The text of a manual · part 31 of 49
FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 16. Input/Output Extension Blocks, pages 246 to 253
Pages 246 to 253 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]
The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Mitsubishi FX-16EYR
Page 246
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)
16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output) 16.11.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.
1. Power supply specifications Item
FX2N-8EYT
Product type
FX2N-16EYT
FX2N-16EYT-C
FX2N extension block
Rated voltage
FX2N connector type extension block
24V DC (supplied from main unit and input/output powered extension unit)
2. Weight and Other specifications (External dimensions are described later.) Item
FX2N-8EYT
MASS (Weight)
FX2N-16EYT
FX2N-16EYT-C
0.2kg (0.44lbs) • • •
Other
0.3kg (0.66lbs)
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Output specifications (Transistor output type) Item
FX2N-8EYT
FX2N-16EYT
Output Points
8 points
Connection type
Vertical terminal block (M3 screws)
FX2N-16EYT-C 16 points
Output unit/type
Connector terminal block
Transistor/sink output
External power supply
5 to 30V DC
Output circuit insulation
Photo-coupler insulation
Indication of output operation
Max. load
Resistance load
Activation of the photo-coupler will light the LED indicator lamp on panel. 0.5A/point 0.3A/point The total load current per common should be The total load current per common should be as follows: as follows: • 4 output points/common: 0.8A or less • 16 output points/common: 1.6A or less • 8 output points/common: 1.6A or less
Inductive load
12W/24V DC
Open circuit leakage current Min. load Response time
7.2 W/24V DC 0.1mA/30V DC -
OFF ON
0.2ms or less for 200mA (at 24V DC)
ON OFF
0.2ms or less for 200mA (at 24V DC)
Load
Load Y
Fuse Output circuit configuration
DC power supply unit
COM1 Y
Fuse
240
DC power supply unit
COM Y
Fuse COM2
DC power supply unit
Y Fuse
DC power supply unit
COM
Page 247
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16 Input/Output Extension Blocks 16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)
11 High-Speed Counters
16.11.2 Parts identification and terminal arrangement FX2N-8EYT With cover
12
Without cover
Output Wiring
Y0 Y2
COM1 Y1 Y3
Rear line extension connector
Output indicator lamps (LED lamps)
13 Wiring for Various Uses Test Run, Maintenance, Troubleshooting
Y4 Y6
COM2 Y5 Y7
14
Output indicator lamps (LED lamps)
Output indicator lamps (LED lamps)
16 Input/Output Extension Blocks
Rear line extension connector
Lower numbers
17 Extension Power Supply Unit
Higher numbers
18 Other Extension Units and Options
Y0 Y2 Y4 Y2 Y4 Y6 COM2 COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Without cover
With cover
15 Input/Output Powered Extension Units
FX2N-16EYT When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.
19 Display Module
20 Terminal Block
241
Page 248
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16 Input/Output Extension Blocks 16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)
FX2N-16EYT-C When an output (Y) number is assigned, 8 points on side A will be used for the lower output numbers, and 8 points on side B will be used for the higher output numbers. Without cover
With cover Output indicator lamps (LED lamps)
Connector type Rear line extension connector
Output indicator lamps (LED lamps)
Terminal arrangement
16.11.3 External dimensions FX2N-8EYT Unit:mm (inches)
90(3.55")
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
43(1.7")
FX2N-16EYT
40(1.58")
242
Unit:mm (inches)
90(3.55")
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
Side No. No. Side A B Y0 1 11 Y0 Y1 2 12 Y1 Y2 3 13 Y2 Y3 4 14 Y3 Y4 5 15 Y4 Y5 6 16 Y5 Y6 7 17 Y6 Y7 8 18 Y7 COM 9 19 COM 10 20
Page 249
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)
11 Unit:mm (inches)
90(3.55")
12 Output Wiring
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
High-Speed Counters
FX2N-16EYT-C
13
40(1.58")
Wiring for Various Uses
9(0.36") 87(3.43")
How to connect connector (FX2N-16EYT-C)
20
9
Side B Side A
8
7
6
5
4
3
2
1
15
19 17 15 13 11 20 18 16 14 12
10
16
9
8
7
6
5
4
3
2
20
1
Input/Output Extension Blocks
A 10
FX-16ECAB type cable
Input/Output Powered Extension Units
Cross section of 20-core flat cable (Be sure to check the wire number.)
