Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 25 of 49

FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 15. Input/Output Powered Extension Units, pages 194 to 201

Pages 194 to 201 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 194

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15. Input/Output Powered Extension Units

DESIGN PRECAUTIONS •

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

DESIGN PRECAUTIONS •

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions.

WIRING PRECAUTIONS • • •

188

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

Page 195

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

11 High-Speed Counters

WIRING PRECAUTIONS • •

• •

12

13 Wiring for Various Uses

• wire 2mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Do not wire vacant terminals externally. Doing so may damage the product. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

Output Wiring

•

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a

14 Test Run, Maintenance, Troubleshooting

15 Input/Output Powered Extension Units

16 Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

189

Page 196

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.1

15.1 Outline

Outline An input/output powered extension unit is used to expand inputs/outputs. Power can be supplied to subsequent extension blocks from an input/output powered extension unit with a built-in 24V DC power supply. An input/output powered extension unit is required when the capacity of the main unit’s built-in power supply is insufficient for the current consumption demands of the extension blocks.

15.1.1 Product configuration There are various types of input/output powered extension units. They differ in supply voltage, number of input/output points, input form, output form and connection type. Input/output powered extension units Power supply

Number of points

Input form

Output form

Connection type

100 to 240V AC

32

24V DC (sink/source)

Relay

Terminal block

48

Triac

24V DC (sink)

Transistor (sink) 100V AC Transistor (source)

15.1.2 Product list Each model of input/output powered extension unit has a sink and source type and a sink type. If you intend to add input/output powered extension units, we recommend you to add the same types of units as the main unit or the sink and source type. Sink :Sink [-common], Source Input Model

Type

Number of points

:Source [+common]

Output Common wiring system

Connection type

Number of points

Common wiring system

16

-

Source

24

-

Source

16

Source

24

Source

16

-

24

-

16

-

Terminal block

-

Terminal block

Type

AC power supply common to 24V DC sink and source input FX2N-32ER-ES/UL

16

Sink

Source Relay

FX2N-48ER-ES/UL

24

Sink

24V DC FX2N-32ET-ESS/UL

16

Sink

Terminal block

Transistor FX2N-48ET-ESS/UL

24

Sink

Source

AC power supply only for 24V DC sink input FX2N-32ER

16

Sink Relay

FX2N-48ER FX2N-32ES

24V DC

FX2N-32ET

24

Sink

16

Sink

16

Sink

Triac(SSR)

16

Sink

24

Sink

Transistor FX2N-48ET

24

Sink

AC power supply only for 100V AC FX2N-48ER-UA1/UL

190

100V AC

24

-

Relay

24

Page 197

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

11

Power supply specifications FX2N-32ER-ES/UL FX2N-32ET-ESS/UL

Item

High-Speed Counters

15.2

15.2 Power supply specifications

FX2N-32ER FX2N-32ES FX2N-32ET

FX2N-48ER-ES/UL FX2N-48ET-ESS/UL

FX2N powered extension unit

Supply voltage

100 to 240V AC

Allowable supply voltage range

85 to 264V AC

Rated frequency

50/60 Hz

Power fuse Rush current

250V 3.15A(3A) 5 x 20mm (0.79")

Up to 40A, 5ms or less

200V AC

Up to 60A, 5ms or less

Without extension block

30W (35VA)

35W (45VA)

24V DC, 250mA or less

24V DC, 460mA or less

When input/output extension blocks are connected, 24V DC service power is consumed by With extension block them. → For details, refer to Chapter 6. Removable terminal block (M3 screw) Item

FX2N-48ER-UA1/UL

Classification

FX2N powered extension unit

Supply voltage

100 to 240V AC

Allowable supply voltage range

85 to 264V AC

Power fuse

15

Up to 40A, 5ms or less

200V AC

Up to 60A, 5ms or less

Power consumption

Input/Output Powered Extension Units

250V 5A 5 x 20mm (0.79") 100V AC

35W (45VA)

24V DC service power supply

None

Connection type

16

Removable terminal block (M3 screw)

Input/Output Extension Blocks

15.2.1 Weight, accessories, etc.

MASS (Weight)

0.65kg (1.43 lbs) •

Accessories

FX2N-48ER-ES/UL FX2N-48ET-ESS/UL

FX2N-48ER FX2N-48ET

0.85kg (1.87 lbs)

FX2N-48ER-UA1/UL

17

1.00kg (2.2 lbs)

•

Terminal protective cover (2 pcs.) (Fitted to FX2N-32ER-ES/UL, FX2N-32ET-ESS/UL, FX2N-48ER-ES/UL, FX2N-48ET-ESS/UL and FX2N-48ERUA1/UL) Extension cable (55mm (2.16")) Optional extension cables (FX0N-30EC and FX0N-65EC) are available. Input/output number label

• •

The terminal block uses M3 terminal screws. Installation of the DIN46277 (35mm (1.37") wide) rail or screws.

•

18 Other Extension Units and Options

Others

FX2N-32ER FX2N-32ES FX2N-32ET

Extension Power Supply Unit

FX2N-32ER-ES/UL FX2N-32ET-ESS/UL

Item

14 Test Run, Maintenance, Troubleshooting

Connection type

Rush current

13 Wiring for Various Uses

24V DC service power supply

250V 5A 5 x 20mm (0.79")

100V AC

Power consumption

12 Output Wiring

Classification

FX2N-48ER FX2N-48ET

19 Display Module

20 Terminal Block

191

Page 198

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.2 Power supply specifications

15.2.2 Part names 1. Front [4] Input display LEDs [5] Terminal block covers

[1] Top cover

[6] Extension device connecting connector cover [7] POWER LED

[8] Output display LEDs

[2] DIN rail mounting hooks [3] Model name [1] Top cover

When adding this to the main unit, connect the supplied extension cable or the optional extension cable to the connector under this top cover.

