Page 226

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16 Input/Output Extension Blocks 16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)

16.4.2 Parts identification and terminal arrangement FX2N-8EX-ES/UL With cover

Without cover

Input indicator lamps (LED lamps)

S/S X1 X3 X0 X2

Rear line extension connector

X5 X7 X4 X6

FX2N-16EX-ES/UL When an input (X) number is assigned, 8 points on the upper side will be used for the lower input numbers, and 8 points on the lower side will be used for the higher input numbers. Without cover

With cover

Rear line extension connector Input indicator lamps (LED lamps)

220

X0 X2 X4 X2 X4 X6 S/S X1 X3 X5 X6 X7 X0 X1 X3 X5 X7

Input indicator lamps (LED lamps)

Lower numbers

Higher numbers

Page 227

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16 Input/Output Extension Blocks 16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)

11 High-Speed Counters

16.4.3 External dimensions FX2N-8EX-ES/UL

12

Unit:mm (inches)

90(3.55")

Output Wiring

13 Wiring for Various Uses

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

9(0.36") 87(3.43")

43(1.7")

14

90(3.55")

15

16

9(0.36") 87(3.43")

Input/Output Extension Blocks

40(1.58")

Unit:mm (inches)

Input/Output Powered Extension Units

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

Test Run, Maintenance, Troubleshooting

FX2N-16EX-ES/UL

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

221

Page 228

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.5

16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C

FX2N-8EX, FX2N-16EX and FX2N-16EX-C

16.5.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring.

1. Power supply specifications Item

FX2N-8EX

Product type

FX2N-16EX

FX2N-16EX-C FX2N connector type extension block

FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-8EX

MASS (Weight)

FX2N-16EX

FX2N-16EX-C

0.2kg (0.44lbs) • • •

Other

0.3kg (0.66lbs)

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Input specifications Item

FX2N-8EX

FX2N-16EX

Input points

8 points

Connection type

Vertical terminal block (M3 screws)

FX2N-16EX-C 16 points

Input form

FX2N connector type extension block

Sink

Input signal voltage

24V DC

Input signal current

5mA/24V DC

Input impedance ON input sensitivity current

10%

4.3k Input ON current

3.5mA or more at 24V DC

Input OFF current

1.5mA or less

Input response time

Approx. 10ms

Input signal form

No-voltage contact input NPN open collector transistor

Input circuit insulation Indication of input operation

Photo-coupler insulation LED on panel lights when input.

Sink input wiring Main unit

S/S 0V 24V

Input circuit diagram

24+

4.3k

222

X

Page 229

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C

11 High-Speed Counters

16.5.2 Parts identification and terminal arrangement FX2N-8EX With cover

12

Without cover

Output Wiring

24+ X1 X3 X0 X2

Rear line extension connector

Input indicator lamps (LED lamps)

13 Wiring for Various Uses Test Run, Maintenance, Troubleshooting

X5 X7 X4 X6

14

Without cover

With cover

Input indicator lamps (LED lamps)

16 Input/Output Extension Blocks

Rear line extension connector

X0 X2 X4 X2 X4 X6 24+ X1 X3 X5 X6 X7 X0 X1 X3 X5 X7

Input indicator lamps (LED lamps)

15 Input/Output Powered Extension Units

FX2N-16EX When an input (X) number is assigned, 8 points on the upper side will be used for the lower input numbers, and 8 points on the lower side will be used for the higher input numbers.

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

223

Page 230

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C

FX2N-16EX-C When an input (X) number is assigned, 8 points on side A will be used for the lower input numbers, and 8 points on side B will be used for the higher input numbers. Without cover

With cover Input indicator lamps (LED lamps)

Connector type Rear line extension connector

Input indicator lamps (LED lamps)

Terminal arrangement

16.5.3 External dimensions FX2N-8EX Unit:mm (inches)

90(3.55")

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

9(0.36") 87(3.43")

43(1.7")

FX2N-16EX

40(1.58")

224

Unit:mm (inches)

90(3.55")

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

9(0.36") 87(3.43")

Side No. No. Side A B X0 1 11 X0 X1 2 12 X1 X2 3 13 X2 X3 4 14 X3 X4 5 15 X4 X5 6 16 X5 X6 7 17 X6 X7 8 18 X7 9 19 24+ 10 20 24+

Page 231

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.5 FX2N-8EX, FX2N-16EX and FX2N-16EX-C

11 Unit:mm (inches)

90(3.55")

12 Output Wiring

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

High-Speed Counters

FX2N-16EX-C

13 Wiring for Various Uses

9(0.36") 87(3.43")

40(1.58")

How to connect connector (FX2N-16EX-C) (Socket)

Connection face of connector The polarity is shown in the following table.

14

Cross section of 20-core flat cable (Be sure to check the wire number.)

