The text of a manual · part 26 of 49
FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 15. Input/Output Powered Extension Units, pages 202 to 209
Pages 202 to 209 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]
The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Mitsubishi FX-16EYR
Page 202
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL
15.3.2 External dimensions FX2N-32ER-ES/UL 2- 4.5 mounting holes
80 (3.15") (mounting hole pitch) 90 (3.55")
Unit : mm (inches)
140 (5.52") (mounting hole pitch) 150 (5.91")
9 (0.36") 87 (3.43")
FX2N-48ER-ES/UL 4- 4.5 mounting holes
90 (3.55")
80 (3.15") (mounting hole pitch)
Unit : mm (inches)
172 (6.78") (mounting hole pitch) 182 (7.17")
9 (0.36") 87 (3.43")
15.3.3 Terminal layout FX2N-32ER-ES/UL L
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 N 24V X1 X3 X5 X7 X1 X3 X5 X7
FX 2N-32ER-ES/UL Y0 Y2
Y4 Y6
Y0 Y2
Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
FX2N-48ER-ES/UL L
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6 N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ER-ES/UL Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
196
Page 203
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
11
FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL
High-Speed Counters
15.4
15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL
15.4.1 Product specifications
13
1. Power supply specifications 2. Input specifications (for sink input and source input) Item
FX2N-32ET-ESS/UL
FX2N-48ET-ESS/UL
16 points
24 points
Input form sink/source
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance
4.3 k
10%
Input ON current
3.5mA or more/24V DC
Input OFF current
1.5mA or less
15
Input response time
Approx. 10ms
Input signal form
No-voltage contact input Sink: NPN open collector transistor Source: PNP open collector transistor
Input circuit insulation
Input/Output Powered Extension Units
Input response time
14
Removable terminal block (M3 screw)
Test Run, Maintenance, Troubleshooting
Connection type
16
Photo-coupler insulation LED on panel lights when input.
Sink input wiring
Source input wiring L N
Fuse
L N
100 to 240V AC
S/S 0V 24V
Fuse
100 to 240V AC
4.3k
4.3k X
17 Extension Power Supply Unit
S/S 0V 24V
Input circuit diagram
Input/Output Extension Blocks
Indication of input operation
Wiring for Various Uses
→ For the power supply specifications, refer to Section 15.2.
Input points
12 Output Wiring
The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.
18
X
Other Extension Units and Options
19 Display Module
20 Terminal Block
197
Page 204
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL
3. Output specifications (transistor output type) Item Output Points
FX2N-32ET-ESS/UL
FX2N-48ET-ESS/UL
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Output unit/type
Transistor/source output
External power supply
5 to 30V DC
Output circuit insulation
Photo-coupler insulation
Indication of output operation
Max. load
Resistance load
Activation of the photo-coupler will light the LED indicator lamp on panel. 0.5A/point 0.5A/point The total load current per common terminal The total load current per common terminal should be the following value. should be the following value. • 4 output points/common terminal: 0.8A or • 4 output points/common terminal: 0.8A or less less • 8 output points/common terminal: 1.6A or less
Inductive load
12W/24V DC
Open circuit leakage current
0.1mA/30V DC
Min. load Response time
OFF ON
0.2ms or less/200mA (at 24V DC)
ON OFF
0.2ms or less/200mA (at 24V DC)
Load Output circuit configuration
DC power supply
Fuse
Y +V
A common number applies to the of [+V ].
198
Page 205
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL
11 High-Speed Counters
15.4.2 External dimensions FX2N-32ET-ESS/UL 2- 4.5 mounting holes
Unit : mm (inches)
Output Wiring
80 (3.15") (mounting hole pitch) 90 (3.55")
12
13 Wiring for Various Uses
9 (0.36")
140 (5.52") (mounting hole pitch) 150 (5.91")
87 (3.43")
FX2N-48ET-ESS/UL 4- 4.5 mounting holes
14
90 (3.55")
172 (6.78") (mounting hole pitch) 182 (7.17")
15 Input/Output Powered Extension Units
80 (3.15") (mounting hole pitch)
Test Run, Maintenance, Troubleshooting
Unit : mm (inches)
9 (0.36") 87 (3.43")
16 Input/Output Extension Blocks
15.4.3 Terminal layout FX2N-32ET-ESS/UL L
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 N 24V X1 X3 X5 X7 X1 X3 X5 X7
17 Extension Power Supply Unit
FX2N-32ET-ESS/UL Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7
18
FX2N-48ET-ESS/UL
Other Extension Units and Options
L
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6 N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ET-ESS/UL
19 Display Module
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V4 +V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7 Y1 Y3 Y5 Y7
