

1

10

0

10

*

* Use a 7-segment display with a latch and a built-in BCD decoder.

160

Y

Signal

COM1

-

Internal circuit

Page 167

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.4 Seven Segment with Latch [SEGL Instructions

11 High-Speed Counters

2. Input/output powered extension unit Example of program M8000

SEGL

D100

Y020

K1

12

1) In the case of sink wiring When inputs are used for sink only and outputs are the transistor sink type in the used input/output powered extension unit

13

PLC

7-segment display +

Transistor output (sink) Y021

Y022

Y023

Y024

Y025

Y026

Y027

1

2

4

8

100

101

102

103

103

102

101

100

Y

Signal

COM1

-

14

Internal circuit

Test Run, Maintenance, Troubleshooting

COM1 Y020

*

15 Input/Output Powered Extension Units

1 2 4 8

Wiring for Various Uses

7-segment display to be used for sink wiring (in the case of transistor output)

Input/output powered extension unit FX2N-32ET FX2N-48ET

Output Wiring

Example of wiring

* Use a 7-segment display with a latch and a built-in BCD decoder.

16 Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

161

Page 168

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.4 Seven Segment with Latch [SEGL Instructions

13.4.2 When BCD instructions are used This subsection gives examples of wiring for displaying the current value of D100 on the 2-digit 7-segment display.

1. Main unit Example of program M8000

BCD

D100

K2Y010

Example of wiring 1) In the case of sink wiring When inputs are used for both sink and source and outputs are the transistor sink type in the used main unit 7-segment display to be used for sink wiring (in the case of transistor output)

Main unit (Ex: FX3G-40MT/ES)

PLC

7-segment display +

Transistor output (sink) COM4 Y010

Y011

Y012

1

2

4

Y013 COM5 Y014 8

1248

162

1

1248

Y015

Y016

Y017

2

4

8

Y

Signal

COM1

-

Internal circuit

Page 169

FX3G Series Programmable Controllers

13 Examples of Wiring for Various Uses

User's Manual - Hardware Edition

13.4 Seven Segment with Latch [SEGL Instructions

11 High-Speed Counters

2. Input/output powered extension unit Example of program M8000

BCD

D100

K2Y020

12

1) In the case of sink wiring When inputs are used for sink only and outputs are the transistor sink type in the used input/output powered extension unit

13

PLC

Wiring for Various Uses

7-segment display to be used for sink wiring (in the case of transistor output)

Input/output powered extension unit FX2N-32ET FX2N-48ET

7-segment display +

Transistor output (sink) Y021

Y022

Y023

Y024

Y025

Y026

Y027

1

2

4

8

1

2

4

8

1248

Y

Signal

COM1

-

14

Internal circuit

Test Run, Maintenance, Troubleshooting

COM1 Y020

Output Wiring

Example of wiring