A 10

9

8

7

6

5

4

3

2

15

20

19 17 15 13 11 20 18 16 14 12

10 1

FX-16ECAB type cable

Input/Output Powered Extension Units

19 17 15 13 11 B 20 18 16 14 12

Test Run, Maintenance, Troubleshooting

20

9

8

7

6

5

4

3

2

1

16 Input/Output Extension Blocks

Side B 24+ Side A 24+

X7 X6 X5 X4 X3 X2 X1 X0 X7 X6 X5 X4 X3 X2 X1 X0

Side B is for the higher input numbers, and side A is for the lower input numbers. (Exe.) Side B X050 to X057 Side A X040 to X047

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

225

Page 232

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.6

16.6 FX2N-16EXL-C (5V DC Input: 16 Points)

FX2N-16EXL-C (5V DC Input: 16 Points)

16.6.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications.

1. Power supply specifications Item

FX2N-16EXL-C

Product type

FX2N connector type extension block for each application

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-16EXL-C

MASS (Weight)

0.3kg (0.66lbs) • • •

Other

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Input specifications Item

FX2N-16EXL-C

Input points

16 points

Connection type

Connector terminal block

Input form

TTL level

Input signal voltage

5V DC

Input signal current

5%

40mA (at 5V DC), maximum

Input impedance

2.2k

ON input sensitivity current

ON(Low) OFF(High)

0.4mA or less

Input sensing voltage

ON(Low)

1.5V DC or less

OFF(High)

3.5V DC or more

OFF ON (High Low)

1ms +1 ms, -0.5 ms

ON OFF (Low High)

1ms +1 ms, -0.5 ms

Input response time Input signal form

Input circuit insulation Indication of input operation

1mA or more

TTL input Photo-coupler insulation LED on panel lights when input.

External unit 5V DC 5+ Input circuit diagram

X 2.2k

226

TTL

Page 233

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.6 FX2N-16EXL-C (5V DC Input: 16 Points)

11

When an input (X) number is assigned, 8 points on side A will be used for the lower input numbers, and 8 points on side B will be used for the higher input numbers. With cover

Without cover Connector type Rear line extension connector

Terminal arrangement

13 Wiring for Various Uses

Input indicator lamps (LED lamps)

12

Side No. No. Side A B X0 1 11 X0 X1 2 12 X1 X2 3 13 X2 X3 4 14 X3 X4 5 15 X4 X5 6 16 X5 X6 7 17 X6 X7 8 18 X7 9 19 5+ 10 20 5+

Output Wiring

Input indicator lamps (LED lamps)

14 Unit:mm (inches)

90(3.55")

15 Input/Output Powered Extension Units

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

Test Run, Maintenance, Troubleshooting

16.6.3 External dimensions

16 Input/Output Extension Blocks

9(0.36") 87(3.43")

40(1.58")

16.6.4 Example of wiring

17 Extension Power Supply Unit

1. Wiring on input side Sink input

5V DC

N S/S

0V 24V X0 Input circuit

TTL

External unit

18 Other Extension Units and Options

L

High-Speed Counters

16.6.2 Parts identification and terminal arrangement

5+ X0 X1 X3 Input circuit

19 Display Module main unit or input/output powered extension unit

20 Terminal Block

227

Page 234

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.6 FX2N-16EXL-C (5V DC Input: 16 Points)

How to connect connector (Socket)

Connection face of connector The polarity is shown in the following table. 20

Cross section of 20-core flat cable (Be sure to check the wire number.)

19 17 15 13 11 B 20 18 16 14 12

A 10

9

8

7

Side B 5+ Side A 5+

228

6

5

4

3

2

20

19 17 15 13 11 20 18 16 14 12

10 1

FX-16ECAB type cable

9

8

7

6

5

4

3

2

1

X7 X6 X5 X4 X3 X2 X1 X0 X7 X6 X5 X4 X3 X2 X1 X0

Side B is for the higher input numbers, and side A is for the lower input numbers. (Exe.) Side B X050 to X057 Side A X040 to X047

Page 235

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

11

FX2N-8EX-UA1/UL (100V AC Input)

High-Speed Counters

16.7

16.7 FX2N-8EX-UA1/UL (100V AC Input)

16.7.1 Product specifications

1. Power supply specifications Item

13

FX2N-8EX-UA1/UL FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

Wiring for Various Uses

Product type

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-8EX-UA1/UL

MASS (Weight)

14

0.2kg (0.44lbs)

Other

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

Test Run, Maintenance, Troubleshooting

• • •

3. Input specifications Item

FX2N-8EX-UA1/UL

Input points

12 Output Wiring

The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring.

15

8 points

Input signal voltage

100 to 120V AC

Input signal current

6.2mA/110V AC 60Hz 4.7mA/100V AC 50Hz

Input/Output Powered Extension Units

Input impedance

Approx. 21k /50Hz Approx. 18k /60Hz

16

Input ON current

3.8mA/80V AC or more

Input OFF current

1.7mA/30V AC or more

Input/Output Extension Blocks

Connection type

Vertical terminal block (M3 screws)

Input form

ON input sensitivity current

AC input

Input response time

Approx. 25 to 30ms

Input signal form Input circuit insulation Indication of input operation

Voltage contact Photo-coupler insulation

17

LED on panel lights when input.

Extension Power Supply Unit

100 to 120V AC COM Photocoupler Input impedance

Fuse

18 Other Extension Units and Options

X*0 Input circuit diagram

Photocoupler Input impedance X*7

19 Display Module

20 Terminal Block

229