20 Terminal Block
199
Page 206
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.5
15.5 FX2N-32ER, FX2N-48ER
FX2N-32ER, FX2N-48ER
15.5.1 Product specifications The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.
1. Power supply specifications → For the power supply specifications, refer to Section 15.2.
2. Input specifications (sink input) Item Input points Connection type
FX2N-32ER
FX2N-48ER
16 points
24 points Removable terminal block (M3 screw)
Input form sink
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance Input response time
10%
4.3 k Input ON current Input OFF current
3.5mA or more/24V DC 1.5mA or less
Input response time
Approx. 10ms
Input signal form
No-voltage contact input NPN open collector transistor
Input circuit insulation Indication of input operation
Photo-coupler insulation LED on panel lights when input.
Sink input wiring L N 24+ COM
Input circuit diagram
4.3k
200
X
Fuse
100 to 240V AC
Page 207
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.5 FX2N-32ER, FX2N-48ER
11
Item Output Points
FX2N-32ER
FX2N-48ER
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Output unit
12
Relay 250V AC/30V DC or less
Output circuit insulation
Mechanical insulation
Indication of output operation
Resistance load
2A/point 2A/point The total load current per common terminal The total load current per common terminal should be the following value. should be the following value. • 4 output points/common terminal: 8A or less • 8 output points/common terminal: 8A or less • 8 output points/common terminal: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.
Inductive load Open circuit leakage current
-
Min. load
14
5V DC, 2mA (reference value) Approx. 10ms
ON OFF
Approx. 10ms
Y
Test Run, Maintenance, Troubleshooting
OFF ON
COM
15
Load DC power supply
Input/Output Powered Extension Units
Output circuit configuration
13 Wiring for Various Uses
Max. load
When power is applied to relay coil, LED is lit.
Output Wiring
External power supply
Response time
High-Speed Counters
3. Output specifications (relay output type)
Fuse Y
External power supply COM
Fuse
16
A common number applies to the of [COM ].
Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
201
Page 208
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.5 FX2N-32ER, FX2N-48ER
15.5.2 External dimensions FX2N-32ER 2- 4.5 mounting holes
90 (3.55")
80 (3.15") (mounting hole pitch)
Unit : mm (inches)
9 (0.36")
140 (5.52") (mounting hole pitch) 150 (5.91")
87 (3.43")
FX2N-48ER 4- 4.5 mounting holes
90 (3.55")
80 (3.15") (mounting hole pitch)
Unit : mm (inches)
9 (0.36")
172 (6.78") (mounting hole pitch) 182 (7.17")
87 (3.43")
15.5.3 Terminal layout FX2N-32ER L
N
COM X0 X2 X4 X6 X0 X2 X4 X6 24+ X1 X3 X5 X7 X1 X3 X5 X7
FX 2N-32ER Y0 Y2
Y4 Y6
Y0 Y2
Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7
FX2N-48ER COM X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L
N
24+ X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
FX2N-48ER Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7
202
Page 209
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
11
FX2N-32ET, FX2N-48ET
High-Speed Counters
15.6
15.6 FX2N-32ET, FX2N-48ET
15.6.1 Product specifications
13
1. Power supply specifications 2. Input specifications (sink input) Item
FX2N-48ET
16 points
24 points
Input form sink
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance
10%
4.3 k Input ON current
3.5mA or more/24V DC
Input OFF current
1.5mA or less
Input response time
Approx. 10ms
Input signal form
No-voltage contact input NPN open collector transistor
Input circuit insulation Indication of input operation
15 Input/Output Powered Extension Units
Input response time
14
Removable terminal block (M3 screw)
Test Run, Maintenance, Troubleshooting
Connection type
FX2N-32ET
Photo-coupler insulation
16
LED on panel lights when input.
Input/Output Extension Blocks
Sink input wiring L N
4.3k
Fuse
100 to 240V AC
17 Extension Power Supply Unit
24+ COM
Input circuit diagram
Wiring for Various Uses
→ For the power supply specifications, refer to Section 15.2.
Input points
12 Output Wiring
The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.
X
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
203