Page 216
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16. Input/Output Extension Blocks DESIGN PRECAUTIONS •
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS •
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions.
WIRING PRECAUTIONS • • •
Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.
WIRING PRECAUTIONS • • • •
210
Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Do not wire vacant terminals externally. Doing so may damage the product. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.
Page 217
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
11
Outline Connect input/output extension blocks to the PLC to add more input/output points. 8 or 16 points can be added by an input/output extension block. Since the power is supplied from the main unit, it is not necessary to prepare another power supply unit for each input/output extension block.
There are various types of input/output extension blocks. Select optimum blocks considering the input type, output type, and connection unit of your system. Input/output extension blocks Number of points
Input type
Output type
Connection unit
Power supply to inside of PLC
8
24V DC (Sink, source)
Relay
Terminal block
Triac
Connector
16
14 Test Run, Maintenance, Troubleshooting
24V DC (Sink)
Transistor (Source)
5V DC
Transistor (Sink)
100V AC system
15
1. For input/output extension :Sink [-common],
Sink Input
:Source [+common]
Output Common system
Connection type
Number of points
Common system
Relay
4(8)*1
-
Terminal block
Relay
4(8)*1
-
Terminal block
17
Source
:Source [+common]
Common to both sink and source inputs FX2N-8ER-ES/UL
24V DC
4(8)*1
Sink
4(8)*1
Sink
Source
Dedicated to sink input only FX2N-8ER
Extension Power Supply Unit
*1.
24V DC
Four inputs and four outputs are occupied as unused numbers.
2. For input extension :Sink [-common],
Sink Input Type
Number of points
Output Common system
Type
Number of points
Common system
Connection type
Common to both sink and source inputs FX2N-8EX-ES/UL
24V DC
8
Sink
Source
-
-
-
Terminal block
FX2N-16EX-ES/UL
24V DC
16
Sink
Source
-
-
-
Terminal block
Dedicated to sink input only 8
Sink
-
-
-
Terminal block
FX2N-16EX
24V DC
16
Sink
-
-
-
Terminal block
FX2N-16EX-C
24V DC
16
Sink
-
-
-
Connector
FX2N-16EXL-C
5V DC
16
Sink
-
-
-
Connector
100V AC
8
-
-
-
Terminal block
100V AC input type FX2N-8EX-UA1/UL
-
211
20 Terminal Block
24V DC
19 Display Module
FX2N-8EX
18 Other Extension Units and Options
Model
16
Type
Input/Output Extension Blocks
Type
Number of points
Source
Input/Output Powered Extension Units
16.1.2 Product list
Model
13 Wiring for Various Uses
Power supply
12 Output Wiring
16.1.1 Product configuration
High-Speed Counters
16.1
16.1 Outline
Page 218
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.1 Outline
3. For output extension Sink
:Sink [-common],
Input Model
Source
:Source [+common]
Output
Connection type
Type
Number of points
Common system
Type
Number of points
Common system
FX2N-8EYR-ES/UL
-
-
-
Relay
8
-
FX2N-8EYR
-
-
-
Relay
8
-
Terminal block
FX2N-16EYR-ES/UL
-
-
-
Relay
16
-
Terminal block
FX2N-16EYR
-
-
-
Relay
16
-
Terminal block
Relay output type Terminal block
Dedicated to sink output only FX2N-8EYT
-
-
-
Transistor
8
Sink
Terminal block
FX2N-8EYT-H
-
-
-
Transistor
8
Sink
Terminal block
FX2N-16EYT
-
-
-
Transistor
16
Sink
Terminal block
FX2N-16EYT-C
-
-
-
Transistor
16
Sink
Connector
FX2N-16EYS
-
-
-
Transistor
16
-
Terminal block
Dedicated to source output only
212
FX2N-8EYT-ESS/UL
-
-
-
Transistor
8
Source
Terminal block
FX2N-16EYT-ESS/UL
-
-
-
Transistor
16
Source
Terminal block
Page 219
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
11
FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
High-Speed Counters
16.2
16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
16.2.1 Product specifications
1. Power supply specifications
13
FX2N-8ER-ES/UL
Product type
FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Wiring for Various Uses
Item
2. Weight and Other specifications (External dimensions are described later.) Item
14
FX2N-8ER-ES/UL 0.2kg (0.44lbs) • • •
Other
Test Run, Maintenance, Troubleshooting
MASS (Weight)
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Input specifications (common to both sink and source inputs) Item
Input/Output Powered Extension Units
4 points
Connection type
Vertical terminal block (M3 screws)
Input form sink/source
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance
4.3k Input ON current
10%
16 Input/Output Extension Blocks
ON input sensitivity current
15
FX2N-8ER-ES/UL
Input points
3.5mA or more at 24V DC
Input OFF current
1.5mA or less
Input response time
Approx. 10ms
Input signal form
Sink input: No-voltage contact input, NPN open collector transistor Source input: No-voltage contact input, PNP open collector transistor
Input circuit insulation
17
Photo-coupler insulation
Extension Power Supply Unit
Indication of input operation
LED on panel lights when input.
Sink input wiring Main unit
Source input wiring S/S
Main unit
S/S 0V 24V
S/S
S/S
18 Other Extension Units and Options
0V 24V Input circuit diagram
4.3k
X
12 Output Wiring
The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.
