Page 210

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.6 FX2N-32ET, FX2N-48ET

3. Output specifications (transistor output type) Item Output Points

FX2N-32ET

FX2N-48ET

16 points

24 points

Connection type

Removable terminal block (M3 screw)

Output unit/type

Transistor/sink output

External power supply

5 to 30V DC

Output circuit insulation

Photo-coupler insulation

Indication of output operation

Max. load

Resistance load

Activation of the photo-coupler will light the LED indicator lamp on panel. 0.5A/point 0.5A/point The total load current per common terminal The total load current per common terminal should be the following value. should be the following value. • 4 output points/common terminal: 0.8A or • 8 output points/common terminal: 1.6A or less less • 8 output points/common terminal: 1.6A or less

Inductive load

12W/24V DC

Open circuit leakage current

0.1mA/30V DC

Min. load Response time

OFF ON

0.2ms or less/200mA (at 24V DC)

ON OFF

0.2ms or less/200mA (at 24V DC)

Load Output circuit configuration

DC power supply Fuse

Y COM

A common number applies to the

204 of [COM

].

Page 211

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.6 FX2N-32ET, FX2N-48ET

11 High-Speed Counters

15.6.2 External dimensions FX2N-32ET 2- 4.5 mounting holes

12

90 (3.55")

Output Wiring

13 Wiring for Various Uses

80 (3.15") (mounting hole pitch)

Unit : mm (inches)

9 (0.36")

140 (5.52") (mounting hole pitch) 150 (5.91")

87 (3.43")

FX2N-48ET

14

2- 4.5 mounting holes

90 (3.55")

172 (6.78") (mounting hole pitch) 182 (7.17")

15 Input/Output Powered Extension Units

80 (3.15") (mounting hole pitch)

Test Run, Maintenance, Troubleshooting

Unit : mm (inches)

9 (0.36") 87 (3.43")

16 Input/Output Extension Blocks

15.6.3 Terminal layout FX2N-32ET L

N

COM X0 X2 X4 X6 X0 X2 X4 X6 24+ X1 X3 X5 X7 X1 X3 X5 X7

17 Extension Power Supply Unit

FX 2N-32ET Y0 Y2

Y4 Y6

Y0 Y2

Y4 Y6

COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7

18

L

N

Other Extension Units and Options

FX2N-48ET COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6 24+ X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7

FX2N-48ET

19 Display Module

Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7

20 Terminal Block

205

Page 212

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.7

15.7 FX2N-32ES

FX2N-32ES

15.7.1 Product specifications The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.

1. Power supply specifications → For the power supply specifications, refer to Section 15.2.

2. Input specifications (sink input) Item

FX2N-32ES

Input points

16 points

Connection type

Removable terminal block (M3 screw)

Input form sink

Input signal voltage

24V DC

Input signal current

5mA/24V DC

Input impedance Input response time

10%

4.3 k Input ON current Input OFF current

3.5mA or more/24V DC 1.5mA or less

Input response time

Approx. 10ms

Input signal form

No-voltage contact input NPN open collector transistor

Input circuit insulation Indication of input operation

Photo-coupler insulation LED on panel lights when input.

Sink input wiring L N 24+ COM

Input circuit diagram

4.3k

206

X

Fuse

100 to 240V AC

Page 213

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.7 FX2N-32ES

11

Item

High-Speed Counters

3. Output specifications (triac output type) FX2N-32ES

Output Points

16 points

Connection type

Removable terminal block (M3 screw)

Output unit

12

Triac output (SSR) 85 to 242V AC

Output circuit insulation

Photo-thyristor insulation

Indication of output operation Resistance load

Max. load

Activation of the photo-thyristor will light the LED indicator lamp on panel. 0.3A/point The total load current per common terminal should be the following value. • 4 output points/common terminal: 0.8A or less

Inductive load

13

15VA/100V AC, 30VA/200V AC 1mA/100V AC, 2mA/200V AC

Min. load

0.4VA/100V AC, 1.6VA/200V AC OFF ON

1ms or less

ON OFF

10ms or less

Wiring for Various Uses

Open circuit leakage current

Response time

Output Wiring

External power supply

14 DC power supply

Output circuit configuration

Fuse

Test Run, Maintenance, Troubleshooting

Load Y COM

A common number applies to the

15 of [COM ].

