Page 186
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.6 Judgment by Error Codes and Representation of Error Codes
14.6.4 Error Code List and Action When a program error occurs in the PLC, the error code is stored in special data registers D8061 - D8067 and D8438. The following actions should be followed for diagnostic errors. Error code
PLC operation at error occurrence
Contents of error
Action
I/O configuration error [M8060(D8060)] The head number of unconnected I/O devic
Example: When X020 is unconnected 1 0 2 0 Example: 1020
BCD conversion value Device number: 10 to 177
Continues operation
1: Input (X), 0: Output (Y)
Unconnected I/O relay numbers are programmed. The PLC continues its operation. Modify the program, check wiring connection, or add the appropriate unit/block.
• •
1st to 3rd digits: Device number 4th digit: I/O type (1 = input (X), 0 = output (Y)) Example: When 1020 is stored in D8060 Inputs X020 and later are unconnected. Serial communication error 2 [M8438 (D8438)] 0000, 3801
No error Parity, overrun or framing error
3802
Communication character error
3803
Communication data sum check error
3804
Communication data format error
3805
Command error
3806
Communication time-out detected
3807
Continues operation
Modem initialization error
3808
N:N network parameter error
3812
Parallel link character error
3813
Parallel link sum error
3814
Parallel link format error
3820
Inverter communication error
•
• •
•
Inverter communication, computer link and programming: Ensure the communication parameters are correctly set according to their applications. N:N network, parallel link, etc.: Check programs according to the applications. Remote maintenance: Ensure modem power is ON and check the settings of the AT commands. Wiring: Check the communication cables for correct wiring.
PLC hardware error [M8061(D8061)] 0000, No error
6101
RAM error
6102
Operation circuit error
6103
I/O bus error (M8069 = ON)
6104 6105
Stops operation
6106
Powered extension unit 24 V failure (M8069 = ON)
When memory casette is used, make sure that the memory cassette is installed correctly.
Check for the correct connection of extension cables.
Watchdog timer error
Check user program. The scan time exceeds the value stored in D8000.
I/O table creation error (CPU error)
When turning the power ON to the main unit, a 24V power failure occurs in a powered extension unit. (The error occurs if the 24V power is not supplied for 10 seconds or more after the main power is turned ON.)
PLC/PP communication error (D8062) 0000, 6201 6202 6203 6204 6205
180
No error Parity, overrun or framing error
Continues operation
Communication character error Communication data sum check error Data format error Command error
Check the cable connection between the programming panel (PP) / programming device and the PLC. This error may occur when a cable is disconnected and reconnected during PLC monitoring.
Page 187
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.6 Judgment by Error Codes and Representation of Error Codes
11 PLC operation at error occurrence
Contents of error
High-Speed Counters
Error code
Action
Serial communication error 1 [M8063 (D8063)] 0000, 6302
Communication character error
6303
Communication data sum check error
6304
Communication data format error
6305
Command error
6306
Communication time-out detected Modem initialization error
6308
N:N network parameter error
6312
Parallel link character error
6313
Parallel link sum error
6314
Parallel link format error
6320
Inverter communication error
• •
•
Inverter communication, computer link and programming: Ensure that the communication parameters are correctly set according to their applications. N:N network, parallel link, etc.: Check programs according to applications. Remote maintenance: Ensure modem power is ON and check the settings of the AT commands. Wiring: Check the communication cables for correct wiring.
14, No error
6401
Program sum check error
6402
Memory capacity setting error
6403
Latched device area setting error
6404
15
Comment area setting error Stops operation
File register area setting error
6406
Special unit (BFM) initial value setting, positioning instruction setting sum check error
6407
Special unit (BFM) initial value setting, positioning instruction setting error
6409
Other setting error
STOP the PLC, and correctly set the parameters.
Input/Output Powered Extension Units
6405
Test Run, Maintenance, Troubleshooting
Parameter error [M8064(D8064)] 0000
16, Input/Output Extension Blocks
Syntax error [M8065(D8065)] 0000
No error Incorrect combination of instruction, device symbol and device number
6501
13 Wiring for Various Uses
6307
•
Output Wiring
Parity, overrun or framing error
Continues operation
12
No error
6301
6502
No OUT T or OUT C before setting value
6503
No setting value after OUT T or OUT C Insufficient number of operands for an applied instruction
17
Same label number is used more than once. Same interrupt input or high speed counter input is used more During programming, each instruction is checked. If a syntax than once. error is detected, modify the instruction correctly. Device number is out of allowed range.
