Page 194
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15. Input/Output Powered Extension Units
DESIGN PRECAUTIONS •
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS •
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions.
WIRING PRECAUTIONS • • •
188
Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.
Page 195
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
11 High-Speed Counters
WIRING PRECAUTIONS • •
• •
12
13 Wiring for Various Uses
• wire 2mm2 or thicker. Do not use common grounding with heavy electrical systems (refer to Section 9.3). Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Do not wire vacant terminals externally. Doing so may damage the product. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire the FX2N/FX3U Series extension equipment in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.
Output Wiring
•
Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product. Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and extension units with a
14 Test Run, Maintenance, Troubleshooting
15 Input/Output Powered Extension Units
16 Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
189
Page 196
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.1
15.1 Outline
Outline An input/output powered extension unit is used to expand inputs/outputs. Power can be supplied to subsequent extension blocks from an input/output powered extension unit with a built-in 24V DC power supply. An input/output powered extension unit is required when the capacity of the main unit’s built-in power supply is insufficient for the current consumption demands of the extension blocks.
15.1.1 Product configuration There are various types of input/output powered extension units. They differ in supply voltage, number of input/output points, input form, output form and connection type. Input/output powered extension units Power supply
Number of points
Input form
Output form
Connection type
100 to 240V AC
32
24V DC (sink/source)
Relay
Terminal block
48
Triac
24V DC (sink)
Transistor (sink) 100V AC Transistor (source)
15.1.2 Product list Each model of input/output powered extension unit has a sink and source type and a sink type. If you intend to add input/output powered extension units, we recommend you to add the same types of units as the main unit or the sink and source type. Sink :Sink [-common], Source Input Model
Type
Number of points
:Source [+common]
Output Common wiring system
Connection type
Number of points
Common wiring system
16
-
Source
24
-
Source
16
Source
24
Source
16
-
24
-
16
-
Terminal block
-
Terminal block
Type
AC power supply common to 24V DC sink and source input FX2N-32ER-ES/UL
16
Sink
Source Relay
FX2N-48ER-ES/UL
24
Sink
24V DC FX2N-32ET-ESS/UL
16
Sink
Terminal block
Transistor FX2N-48ET-ESS/UL
24
Sink
Source
AC power supply only for 24V DC sink input FX2N-32ER
16
Sink Relay
FX2N-48ER FX2N-32ES
24V DC
FX2N-32ET
24
Sink
16
Sink
16
Sink
Triac(SSR)
16
Sink
24
Sink
Transistor FX2N-48ET
24
Sink
AC power supply only for 100V AC FX2N-48ER-UA1/UL
190
100V AC
24
-
Relay
24
Page 197
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
11
Power supply specifications FX2N-32ER-ES/UL FX2N-32ET-ESS/UL
Item
High-Speed Counters
15.2
15.2 Power supply specifications
FX2N-32ER FX2N-32ES FX2N-32ET
FX2N-48ER-ES/UL FX2N-48ET-ESS/UL
FX2N powered extension unit
Supply voltage
100 to 240V AC
Allowable supply voltage range
85 to 264V AC
Rated frequency
50/60 Hz
Power fuse Rush current
250V 3.15A(3A) 5 x 20mm (0.79")
Up to 40A, 5ms or less
200V AC
Up to 60A, 5ms or less
Without extension block
30W (35VA)
35W (45VA)
24V DC, 250mA or less
24V DC, 460mA or less
When input/output extension blocks are connected, 24V DC service power is consumed by With extension block them. → For details, refer to Chapter 6. Removable terminal block (M3 screw) Item
FX2N-48ER-UA1/UL
Classification
FX2N powered extension unit
Supply voltage
100 to 240V AC
Allowable supply voltage range
85 to 264V AC
Power fuse
15
Up to 40A, 5ms or less
200V AC
Up to 60A, 5ms or less
Power consumption
Input/Output Powered Extension Units
250V 5A 5 x 20mm (0.79") 100V AC
35W (45VA)
24V DC service power supply
None
Connection type
16
Removable terminal block (M3 screw)
Input/Output Extension Blocks
15.2.1 Weight, accessories, etc.
MASS (Weight)
0.65kg (1.43 lbs) •
Accessories
FX2N-48ER-ES/UL FX2N-48ET-ESS/UL
FX2N-48ER FX2N-48ET
0.85kg (1.87 lbs)
FX2N-48ER-UA1/UL
17
1.00kg (2.2 lbs)
•
Terminal protective cover (2 pcs.) (Fitted to FX2N-32ER-ES/UL, FX2N-32ET-ESS/UL, FX2N-48ER-ES/UL, FX2N-48ET-ESS/UL and FX2N-48ERUA1/UL) Extension cable (55mm (2.16")) Optional extension cables (FX0N-30EC and FX0N-65EC) are available. Input/output number label
• •
The terminal block uses M3 terminal screws. Installation of the DIN46277 (35mm (1.37") wide) rail or screws.
•
18 Other Extension Units and Options
Others
FX2N-32ER FX2N-32ES FX2N-32ET
Extension Power Supply Unit
FX2N-32ER-ES/UL FX2N-32ET-ESS/UL
Item
14 Test Run, Maintenance, Troubleshooting
Connection type
Rush current
13 Wiring for Various Uses
24V DC service power supply
250V 5A 5 x 20mm (0.79")
100V AC
Power consumption
12 Output Wiring
Classification
FX2N-48ER FX2N-48ET
19 Display Module
20 Terminal Block
191
Page 198
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.2 Power supply specifications
15.2.2 Part names 1. Front [4] Input display LEDs [5] Terminal block covers
[1] Top cover
[6] Extension device connecting connector cover [7] POWER LED
[8] Output display LEDs
[2] DIN rail mounting hooks [3] Model name [1] Top cover
When adding this to the main unit, connect the supplied extension cable or the optional extension cable to the connector under this top cover.
