Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 31 of 49

FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 16. Input/Output Extension Blocks, pages 246 to 253

Pages 246 to 253 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 246

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)

16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output) 16.11.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.

1. Power supply specifications Item

FX2N-8EYT

Product type

FX2N-16EYT

FX2N-16EYT-C

FX2N extension block

Rated voltage

FX2N connector type extension block

24V DC (supplied from main unit and input/output powered extension unit)

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-8EYT

MASS (Weight)

FX2N-16EYT

FX2N-16EYT-C

0.2kg (0.44lbs) • • •

Other

0.3kg (0.66lbs)

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Output specifications (Transistor output type) Item

FX2N-8EYT

FX2N-16EYT

Output Points

8 points

Connection type

Vertical terminal block (M3 screws)

FX2N-16EYT-C 16 points

Output unit/type

Connector terminal block

Transistor/sink output

External power supply

5 to 30V DC

Output circuit insulation

Photo-coupler insulation

Indication of output operation

Max. load

Resistance load

Activation of the photo-coupler will light the LED indicator lamp on panel. 0.5A/point 0.3A/point The total load current per common should be The total load current per common should be as follows: as follows: • 4 output points/common: 0.8A or less • 16 output points/common: 1.6A or less • 8 output points/common: 1.6A or less

Inductive load

12W/24V DC

Open circuit leakage current Min. load Response time

7.2 W/24V DC 0.1mA/30V DC -

OFF ON

0.2ms or less for 200mA (at 24V DC)

ON OFF

0.2ms or less for 200mA (at 24V DC)

Load

Load Y

Fuse Output circuit configuration

DC power supply unit

COM1 Y

Fuse

240

DC power supply unit

COM Y

Fuse COM2

DC power supply unit

Y Fuse

DC power supply unit

COM

Page 247

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16 Input/Output Extension Blocks 16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)

11 High-Speed Counters

16.11.2 Parts identification and terminal arrangement FX2N-8EYT With cover

12

Without cover

Output Wiring

Y0 Y2

COM1 Y1 Y3

Rear line extension connector

Output indicator lamps (LED lamps)

13 Wiring for Various Uses Test Run, Maintenance, Troubleshooting

Y4 Y6

COM2 Y5 Y7

14

Output indicator lamps (LED lamps)

Output indicator lamps (LED lamps)

16 Input/Output Extension Blocks

Rear line extension connector

Lower numbers

17 Extension Power Supply Unit

Higher numbers

18 Other Extension Units and Options

Y0 Y2 Y4 Y2 Y4 Y6 COM2 COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7

Without cover

With cover

15 Input/Output Powered Extension Units

FX2N-16EYT When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.

19 Display Module

20 Terminal Block

241

Page 248

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16 Input/Output Extension Blocks 16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)

FX2N-16EYT-C When an output (Y) number is assigned, 8 points on side A will be used for the lower output numbers, and 8 points on side B will be used for the higher output numbers. Without cover

With cover Output indicator lamps (LED lamps)

Connector type Rear line extension connector

Output indicator lamps (LED lamps)

Terminal arrangement

16.11.3 External dimensions FX2N-8EYT Unit:mm (inches)

90(3.55")

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

9(0.36") 87(3.43")

43(1.7")

FX2N-16EYT

40(1.58")

242

Unit:mm (inches)

90(3.55")

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

9(0.36") 87(3.43")

Side No. No. Side A B Y0 1 11 Y0 Y1 2 12 Y1 Y2 3 13 Y2 Y3 4 14 Y3 Y4 5 15 Y4 Y5 6 16 Y5 Y6 7 17 Y6 Y7 8 18 Y7 COM 9 19 COM 10 20

Page 249

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)

11 Unit:mm (inches)

90(3.55")

12 Output Wiring

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

High-Speed Counters

FX2N-16EYT-C

13

40(1.58")

Wiring for Various Uses

9(0.36") 87(3.43")

How to connect connector (FX2N-16EYT-C)

20

9

Side B Side A

8

7

6

5

4

3

2

1

15

19 17 15 13 11 20 18 16 14 12

10

16

9

8

7

6

5

4

3

2

20

1

Input/Output Extension Blocks

A 10

FX-16ECAB type cable

Input/Output Powered Extension Units

Cross section of 20-core flat cable (Be sure to check the wire number.)