Extension Power Supply Unit
6504 6505
Stops operation
Invalid instruction
6507
Invalid label number [P]
6508
Invalid interrupt input [I]
6509
Other error
6510
MC nesting number error
18 Other Extension Units and Options
6506
19 Display Module
20 Terminal Block
181
Page 188
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.6 Judgment by Error Codes and Representation of Error Codes
Error code
PLC operation at error occurrence
Contents of error
Action
Circuit error [M8066(D8066)] 0000, No error
6610
LD, LDI is continuously used 9 times or more.
6611
More ANB/ORB instructions than LD/LDI instructions
6612
Less ANB/ORB instructions than LD/LDI instructions
6613
MPS is continuously used 12 times or more.
6614
No MPS instruction
6615
No MPP instruction
6616
No coil between MPS, MRD and MPP, or incorrect combination
6617
Instruction below is not connected to bus line: STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET, IRET, FEND or END
6618
STL, MC or MCR can be used only in main program, but it is used elsewhere (e.g. in interrupt routine or subroutine).
6619
Invalid instruction is used in FOR-NEXT loop: STL, RET, MC, MCR, I (interrupt pointer) or IRET.
6620 6621
Stops operation
FOR-NEXT instruction nesting level exceeded Numbers of FOR and NEXT instructions do not match.
6622
No NEXT instruction
6623
No MC instruction
6624
No MCR instruction
6625
STL instruction is continuously used 9 times or more.
6626
Invalid instruction is programmed within STL-RET loop: MC, MCR, I (interrupt pointer), SRET or IRET.
6627
No STL instruction
6628
Invalid instruction is used in main program: I (interrupt pointer), SRET or IRET
6629
No P or I (interrupt pointer)
6630
No SRET or IRET instruction STL-RET or MC-MCR instructions in subroutine
6631
SRET programmed in invalid location
6632
FEND programmed in invalid location
182
This error occurs when a combination of instructions is incorrect in the entire circuit block or when the relationship between a pair of instructions is incorrect. Modify the instructions in the program mode so that their mutual relationship becomes correct.
Page 189
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.6 Judgment by Error Codes and Representation of Error Codes
11 PLC operation at error occurrence
Contents of error
High-Speed Counters
Error code
Action
Operation error [M8067(D8067)] 0000, No error
6701
6702 6703 6704 6705 6706
File register is accessed without parameter setting of file register.
6707
12
13 Wiring for Various Uses
No jump destination (pointer) for CJ or CALL instruction Label is undefined or out of P0 to P4095 due to indexing. Label P63 is executed in CALL instruction; cannot be used in CALL instruction as P63 is for jumping to END This error occurs in the execution of operation. Review the instruction. program, or check the contents of the operands used in the applied instructions. CALL instruction nesting level is 6 or more Even if the syntax or circuit design is correct, an operation Interrupt nesting level is 3 or more error may still occur. FOR-NEXT instruction nesting level is 6 or more. For example: "T500Z" itself is not an error. But if Z had a value of 100, the Operand of applied instruction is inapplicable device. timer T600 would attempt to be accessed. This would cause Device number range or data value for operand of applied an operation error since there is no T600 device available. instruction exceeds limit.
Output Wiring
• • •
FROM/TO instruction error
Test Run, Maintenance, Troubleshooting
Other (e.g. improper branching)
This error occurs in the execution of operation. Review the program, or check the contents of the operands used in the applied instructions. Even if the syntax or circuit design is correct, an operation error may still occur. For example: "T500Z" itself is not an error. But if Z had a value of 100, the timer T600 would attempt to be accessed. This would cause an operation error since there is no T600 device available.
Input/Output Powered Extension Units
14
This error occurs in the execution of the operation. • Review the program, or check the contents of the operands used in the applied instructions. • Check whether the specified buffer memories exist in the equipment. • Check whether the extension cables are correctly connected.
6710
Mismatch among parameters
This error occurs when the same device is used within the source and destination in a shift instruction, etc.