Test Run, Maintenance, Troubleshooting
Connection face of connector The polarity is shown in the following table.
19 17 15 13 11 B 20 18 16 14 12
14
(Socket)
Side B is for the higher input numbers, COM Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0 and side A is for the lower input numbers. COM Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0 (Exe.) Side B X050 to X057 Side A X040 to X047
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
243
Page 250
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.12 FX2N-8EYT-H (Transistor Output)
16.12 FX2N-8EYT-H (Transistor Output) 16.12.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.
1. Power supply specifications Item
FX2N-8EYT-H
Product type
FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
2. Weight and Other specifications (External dimensions are described later.) Item
FX2N-8EYT-H
MASS (Weight)
0.2kg (0.44lbs) • • •
Other
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Output specifications (Transistor output type) Item
FX2N-8EYT-H
Output Points
8 points
Connection type
Vertical terminal block (M3 screws)
Output unit/type
Transistor/sink output
External power supply
5 to 30V DC
Output circuit insulation
Photo-coupler insulation
Indication of output operation
Max. load
Resistance load
Activation of the photo-coupler will light the LED indicator lamp on panel. 1A/point The total load current per common should be as follows: • 4 output points/common: 2A or less
Inductive load
24W/24V DC
Open circuit leakage current
0.1mA/30V DC
Min. load Response time
OFF ON
0.2ms or less/1A
ON OFF
0.4ms or less/1A
Load Y Fuse Output circuit configuration
DC power supply unit
COM1 Y
Fuse COM2 DC power supply unit
244
Page 251
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.12 FX2N-8EYT-H (Transistor Output)
11
With cover
High-Speed Counters
16.12.2 Parts identification and terminal arrangement Without cover
Output Wiring
Y0 Y2
COM1 Y1 Y3
Rear line extension connector
Output indicator lamps (LED lamps)
12
13 Wiring for Various Uses
Y4 Y6
COM2 Y5 Y7
14 Test Run, Maintenance, Troubleshooting
16.12.3 External dimensions
16
90(3.55")
80(3.15") (mounting hole pitch)
Unit:mm (inches)
Input/Output Extension Blocks
43(1.7")
Input/Output Powered Extension Units
2- 4.5 mounting holes
15
17
9(0.36") 87(3.43")
Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
245
Page 252
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.13 FX2N-16EYS (Triac Output: 16 Points)
16.13 FX2N-16EYS (Triac Output: 16 Points) 16.13.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.
1. Power supply specifications Item
FX2N-16EYS
Product type
FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
2. Weight and Other specifications (External dimensions are described later.) Item
FX2N-16EYS
MASS (Weight)
0.3kg (0.66lbs) • • •
Other
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Output specifications (Triac output type) Item
FX2N-16EYS
Output Points
16 points
Connection type
Vertical terminal block (M3 screws)
Output type
Triac output (SSR)
External power supply
85 to 242V AC
Output circuit insulation
Photo-coupler insulation
Indication of output operation
Max. load
Resistance load
Activation of the photo-thyristor will light the LED indicator lamp on panel. 0.3A/point The total load current per common should be as follows: • 8 output points/common: 0.8A or less
Inductive load
15VA/100V AC, 30VA/200V AC
Open circuit leakage current
1mA/100V AC, 2mA/200V AC
Min. load
0.4VA/100V AC, 1.6VA/200V AC
Response time
OFF ON
1ms or less
ON OFF
10ms or less
Load Y Output circuit configuration
Fuse
U
COM AC power supply A common number applies to the
246 of [COM ].
Page 253
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.13 FX2N-16EYS (Triac Output: 16 Points)
11
When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.
Rear line extension connector
Lower numbers
13 Wiring for Various Uses
Output indicator lamps (LED lamps)
12 Output Wiring
Output indicator lamps (LED lamps)
14
Higher numbers
Test Run, Maintenance, Troubleshooting
Y0 Y2 Y4 Y2 Y4 Y6 COM2 COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7
Without cover
With cover
High-Speed Counters
16.13.2 Parts identification and terminal arrangement
15
16 90(3.55")
17 Extension Power Supply Unit
40(1.58")
Unit:mm (inches)
Input/Output Extension Blocks
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
Input/Output Powered Extension Units
16.13.3 External dimensions
9(0.36") 87(3.43")
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
247