Input/Output Powered Extension Units

15.7.2 External dimensions 2- 4.5 mounting holes

16

90 (3.55")

Input/Output Extension Blocks

17 Extension Power Supply Unit

80 (3.15") (mounting hole pitch)

Unit : mm (inches)

9 (0.36")

140 (5.52") (mounting hole pitch) 150 (5.91")

87 (3.43")

18

15.7.3 Terminal layout

N

Other Extension Units and Options

L

COM X0 X2 X4 X6 X0 X2 X4 X6 24+ X1 X3 X5 X7 X1 X3 X5 X7

FX2N-32ES Y4 Y6

Y0 Y2

Display Module

Y0 Y2

19 Y4 Y6

COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7

20 Terminal Block

207

Page 214

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.8

15.8 FX2N-48ER-UA1/UL

FX2N-48ER-UA1/UL

15.8.1 Product specifications The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.

1. Power supply specifications → For the power supply specifications, refer to Section 15.2.

2. Input specifications (100V AC Input) Item

FX2N-48ER-UA1/UL

Input points

24 points

Connection type

Removable terminal block (M3 screw)

Input form

AC input

Input signal voltage

100 to 120V AC +10%,-15% 50/60 Hz

Input signal current

4.7 mA/100V AC 50 Hz (70% or less when turned on simultaneously) 6.2 mA/110V AC 60 Hz (70% or less when turned on simultaneously)

Input impedance

Approx. 21 k /50 Hz Approx. 18 k /60 Hz

Input response time

Input ON current

3.8mA or more/80V AC

Input OFF current

1.7mA or less/30V AC

Input response time

Approx. 25 to 30ms

Input signal form Input circuit insulation Indication of input operation

Contact input Photo-coupler insulation LED on panel lights when input.

L N

Fuse

100 to 240V AC Input circuit diagram

COM *1 X *1 Input impedance

208

Page 215

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.8 FX2N-48ER-UA1/UL

11

Item

High-Speed Counters

3. Output specifications (relay output type) FX2N-48ER-UA1/UL

Output Points

24 points

Connection type

Removable terminal block (M3 screw)

Output unit

Relay

External power supply Output circuit insulation

Mechanical insulation

Indication of output operation

Supplying power to the relay coil will light the LED indicator lamp on panel.

Resistance load

80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.2.

Inductive load Open circuit leakage current

-

Min. load

14

5V DC, 2mA (reference value) OFF ON

Approx. 10ms

ON OFF

Approx. 10ms

Y

Test Run, Maintenance, Troubleshooting

Response time

COM

15

Load DC power supply

Input/Output Powered Extension Units

Fuse

Output circuit configuration

External power supply

Y

COM Fuse A common number applies to the of [COM

16

].

Input/Output Extension Blocks

15.8.2 External dimensions 4- 4.5 mounting holes

17

90 (3.55")

Extension Power Supply Unit

80 (3.15") (mounting hole pitch)

Unit : mm (inches)

18 Other Extension Units and Options

9 (0.36")

210 (8.27") (mounting hole pitch) 220 (8.67")

87 (3.43")

19

15.8.3 Terminal layout N

X1 X3 X5 X7

X0 X2 X4 X6 X1 X3 X5 X7

Display Module

COM COM X0 X2 X4 X6

L

13 Wiring for Various Uses

Max. load

2A/point The total load current of resistance loads per common terminal should be the following value. • 4 output points/common terminal: 8A or less • 8 output points/common terminal: 8A or less

12 Output Wiring

30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)

X0 X2 X4 X6 X1 X3 X5 X7

FX2N-48ER-UA1/UL Y0 Y2 Y4 Y6 COM3 Y1 Y3 COM4 Y5 Y7

20

Y0 Y2 Y4 Y6 COM5 Y1 Y3 Y5 Y7

Terminal Block

Y0 Y2 Y4 Y6 COM1 Y1 Y3 COM2 Y5 Y7

209