6730
Incorrect sampling time (TS) (TS
6732
Incompatible input filter constant ( ) ( < 0 or 100 )
6733
Incompatible proportional gain (KP) (KP < 0)
6734
Incompatible integral time (TI) (TI < 0)
6735
Incompatible derivative gain (KD) (KD < 0 or 201 KD)
6736
Incompatible derivative time (TD) (TD < 0)
6740
Sampling time (TS)
6708
Continues operation
6709
<Auto tuning is continued.> The operation is continued in the condition "sampling time (TS) = cyclic time (scan time)".
17 Extension Power Supply Unit
<PID instruction is stopped.> This error occurs in the parameter setting value or operation data executing PID instruction. Check the contents of the parameters.
16 Input/Output Extension Blocks
Scan time
0)
15
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
183
Page 190
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.6 Judgment by Error Codes and Representation of Error Codes
Error code
PLC operation at error occurrence
Contents of error
Action
Operation error [M8067(D8067)] 6742
Variation of measured value exceeds limit. ( PV < -32768 or +32767 < PV)
6743
Deviation exceeds limit. (EV < -32768 or +32767 < EV)
6744
Integral result exceeds limit. (Outside range from -32768 to +32767)
6745
Derivative value exceeds limit due to derivative gain (KD).
6746
Derivative result exceeds limit. (Outside range from -32768 to +32767)
6747
PID operation result exceeds limit. (Outside range from -32768 to +32767)
6748
<Transpose of output upper limit value and output lower limit PID output upper limit set value < PID output lower limit set value. PID operation is continued.> value. Check whether the target setting contents are correct.
6749
Abnormal PID input variation alarm set value or output <Alarm output is not given. PID operation is continued.> variation alarm set value (Set value < 0) Check whether the target setting contents are correct.
<PID operation is continued.> The operation is continued with each parameter set to the maximum or minimum value.
<Step response method> Improper auto tuning result
<Auto tuning is finished. PID operation is started.> • The deviation at start of auto tuning is 150 or less. • The deviation at end of auto tuning is 1/3 or more of the deviation at start of auto tuning. Check the measured value and target value, and then execute auto tuning again.
<Step response method> Auto tuning operation direction mismatch
<Auto tuning is forcibly finished. PID operation is not started.> The operation direction estimated from the measured value at the start of auto tuning was different from the actual operation direction of the output during auto tuning. Correct the relationship among the target value, output value for auto tuning, and the measured value, and then execute auto tuning again.
6752
<Step response method> Improper auto tuning result
<Auto tuning is finished. PID operation is not started.> Because the set value was fluctuated during auto tuning, auto tuning was not executed correctly. Set the sampling time to a value larger than the output change cycle, or set a larger value for the input filter constant. After changing the setting, execute auto tuning again.
6753
<Limit cycle method> Auto tuning operation direction mismatch
6750
6751
6754
Continues operation
<Auto tuning is forcibly finished. PID operation is not started.> <Limit cycle method> Abnormal PV threshold (hysteresis) set value for auto tuning Check whether the target setting contents are correct. (SHPV < 0)
6755
<Limit cycle method> <Auto tuning is forcibly finished. PID operation is not Abnormal auto tuning transfer status started.> (Data of device controlling transfer status is abnormally Ensure that devices occupied by PID instruction are not overwritten.) overwritten in the program.
6756
<Auto tuning is forcibly finished. PID operation is not started.> The auto tuning time is longer than necessary. Increase the difference (ULV - LLV) between the upper limit and lower limit of the output value for auto tuning, set a smaller value to the input filter constant ( ), or set a smaller value to the PV threshold (SHPV) for auto tuning, and then check the result for improvement.
184
<Limit cycle method> Abnormal result due to excessive auto tuning measurement time ( on > , on < 0, < 0)
Page 191
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.6 Judgment by Error Codes and Representation of Error Codes
11 PLC operation at error occurrence
Contents of error
High-Speed Counters
Error code
Action
Operation error [M8067(D8067)]
<Limit cycle method> Auto tuning result exceeds integral time. (TI = outside range from 0 to 32767)
6759
<Limit cycle method> Auto tuning result exceeds derivative time. (TD = outside range from 0 to 32767)
6760
ABS data read from servo sum check error Continues operation
Check servo wiring and parameter setting. Also check ABS instruction.
Port specified by inverter communication instruction is already Check to make sure the port is not specified by another used in another communication. instruction.
6764
Pulse output number is already used in a positioning Check to make sure the pulse output destination is not being instruction or pulse output instruction (PLSY, PWM, etc.). driven by another positioning instruction.
