17 Extension Power Supply Unit 17.1 Outline
17. Extension Power Supply Unit
DESIGN PRECAUTIONS •
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS •
17.1
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions.
Outline When the internal power supplied from the FX3G Series PLC is insufficient for powering output extension blocks or special function blocks, the FX3U-1PSU-5V (extension power supply unit) is available. Only one FX3U-1PSU-5V unit may be connected to a FX3G PLC system. Connect extension equipment to the FX 3U -1PSU-5V according to the configuration specification limits described in Subsection 17.2.2. → For the system configuration with FX3U-1PSU-5V, refer to Chapter 6. → For the mounting, refer to Chapter 8. → For the wiring, refer to Chapter 9.
248
Page 255
FX3G Series Programmable Controllers
17 Extension Power Supply Unit
User's Manual - Hardware Edition
11
Specifications
High-Speed Counters
17.2
17.2 Specifications
17.2.1 Generic Specifications
17.2.2 Performance Specifications Items
13
Specifications
Allowable supply voltage range
85-264V AC
Rated frequency
50/60Hz
Allowable instantaneous power failure time
The allowable momentary power failure time depends on the power supply used. • 100V AC power supply system: The operation is continued to the momentary power failure for 10 or less ms. • 200V AC power supply system: The operation is continued to the momentary power failure for 100 or less ms. 30A max. 5ms or less/100V AC, 65A max. 5ms or less/200V AC
Power consumption
20W Max.
Output current (Internal for supply)
*1.
24V DC
0.3A*1
5V DC
1A*1
15
The output current depends on the ambient temperature as shown in the dirating curve below.
Input/Output Powered Extension Units
Derating curve Output current [A] 5V DC 1.0 0.8
16
24V DC
Input/Output Extension Blocks
0.3 0.2 0
40 55 Ambient temperature [°C]
17.2.3 External Dimensions
17 Extension Power Supply Unit
Unit:mm (inches)
80(3.15") (mouning hole pitch) 90(3.55")
2- 4.5 mounting holes
19
9(0.36")
Display Module
55(2.17")
18 Other Extension Units and Options
4(0.16")
14 Test Run, Maintenance, Troubleshooting
100-240V AC
Wiring for Various Uses
Supply voltage
Rush current
12 Output Wiring
The generic specifications are the same as those for the main unit. → For the generic specifications, refer to Section 4.1.
87(3.43")
20 Terminal Block
249
Page 256
FX3G Series Programmable Controllers User's Manual - Hardware Edition
17.3
17 Extension Power Supply Unit 17.3 Extension Power Supply Unit Related Precaution
Extension Power Supply Unit Related Precaution 1. The power is supplied as follows when the input extension block (including the FX2N-8ERES/UL and FX2N-8ER) is used on the downstream side of the extension power supply unit. • When the main unit is located on the upstream side of the extension power supply unit The power is supplied from the main unit. → For details, refer to Chapter 6 • When the input/output powered extension unit is located on the upstream side of the extension power supply unit The power is supplied from the 24V DC service power supply of the input/output powered extension unit. → For details, refer to Chapter 6
2. Grounding and power cables should be positioned to exit the unit from above. → For details, refer to Subsection 9.4.4 and Subsection 9.4.5.