FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 16. Input/Output Extension Blocks, pages 216 to 225

Pages 216 to 225 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 216

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16. Input/Output Extension Blocks DESIGN PRECAUTIONS •

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

DESIGN PRECAUTIONS •

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions.

WIRING PRECAUTIONS • • •

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

WIRING PRECAUTIONS • • • •

210

Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Do not wire vacant terminals externally. Doing so may damage the product. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Page 217

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

11

Outline Connect input/output extension blocks to the PLC to add more input/output points. 8 or 16 points can be added by an input/output extension block. Since the power is supplied from the main unit, it is not necessary to prepare another power supply unit for each input/output extension block.

There are various types of input/output extension blocks. Select optimum blocks considering the input type, output type, and connection unit of your system. Input/output extension blocks Number of points

Input type

Output type

Connection unit

Power supply to inside of PLC

8

24V DC (Sink, source)

Relay

Terminal block

Triac

Connector

16

14 Test Run, Maintenance, Troubleshooting

24V DC (Sink)

Transistor (Source)

5V DC

Transistor (Sink)

100V AC system

15

1. For input/output extension :Sink [-common],

Sink Input

:Source [+common]

Output Common system

Connection type

Number of points

Common system

Relay

4(8)*1

-

Terminal block

Relay

4(8)*1

-

Terminal block

17

Source

:Source [+common]

Common to both sink and source inputs FX2N-8ER-ES/UL

24V DC

4(8)*1

Sink

4(8)*1

Sink

Source

Dedicated to sink input only FX2N-8ER

Extension Power Supply Unit

*1.

24V DC

Four inputs and four outputs are occupied as unused numbers.

2. For input extension :Sink [-common],

Sink Input Type

Number of points

Output Common system

Type

Number of points

Common system

Connection type

Common to both sink and source inputs FX2N-8EX-ES/UL

24V DC

8

Sink

Source

-

-

-

Terminal block

FX2N-16EX-ES/UL

24V DC

16

Sink

Source

-

-

-

Terminal block

Dedicated to sink input only 8

Sink

-

-

-

Terminal block

FX2N-16EX

24V DC

16

Sink

-

-

-

Terminal block

FX2N-16EX-C

24V DC

16

Sink

-

-

-

Connector

FX2N-16EXL-C

5V DC

16

Sink

-

-

-

Connector

100V AC

8

-

-

-

Terminal block

100V AC input type FX2N-8EX-UA1/UL

-

211

20 Terminal Block

24V DC

19 Display Module

FX2N-8EX

18 Other Extension Units and Options

Model

16

Type

Input/Output Extension Blocks

Type

Number of points

Source

Input/Output Powered Extension Units

16.1.2 Product list

Model

13 Wiring for Various Uses

Power supply

12 Output Wiring

16.1.1 Product configuration

High-Speed Counters

16.1

16.1 Outline

Page 218

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.1 Outline

3. For output extension Sink

:Sink [-common],

Input Model

Source

:Source [+common]

Output

Connection type

Type

Number of points

Common system

Type

Number of points

Common system

FX2N-8EYR-ES/UL

-

-

-

Relay

8

-

FX2N-8EYR

-

-

-

Relay

8

-

Terminal block

FX2N-16EYR-ES/UL

-

-

-

Relay

16

-

Terminal block

FX2N-16EYR

-

-

-

Relay

16

-

Terminal block

Relay output type Terminal block

Dedicated to sink output only FX2N-8EYT

-

-

-

Transistor

8

Sink

Terminal block

FX2N-8EYT-H

-

-

-

Transistor

8

Sink

Terminal block

FX2N-16EYT

-

-

-

Transistor

16

Sink

Terminal block

FX2N-16EYT-C

-

-

-

Transistor

16

Sink

Connector

FX2N-16EYS

-

-

-

Transistor

16

-

Terminal block

Dedicated to source output only

212

FX2N-8EYT-ESS/UL

-

-

-

Transistor

8

Source

Terminal block

FX2N-16EYT-ESS/UL

-

-

-

Transistor

16

Source

Terminal block

Page 219

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

11

FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)