4.3k
X
19 Display Module
20 Terminal Block
213
Page 220
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16 Input/Output Extension Blocks 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
4. Output specifications (Relay output type) Item
FX2N-8ER-ES/UL
Output Points
4 points
Connection type
Vertical terminal block (M3 screws)
Output type
Relay 30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
External power supply Output circuit insulation
Mechanical insulation
Indication of output operation Resistance load Max. load
Supplying power to the relay coil will light the LED indicator lamp on panel. 2A/point The total resistance load current per common should be as follows: • 4 output points/common: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.
Inductive load Open circuit leakage current
-
Min. load
5V DC, 2mA (reference values)
Response time
OFF ON
Approx. 10ms
ON OFF
Approx. 10ms
Load DC power supply unit
Output circuit configuration
Y COM1
Fuse
16.2.2 Parts identification and terminal arrangement Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower four points. With cover
Without cover
Rear line extension connector
S/S X1 X3 X0 X2
Input indicator lamps (LED lamps) Output indicator lamps (LED lamps)
Y0 Y2
COM1 Y1 Y3
214
Page 221
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16 Input/Output Extension Blocks 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
11
12 90(3.55")
13 9(0.36") 87(3.43")
Wiring for Various Uses
43(1.7")
Unit:mm(inches)
Output Wiring
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
High-Speed Counters
16.2.3 External dimensions
14 Test Run, Maintenance, Troubleshooting
15 Input/Output Powered Extension Units
16 Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
215
Page 222
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16.3
16 Input/Output Extension Blocks 16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
FX2N-8ER (24V DC Sink Input, Relay Output)
16.3.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.
1. Power supply specifications Item
FX2N-8ER
Product type
FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
2. Weight and Other specifications (External dimensions are described later.) Item
FX2N-8ER
MASS (Weight)
0.2kg (0.44lbs) • • •
Other
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
3. Input specifications Item
FX2N-8ER
Input points
4 points
Connection type
Vertical terminal block (M3 screws)
Input form
Sink
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance ON input sensitivity current
10%
4.3k Input ON current
3.5mA or more at 24V DC
Input OFF current
1.5mA or less
Input response time
Approx. 10ms
Input signal form
No-voltage contact input NPN open collector transistor
Input circuit insulation Indication of input operation
Photo-coupler insulation LED on panel lights when input.
Sink input wiring Main unit
S/S 0V 24V
Input circuit diagram
24+
4.3k
216
X
Page 223
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
11
Item
High-Speed Counters
4. Output specifications (Relay output type) FX2N-8ER
Output Points
4 points
Connection type
Vertical terminal block (M3 screws)
Output type
Relay
External power supply Output circuit insulation
Mechanical insulation
Indication of output operation Resistance load Max. load
Supplying power to the relay coil will light the LED indicator lamp on panel. 2A/point The total resistance load current per common should be as follows: • 4 output points/common: 8A or less
Inductive load Open circuit leakage current
-
Min. load
13 Wiring for Various Uses
80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.
12 Output Wiring
30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
5V DC, 2mA (reference values)
Response time
OFF ON
Approx. 10ms
ON OFF
Approx. 10ms
DC power supply unit
Output circuit configuration
Test Run, Maintenance, Troubleshooting
Load
14
Y
Fuse
15
16.3.2 Parts identification and terminal arrangement
Input/Output Powered Extension Units
COM1
With cover
Without cover
17 Extension Power Supply Unit
Rear line extension connector
24+ X1 X3 X0 X2
Input indicator lamps (LED lamps) Output indicator lamps (LED lamps)
16 Input/Output Extension Blocks
Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower four points.
18 Other Extension Units and Options
Y0 Y2
COM1 Y1 Y3
19 Display Module
20 Terminal Block
217
Page 224
FX3G Series Programmable Controllers
16 Input/Output Extension Blocks
User's Manual - Hardware Edition
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
16.3.3 External dimensions
43(1.7")
218
Unit:mm(inches)
90(3.55")
80(3.15") (mounting hole pitch)
2- 4.5 mounting holes
9(0.36") 87(3.43")
Page 225
FX3G Series Programmable Controllers User's Manual - Hardware Edition
16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)
11
FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)
High-Speed Counters
16.4
16 Input/Output Extension Blocks
16.4.1 Product specifications
1. Power supply specifications Item
FX2N-8EX-ES/UL
13
FX2N-16EX-ES/UL FX2N extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Wiring for Various Uses
Product type
2. Weight and Other specifications (External dimensions are described later.) Item
FX2N-8EX-ES/UL
FX2N-16EX-ES/UL
0.2kg (0.44lbs)
0.3kg (0.66lbs)
MASS (Weight) Other
14
The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Test Run, Maintenance, Troubleshooting
• • •
3. Input specifications (common to both sink and source inputs) Item
FX2N-8EX-ES/UL
FX2N-16EX-ES/UL
8 points
16 points
Input points
Vertical terminal block (M3 screws)
Input form sink/source
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance
10%
16
4.3k Input ON current
3.5mA or more at 24V DC
Input OFF current
1.5mA or less
Input response time
Approx. 10ms
Input signal form
Sink input: No-voltage contact input, NPN open collector transistor Source input: No-voltage contact input, PNP open collector transistor
Input circuit insulation
Input/Output Extension Blocks
ON input sensitivity current
15 Input/Output Powered Extension Units
Connection type
Photo-coupler insulation
Indication of input operation
17
LED on panel lights when input.
Main unit
Extension Power Supply Unit
Sink input wiring
Source input wiring S/S
Main unit
S/S
0V
0V
24V
24V
S/S
S/S
18
X
4.3k
Other Extension Units and Options
Input circuit diagram
4.3k
12 Output Wiring
The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring.
X
19 Display Module
20 Terminal Block
219