Page 236
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.7 FX2N-8EX-UA1/UL (100V AC Input)
16.7.2 Parts identification and terminal arrangement With cover
Without cover X0 X2
COM1 X1 X3
Rear line extension connector
Input indicator lamps (LED lamps)
X5 X7 X4 X6
16.7.3 External dimensions
43(1.7")
230
Unit:mm (inches)
90(3.55")
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
Page 237
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
11
FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
High-Speed Counters
16.8
16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
16.8.1 Product specifications
1. Power supply specifications Item
FX2N-8EYR-ES/UL
13
FX2N-16EYR-ES/UL FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Wiring for Various Uses
Product type
2. Weight and Other specifications (External dimensions are described later.) Item MASS (Weight) Other
FX2N-16EYR-ES/UL
0.2kg (0.44lbs)
0.3kg (0.66lbs)
14
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Test Run, Maintenance, Troubleshooting
• • •
FX2N-8EYR-ES/UL
3. Output specifications (Relay output type) Item Output Points
FX2N-16EYR-ES/UL
8 points
16 points Vertical terminal block (M3 screws)
Output type
Relay
External power supply
30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
Output circuit insulation Indication of output operation
Max. load Inductive load
Mechanical insulation
16
Supplying power to the relay coil will light the LED indicator lamp on panel.
Input/Output Extension Blocks
Resistance load
2A/point The total resistance load current per common should be as follows: • 4 output points/common: 8A or less • 8 output points/common: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3. -
Min. load
5V DC, 2mA (reference values) OFF ON
Approx. 10ms
ON OFF
Approx. 10ms
18
Load
Other Extension Units and Options
Y Fuse COM Output circuit configuration
DC power supply unit Y
19
Fuse
Display Module
COM AC power supply unit A common number applies to the
17 Extension Power Supply Unit
Open circuit leakage current
Response time
15 Input/Output Powered Extension Units
Connection type
FX2N-8EYR-ES/UL
12 Output Wiring
The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.
of [COM ].
20 Terminal Block
231
Page 238
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
16.8.2 Parts identification and terminal arrangement FX2N-8EYR-ES/UL With cover
Without cover
Y0 Y2
COM1 Y1 Y3
Rear line extension connector
Output indicator lamps (LED lamps)
Y4 Y6
COM2 Y5 Y7
FX2N-16EYR-ES/UL When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.
Output indicator lamps (LED lamps) Rear line extension connector Output indicator lamps (LED lamps)
232
Y0 Y2 Y4 Y2 Y4 Y6 COM2 COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Without cover
With cover
Lower numbers
Higher numbers
Page 239
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.8 FX2N-8EYR-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
11 High-Speed Counters
16.8.3 External dimensions FX2N-8EYR-ES/UL
12
Unit:mm (inches)
90(3.55")
Output Wiring
13 Wiring for Various Uses
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
43(1.7")
14
90(3.55")
15
16
9(0.36") 87(3.43")
Input/Output Extension Blocks
40(1.58")
Unit:mm (inches)
Input/Output Powered Extension Units
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
Test Run, Maintenance, Troubleshooting
FX2N-16EYR-ES/UL
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
233
Page 240
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16.9
16 Input/Output Extension Blocks 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
16.9.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.
1. Power supply specifications Item
FX2N-8EYT-ESS/UL
FX2N-16EYT-ESS/UL
Product type
FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
2. Weight and Other specifications (External dimensions are described later.) Item MASS (Weight) • • •
Other
FX2N-8EYT-ESS/UL
FX2N-16EYT-ESS/UL
0.2kg (0.44lbs)
0.3kg (0.66lbs)
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Output specifications (Transistor output type) Item Output Points
FX2N-8EYT-ESS/UL
FX2N-16EYT-ESS/UL
8 points
16 points
Connection type
Vertical terminal block (M3 screws)
Output unit/type
Transistor/source output
External power supply
5 to 30V DC
Output circuit insulation
Photo-coupler insulation
Indication of output operation
Max. load
Resistance load
Activation of the photo-coupler will light the LED indicator lamp on panel. 0.5A/point The total load current per common should be as follows: • 4 output points/common: 0.8A or less • 8 output points/common: 1.6A or less
Inductive load
12W/24V DC
Open circuit leakage current
0.1mA/30V DC
Min. load Response time
OFF ON
0.2ms or less for 200mA (at 24V DC)
ON OFF
0.2ms or less for 200mA (at 24V DC)
Load Y Output circuit configuration
Fuse +V DC power supply A common number applies to the
234 of [+V ].