High-Speed Counters

16.2

16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)

16.2.1 Product specifications

1. Power supply specifications

13

FX2N-8ER-ES/UL

Product type

FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

Wiring for Various Uses

Item

2. Weight and Other specifications (External dimensions are described later.) Item

14

FX2N-8ER-ES/UL 0.2kg (0.44lbs) • • •

Other

Test Run, Maintenance, Troubleshooting

MASS (Weight)

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Input specifications (common to both sink and source inputs) Item

Input/Output Powered Extension Units

4 points

Connection type

Vertical terminal block (M3 screws)

Input form sink/source

Input signal voltage

24V DC

Input signal current

5mA/24V DC

Input impedance

4.3k Input ON current

10%

16 Input/Output Extension Blocks

ON input sensitivity current

15

FX2N-8ER-ES/UL

Input points

3.5mA or more at 24V DC

Input OFF current

1.5mA or less

Input response time

Approx. 10ms

Input signal form

Sink input: No-voltage contact input, NPN open collector transistor Source input: No-voltage contact input, PNP open collector transistor

Input circuit insulation

17

Photo-coupler insulation

Extension Power Supply Unit

Indication of input operation

LED on panel lights when input.

Sink input wiring Main unit

Source input wiring S/S

Main unit

S/S 0V 24V

S/S

S/S

18 Other Extension Units and Options

0V 24V Input circuit diagram

4.3k

X

12 Output Wiring

The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.

4.3k

X

19 Display Module

20 Terminal Block

213

Page 220

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16 Input/Output Extension Blocks 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)

4. Output specifications (Relay output type) Item

FX2N-8ER-ES/UL

Output Points

4 points

Connection type

Vertical terminal block (M3 screws)

Output type

Relay 30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)

External power supply Output circuit insulation

Mechanical insulation

Indication of output operation Resistance load Max. load

Supplying power to the relay coil will light the LED indicator lamp on panel. 2A/point The total resistance load current per common should be as follows: • 4 output points/common: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.

Inductive load Open circuit leakage current

-

Min. load

5V DC, 2mA (reference values)

Response time

OFF ON

Approx. 10ms

ON OFF

Approx. 10ms

Load DC power supply unit

Output circuit configuration

Y COM1

Fuse

16.2.2 Parts identification and terminal arrangement Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower four points. With cover

Without cover

Rear line extension connector

S/S X1 X3 X0 X2

Input indicator lamps (LED lamps) Output indicator lamps (LED lamps)

Y0 Y2

COM1 Y1 Y3

214

Page 221

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16 Input/Output Extension Blocks 16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)

11

12 90(3.55")

13 9(0.36") 87(3.43")

Wiring for Various Uses

43(1.7")

Unit:mm(inches)

Output Wiring

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

High-Speed Counters

16.2.3 External dimensions

14 Test Run, Maintenance, Troubleshooting

15 Input/Output Powered Extension Units

16 Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

215

Page 222

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16.3

16 Input/Output Extension Blocks 16.3 FX2N-8ER (24V DC Sink Input, Relay Output)

FX2N-8ER (24V DC Sink Input, Relay Output)

16.3.1 Product specifications The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.

1. Power supply specifications Item

FX2N-8ER

Product type

FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-8ER

MASS (Weight)

0.2kg (0.44lbs) • • •

Other

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

3. Input specifications Item

FX2N-8ER

Input points

4 points

Connection type

Vertical terminal block (M3 screws)

Input form

Sink

Input signal voltage

24V DC

Input signal current

5mA/24V DC

Input impedance ON input sensitivity current

10%

4.3k Input ON current

3.5mA or more at 24V DC

Input OFF current

1.5mA or less

Input response time

Approx. 10ms

Input signal form

No-voltage contact input NPN open collector transistor

Input circuit insulation Indication of input operation

Photo-coupler insulation LED on panel lights when input.