[2] DIN rail mounting hooks (2 places)

The input/output powered extension unit can be installed on DIN rail (35mm (1.38") wide).

[3] Model name

The model name of the input/output powered extension unit is indicated.

[4] Input display LEDs (red)

When an input terminal (X0, X1, etc.) is turned on, the corresponding LED lamps are also turned on. The input numbers change depending on input/output allocation. The input/output powered extension unit (48 points type) assigns input numbers in ascending order from A B C below.

A

C 0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

B [5] Terminal block covers

The covers can be opened about 90 for wiring. Keep the covers closed while the PLC is running (the unit power is on).

[6] Extension device connecting connector cover

Connect the extension cable of input/output powered extension unit/block or special function unit/block to the extension device connecting connector under this cover. FX3U Series extension devices, FX2N Series extension devices, are compatible and can be connected. → For details on extension devices, refer to Chapter 15, Chapter 16 and Section 18.1.

[7] POWER LED (green)

The LED lamp is on (green) while the power supply terminal is on.

[8] Output display LEDs (red)

When an output terminal (Y0, Y1, etc.) is turned on, the corresponding LED lamps are also turned on. The output numbers change depending on input/output allocation. The input/output powered extension unit (48 points type) assigns output numbers in ascending order from A B C below.

A

C 0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

B

192

0

1

2

3

4

5

6

7

Page 199

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.2 Power supply specifications

11 High-Speed Counters

When the terminal block covers are open [10] Input (X) terminals [11] Terminal block fitting screws

[9] Power supply terminal

12 Output Wiring

[12] Terminal names [13] Terminal block covers

[12] Terminal names

13

Wire switches and sensors to these terminals.

[11] Terminal block mounting screws

If the input/output powered extension unit must be replaced, loosen these screws to remove the upper part of the terminal block. → For anchoring the terminal block, refer to Subsection 9.1.2.

[12] Terminal names

The signal names for the power supply, input terminals and output terminals are shown.

[13] Terminal block covers

Protects the upper and lower stages of the terminal block.

[14] Output (Y) terminals

Wire the intended loads (contactors, solenoid valves, etc.) to these terminals.

[15] Protective terminal covers

A protective terminal cover (refer to the following drawing) is fitted to the lower stage of each terminal block to prevent fingers from touching terminals, thereby improving the safety. (FX2NE -ES(S)/UL, UA1/UL)

2. Side

14

15 Input/Output Powered Extension Units

Connect the power supply to the input/output powered extension unit at this terminal.

Test Run, Maintenance, Troubleshooting

[9] Power supply terminal [10] Input (X) terminals

Wiring for Various Uses

[14] Output (Y) terminals [11] Terminal block mounting screws

[15] Protective terminal covers

16 Input/Output Extension Blocks

[1] Nameplate [2] DIN rail mounting groove

17 The product model name, control number and power supply specifications are shown.

[2] DIN rail mounting groove

The unit can be installed on DIN46277 rail (35mm (1.38") wide).

Extension Power Supply Unit

[1] Nameplate

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

193

Page 200

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.3

15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL

FX2N-32ER-ES/UL, FX2N-48ER-ES/UL

15.3.1 Product specifications The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.

1. Power supply specifications → For the power supply specifications, refer to Section 15.2.

2. Input specifications (for sink input and source input) Item Input points

FX2N-32ER-ES/UL

FX2N-48ER-ES/UL

16 points

24 points

Connection type

Removable terminal block (M3 screw)

Input form sink/source

Input signal voltage

24V DC

Input signal current

5mA/24V DC

Input impedance Input response time

4.3 k Input ON current

3.5mA or more/24V DC

Input OFF current

1.5mA or less

Input response time

Approx. 10ms

Input signal form

No-voltage contact input Sink: NPN open collector transistor Source: PNP open collector transistor

Input circuit insulation

Photo-coupler insulation

Indication of input operation

LED on panel lights when input.

Sink input wiring

Source input wiring L N S/S 0V 24V

Input circuit diagram

4.3k

Fuse

L N

100 to 240V AC

S/S 0V 24V

4.3k X

194

10%

X

Fuse

100 to 240V AC

Page 201

FX3G Series Programmable Controllers

15 Input/Output Powered Extension Units

User's Manual - Hardware Edition

15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL

11

Item Output Points

FX2N-32ER-ES/UL

FX2N-48ER-ES/UL

16 points

24 points

Connection type

Removable terminal block (M3 screw)

Output unit

Relay 30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)

Output circuit insulation Indication of output operation Resistance load

2A/point The total load current per common terminal The total load current per common terminal should be the following value. should be the following value. • 4 output points/common terminal: 8A or less • 4 output points/common terminal: 8A or less • 8 output points/common terminal: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.

Inductive load Open circuit leakage current

-

Min. load

14

5V DC, 2mA (reference value) Approx. 10ms

ON OFF

Approx. 10ms

Y

Test Run, Maintenance, Troubleshooting

OFF ON

COM

15

Load DC power supply

Input/Output Powered Extension Units

Output circuit configuration

13 Wiring for Various Uses

Max. load

Mechanical insulation Supplying power to the relay coil will light the LED indicator lamp on panel.

12 Output Wiring

External power supply

Response time

High-Speed Counters

3. Output specifications (relay output type)

Fuse Y

External power supply COM

Fuse A common number applies to the

16 of [COM ].

Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

195