[2] DIN rail mounting hooks (2 places)
The input/output powered extension unit can be installed on DIN rail (35mm (1.38") wide).
[3] Model name
The model name of the input/output powered extension unit is indicated.
[4] Input display LEDs (red)
When an input terminal (X0, X1, etc.) is turned on, the corresponding LED lamps are also turned on. The input numbers change depending on input/output allocation. The input/output powered extension unit (48 points type) assigns input numbers in ascending order from A B C below.
A
C 0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
B [5] Terminal block covers
The covers can be opened about 90 for wiring. Keep the covers closed while the PLC is running (the unit power is on).
[6] Extension device connecting connector cover
Connect the extension cable of input/output powered extension unit/block or special function unit/block to the extension device connecting connector under this cover. FX3U Series extension devices, FX2N Series extension devices, are compatible and can be connected. → For details on extension devices, refer to Chapter 15, Chapter 16 and Section 18.1.
[7] POWER LED (green)
The LED lamp is on (green) while the power supply terminal is on.
[8] Output display LEDs (red)
When an output terminal (Y0, Y1, etc.) is turned on, the corresponding LED lamps are also turned on. The output numbers change depending on input/output allocation. The input/output powered extension unit (48 points type) assigns output numbers in ascending order from A B C below.
A
C 0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
B
192
0
1
2
3
4
5
6
7
Page 199
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.2 Power supply specifications
11 High-Speed Counters
When the terminal block covers are open [10] Input (X) terminals [11] Terminal block fitting screws
[9] Power supply terminal
12 Output Wiring
[12] Terminal names [13] Terminal block covers
[12] Terminal names
13
Wire switches and sensors to these terminals.
[11] Terminal block mounting screws
If the input/output powered extension unit must be replaced, loosen these screws to remove the upper part of the terminal block. → For anchoring the terminal block, refer to Subsection 9.1.2.
[12] Terminal names
The signal names for the power supply, input terminals and output terminals are shown.
[13] Terminal block covers
Protects the upper and lower stages of the terminal block.
[14] Output (Y) terminals
Wire the intended loads (contactors, solenoid valves, etc.) to these terminals.
[15] Protective terminal covers
A protective terminal cover (refer to the following drawing) is fitted to the lower stage of each terminal block to prevent fingers from touching terminals, thereby improving the safety. (FX2NE -ES(S)/UL, UA1/UL)
2. Side
14
15 Input/Output Powered Extension Units
Connect the power supply to the input/output powered extension unit at this terminal.
Test Run, Maintenance, Troubleshooting
[9] Power supply terminal [10] Input (X) terminals
Wiring for Various Uses
[14] Output (Y) terminals [11] Terminal block mounting screws
[15] Protective terminal covers
16 Input/Output Extension Blocks
[1] Nameplate [2] DIN rail mounting groove
17 The product model name, control number and power supply specifications are shown.
[2] DIN rail mounting groove
The unit can be installed on DIN46277 rail (35mm (1.38") wide).
Extension Power Supply Unit
[1] Nameplate
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
193
Page 200
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.3
15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL
FX2N-32ER-ES/UL, FX2N-48ER-ES/UL
15.3.1 Product specifications The generic specifications are the same as those for the main unit. → Refer to Section 4.1 for generic specifications. For external wiring, refer to the following chapters. → Refer to Chapter 9 for power supply wiring. → Refer to Chapter 10 for input wiring. → Refer to Chapter 12 for output wiring.
1. Power supply specifications → For the power supply specifications, refer to Section 15.2.
2. Input specifications (for sink input and source input) Item Input points
FX2N-32ER-ES/UL
FX2N-48ER-ES/UL
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Input form sink/source
Input signal voltage
24V DC
Input signal current
5mA/24V DC
Input impedance Input response time
4.3 k Input ON current
3.5mA or more/24V DC
Input OFF current
1.5mA or less
Input response time
Approx. 10ms
Input signal form
No-voltage contact input Sink: NPN open collector transistor Source: PNP open collector transistor
Input circuit insulation
Photo-coupler insulation
Indication of input operation
LED on panel lights when input.
Sink input wiring
Source input wiring L N S/S 0V 24V
Input circuit diagram
4.3k
Fuse
L N
100 to 240V AC
S/S 0V 24V
4.3k X
194
10%
X
Fuse
100 to 240V AC
Page 201
FX3G Series Programmable Controllers
15 Input/Output Powered Extension Units
User's Manual - Hardware Edition
15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL
11
Item Output Points
FX2N-32ER-ES/UL
FX2N-48ER-ES/UL
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Output unit
Relay 30V DC or less 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
Output circuit insulation Indication of output operation Resistance load
2A/point The total load current per common terminal The total load current per common terminal should be the following value. should be the following value. • 4 output points/common terminal: 8A or less • 4 output points/common terminal: 8A or less • 8 output points/common terminal: 8A or less 80VA → For the product life, refer to Subsection 14.4.3. → For cautions on external wiring, refer to Subsection 12.1.3.
Inductive load Open circuit leakage current
-
Min. load
14
5V DC, 2mA (reference value) Approx. 10ms
ON OFF
Approx. 10ms
Y
Test Run, Maintenance, Troubleshooting
OFF ON
COM
15
Load DC power supply
Input/Output Powered Extension Units
Output circuit configuration
13 Wiring for Various Uses
Max. load
Mechanical insulation Supplying power to the relay coil will light the LED indicator lamp on panel.
12 Output Wiring
External power supply
Response time
High-Speed Counters
3. Output specifications (relay output type)
Fuse Y
External power supply COM
Fuse A common number applies to the
16 of [COM ].
Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
195