Test Run, Maintenance, Troubleshooting

Connection face of connector The polarity is shown in the following table.

19 17 15 13 11 B 20 18 16 14 12

14

(Socket)

Side B is for the higher input numbers, COM Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0 and side A is for the lower input numbers. COM Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0 (Exe.) Side B X050 to X057 Side A X040 to X047

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

243

Page 250

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.12 FX2N-8EYT-H (Transistor Output)

16.12 FX2N-8EYT-H (Transistor Output) 16.12.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.

1. Power supply specifications Item

FX2N-8EYT-H

Product type

FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-8EYT-H

MASS (Weight)

0.2kg (0.44lbs) • • •

Other

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Output specifications (Transistor output type) Item

FX2N-8EYT-H

Output Points

8 points

Connection type

Vertical terminal block (M3 screws)

Output unit/type

Transistor/sink output

External power supply

5 to 30V DC

Output circuit insulation

Photo-coupler insulation

Indication of output operation

Max. load

Resistance load

Activation of the photo-coupler will light the LED indicator lamp on panel. 1A/point The total load current per common should be as follows: • 4 output points/common: 2A or less

Inductive load

24W/24V DC

Open circuit leakage current

0.1mA/30V DC

Min. load Response time

OFF ON

0.2ms or less/1A

ON OFF

0.4ms or less/1A

Load Y Fuse Output circuit configuration

DC power supply unit

COM1 Y

Fuse COM2 DC power supply unit

244

Page 251

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.12 FX2N-8EYT-H (Transistor Output)

11

With cover

High-Speed Counters

16.12.2 Parts identification and terminal arrangement Without cover

Output Wiring

Y0 Y2

COM1 Y1 Y3

Rear line extension connector

Output indicator lamps (LED lamps)

12

13 Wiring for Various Uses

Y4 Y6

COM2 Y5 Y7

14 Test Run, Maintenance, Troubleshooting

16.12.3 External dimensions

16

90(3.55")

80(3.15") (mounting hole pitch)

Unit:mm (inches)

Input/Output Extension Blocks

43(1.7")

Input/Output Powered Extension Units

2- 4.5 mounting holes

15

17

9(0.36") 87(3.43")

Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

245

Page 252

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.13 FX2N-16EYS (Triac Output: 16 Points)

16.13 FX2N-16EYS (Triac Output: 16 Points) 16.13.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 12 for output wiring.

1. Power supply specifications Item

FX2N-16EYS

Product type

FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-16EYS

MASS (Weight)

0.3kg (0.66lbs) • • •

Other

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Output specifications (Triac output type) Item

FX2N-16EYS

Output Points

16 points

Connection type

Vertical terminal block (M3 screws)

Output type

Triac output (SSR)

External power supply

85 to 242V AC

Output circuit insulation

Photo-coupler insulation

Indication of output operation

Max. load

Resistance load

Activation of the photo-thyristor will light the LED indicator lamp on panel. 0.3A/point The total load current per common should be as follows: • 8 output points/common: 0.8A or less

Inductive load

15VA/100V AC, 30VA/200V AC

Open circuit leakage current

1mA/100V AC, 2mA/200V AC

Min. load

0.4VA/100V AC, 1.6VA/200V AC

Response time

OFF ON

1ms or less

ON OFF

10ms or less

Load Y Output circuit configuration

Fuse

U

COM AC power supply A common number applies to the

246 of [COM ].

Page 253

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.13 FX2N-16EYS (Triac Output: 16 Points)

11

When an output (Y) number is assigned, 8 points on the upper side will be used for the lower output numbers, and 8 points on the lower side will be used for the higher output numbers.

Rear line extension connector

Lower numbers

13 Wiring for Various Uses

Output indicator lamps (LED lamps)

12 Output Wiring

Output indicator lamps (LED lamps)

14

Higher numbers

Test Run, Maintenance, Troubleshooting

Y0 Y2 Y4 Y2 Y4 Y6 COM2 COM1 Y1 Y3 Y5 Y6 Y7 Y0 Y1 Y3 Y5 Y7

Without cover

With cover

High-Speed Counters

16.13.2 Parts identification and terminal arrangement

15

16 90(3.55")

17 Extension Power Supply Unit

40(1.58")

Unit:mm (inches)

Input/Output Extension Blocks

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

Input/Output Powered Extension Units

16.13.3 External dimensions

9(0.36") 87(3.43")

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

247