Sink input wiring Main unit

S/S 0V 24V

Input circuit diagram

24+

4.3k

216

X

Page 223

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.3 FX2N-8ER (24V DC Sink Input, Relay Output)

11

Item

High-Speed Counters

4. Output specifications (Relay output type) FX2N-8ER

Output Points

4 points

Connection type

Vertical terminal block (M3 screws)

Output type

Relay

External power supply Output circuit insulation

Mechanical insulation

Indication of output operation Resistance load Max. load

Supplying power to the relay coil will light the LED indicator lamp on panel. 2A/point The total resistance load current per common should be as follows: • 4 output points/common: 8A or less

Inductive load Open circuit leakage current

-

Min. load

13 Wiring for Various Uses

80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.

12 Output Wiring

30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)

5V DC, 2mA (reference values)

Response time

OFF ON

Approx. 10ms

ON OFF

Approx. 10ms

DC power supply unit

Output circuit configuration

Test Run, Maintenance, Troubleshooting

Load

14

Y

Fuse

15

16.3.2 Parts identification and terminal arrangement

Input/Output Powered Extension Units

COM1

With cover

Without cover

17 Extension Power Supply Unit

Rear line extension connector

24+ X1 X3 X0 X2

Input indicator lamps (LED lamps) Output indicator lamps (LED lamps)

16 Input/Output Extension Blocks

Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower four points.

18 Other Extension Units and Options

Y0 Y2

COM1 Y1 Y3

19 Display Module

20 Terminal Block

217

Page 224

FX3G Series Programmable Controllers

16 Input/Output Extension Blocks

User's Manual - Hardware Edition

16.3 FX2N-8ER (24V DC Sink Input, Relay Output)

16.3.3 External dimensions

43(1.7")

218

Unit:mm(inches)

90(3.55")

80(3.15") (mounting hole pitch)

2- 4.5 mounting holes

9(0.36") 87(3.43")

Page 225

FX3G Series Programmable Controllers User's Manual - Hardware Edition

16.4 FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)

11

FX2N-8EX-ES/UL, FX2N-16EX-ES/UL (24V DC Sink/Source Input)

High-Speed Counters

16.4

16 Input/Output Extension Blocks

16.4.1 Product specifications

1. Power supply specifications Item

FX2N-8EX-ES/UL

13

FX2N-16EX-ES/UL FX2N extension block

Rated voltage

24V DC (supplied from main unit and input/output powered extension unit)

Wiring for Various Uses

Product type

2. Weight and Other specifications (External dimensions are described later.) Item

FX2N-8EX-ES/UL

FX2N-16EX-ES/UL

0.2kg (0.44lbs)

0.3kg (0.66lbs)

MASS (Weight) Other

14

The extension cable is already connected to the extension block. Accessories: Label for indication of input/output number The DIN46277 rail (width: 35 mm (1.38")) or direct installation.

Test Run, Maintenance, Troubleshooting

• • •

3. Input specifications (common to both sink and source inputs) Item

FX2N-8EX-ES/UL

FX2N-16EX-ES/UL

8 points

16 points

Input points

Vertical terminal block (M3 screws)

Input form sink/source

Input signal voltage

24V DC

Input signal current

5mA/24V DC

Input impedance

10%

16

4.3k Input ON current

3.5mA or more at 24V DC

Input OFF current

1.5mA or less

Input response time

Approx. 10ms

Input signal form

Sink input: No-voltage contact input, NPN open collector transistor Source input: No-voltage contact input, PNP open collector transistor

Input circuit insulation

Input/Output Extension Blocks

ON input sensitivity current

15 Input/Output Powered Extension Units

Connection type

Photo-coupler insulation

Indication of input operation

17

LED on panel lights when input.

Main unit

Extension Power Supply Unit

Sink input wiring

Source input wiring S/S

Main unit

S/S

0V

0V

24V

24V

S/S

S/S

18

X

4.3k

Other Extension Units and Options

Input circuit diagram

4.3k

12 Output Wiring

The generic specifications are identical to the main unit specifications. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 10 for input wiring.

X

19 Display Module

20 Terminal Block

219