Page 241
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16 Input/Output Extension Blocks 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
11 High-Speed Counters
16.9.2 Parts identification and terminal arrangement FX2N-8EYT-ESS/UL With cover
12
Without cover
Output Wiring
Y0 Y2
+V0 Y1 Y3
Rear line extension connector
Output indicator lamps (LED lamps)
13 Wiring for Various Uses Test Run, Maintenance, Troubleshooting
Y4 Y6
+V1 Y5 Y7
14
Without cover
With cover
Output indicator lamps (LED lamps)
16 Input/Output Extension Blocks
Rear line extension connector
Lower numbers
17 Extension Power Supply Unit
Higher numbers
18 Other Extension Units and Options
Y0 Y2 Y4 Y2 Y4 Y6 +V1 +V0 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Output indicator lamps (LED lamps)
15 Input/Output Powered Extension Units
FX2N-16EYT-ESS/UL When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.
19 Display Module
20 Terminal Block
235
Page 242
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16 Input/Output Extension Blocks 16.9 FX2N-8EYT-ESS/UL, FX2N-16EYT-ESS/UL (Transistor Output)
16.9.3 External dimensions FX2N-8EYT-ESS/UL Unit:mm (inches)
90(3.55")
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
43(1.7")
FX2N-16EYT-ESS/UL
40(1.58")
236
Unit:mm (inches)
90(3.55")
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
Page 243
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)
11 High-Speed Counters
16.10 FX2N-8EYR, FX2N-16EYR (Relay Output) 16.10.1 Product specifications
1. Power supply specifications Item
FX2N-8EYR
13
FX2N-16EYR FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Wiring for Various Uses
Product type
2. Weight and Other specifications (External dimensions are described later.) Item MASS (Weight) Other
FX2N-16EYR 0.3kg (0.66lbs)
14
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Test Run, Maintenance, Troubleshooting
• • •
FX2N-8EYR 0.2kg (0.44lbs)
3. Output specifications (Relay output type) Item Output Points
FX2N-16EYR
8 points
16 points Vertical terminal block (M3 screws)
Output type
Relay
External power supply
250V AC 30V DC or less
Output circuit insulation Indication of output operation
Max. load Inductive load
Mechanical insulation
16
Supplying power to the relay coil will light the LED indicator lamp on panel. 2A/point The total resistance load current per common should be as follows: • 4 output points/common: 8A or less • 8 output points/common: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.
Open circuit leakage current
5V DC, 2mA (reference values)
OFF ON
Approx. 10ms
ON OFF
Approx. 10ms
Load
18
Y
Other Extension Units and Options
Fuse COM Output circuit configuration
DC power supply Load
Y
19
Fuse
Display Module
COM AC power supply A common number applies to the
17 Extension Power Supply Unit
Min. load
Input/Output Extension Blocks
Resistance load
Response time
15 Input/Output Powered Extension Units
Connection type
FX2N-8EYR
12 Output Wiring
The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.
of [COM ].
20 Terminal Block
237
Page 244
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)
16.10.2 Parts identification and terminal arrangement FX2N-8EYR With cover
Without cover
Y0 Y2
COM1 Y1 Y3
Rear line extension connector
Output indicator lamps (LED lamps)
Y4 Y6
COM2 Y5 Y7
FX2N-16EYR When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.
Output indicator lamps (LED lamps) Rear line extension connector Output indicator lamps (LED lamps)
238
Y0 Y2 Y4 Y2 Y4 Y6 COM2 COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Without cover
With cover
Lower numbers
Higher numbers
Page 245
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.10 FX2N-8EYR, FX2N-16EYR (Relay Output)
11 High-Speed Counters
16.10.3 External dimensions FX2N-8EYR Unit:mm (inches)
12
90(3.55")
Output Wiring
13 Wiring for Various Uses
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
43(1.7")
14
FX2N-16EYR
15
90(3.55")
80(3.15") (mounting hole pitch)
Unit:mm (inches)
Input/Output Powered Extension Units
40(1.58")
Test Run, Maintenance, Troubleshooting
2- 4.5 mounting holes
16
9(0.36") 87(3.43")
Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
239