6765
Number of applied instruction exceeds limit.
6770
EEPROM access error
6772
EEPROM memory cassette is protected against writing.
The number of times an applied instruction is used in the program exceeds the specified limit.
Special block error [M8449 (D8449)] 020*1
General data sum error
021*1
General data message error
Continues operation
FROM/TO error
This error occurs in the execution of operation. • Review the program, or check the contents of the operands used in the applied instructions. • Check whether the specified buffer memories exist in the counterpart equipment. • Check for the correct connection of extension cables. •
090*1
Peripheral equipment access error •
The unit number 0 to 7 of the special function unit/block error is put in
17
18 Other Extension Units and Options
*1.
Check the cable connection between the programming panel (PP) / programming device and the PLC. Check for the correct connection of extension cables.
16
Extension Power Supply Unit
080*1
Check for the correct connection of extension cables.
15
Input/Output Extension Blocks
The write-protect switch of the EEPROM memory cassette was set to ON when data was transferred to the EEPROM memory.
14
Input/Output Powered Extension Units
6763
Check to make sure the input (X), as specified by DSZR or ZRN instruction, is not being used for the following purposes: Input (X) specified by DSZR or ZRN instruction is already - Input interrupt (including the delay function) used in another instruction. - High speed counter C235 to C255 - Pulse catch M8170 to M8175 - SPD instruction
13
Test Run, Maintenance, Troubleshooting
6762
<Auto tuning is finished (KP = 32767). PID operation is started.> The auto tuning time is longer than necessary. Increase the difference (ULV - LLV) between the upper limit and lower limit of the output value for auto tuning, set a smaller value to the input filter constant ( ), or set a smaller value to the PV threshold (SHPV) for auto tuning, and then check the result for improvement.
Wiring for Various Uses
6758
12 Output Wiring
6757
PID operation is <Auto tuning is finished (KP = 32767). started.> <Limit cycle method> The variation of the measured value (PV) is small compared Auto tuning result exceeds proportional gain. (KP = outside with the output value. Multiply the measured value (PV) by range from 0 to 32767) "10" so that the variation of the measured value will increase during auto tuning.
.
19 Display Module
20 Terminal Block
185
Page 192
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.7
14.7 Troubleshooting
Troubleshooting → For the procedures on running and stopping the PLC, refer to Section 14.2. → For the procedures on operating peripheral devices, refer to the manuals for the peripheral devices. → For the phone numbers and addresses of Mitsubishi Electric System & Service Co., Ltd., refer to the service network at the end of this manual.
14.7.1 Output does not operate (main unit and input/output extension blocks) 1. Output does not turn on. Stop the PLC, and forcibly turn the inoperable output on then off with a peripheral device or the display module to check its operation. Check for troubles with external wiring. • When the output operates The output may be turned off unintentionally in the program. Reexamine the program. (Duplicate coil or RST instructions) • When the output does not operate Check the configuration of the connected devices and the connection of the extension cables. If the configuration of the external wiring and connected devices and the connection of the extension cables are acceptable, the output circuit may be damaged. Consult your local Mitsubishi Electric distributer.
2. Output does not turn off. Stop the PLC, and check that the output turns off. Check for trouble with external wiring. → For the procedures on running and stopping the PLC, refer to Section 14.2. • When the output turns off The output may be turned on unintentionally in the program. Check that there are no duplicate coils in the program. • When the output does not turn off The output circuit may be damaged. Consult your local Mitsubishi Electric distributer.
14.7.2 24V DC input does not operate (main unit and input/output extension blocks) 1. Input does not turn on. Disconnect the external wiring and connect the S/S terminal and the 0V terminal or the 24V terminal. Short-circuit the 0V terminal or 24V terminal not connected to the S/S terminal and the input terminal, then check the input display LED or a peripheral device to confirm that the input turns on. Measures When input turns on
Check that the input device does not have a built-in diode or parallel resistance. If so, refer to Subsection 10.2.2.
Measure the voltage between the 0V terminal or 24V terminal not connected to the S/S terminal and the input When input does not terminal with a tester to confirm that the voltage is 24V DC. turn on • Check the configuration of the external wiring and connected devices and the connection of the extension cables.
2. Input does not turn off. Check for leakage current from input devices. If the leakage current is 1.5mA or more, it is necessary to connect a bleeder resistance. → For details on the measures, refer to Subsection 10.2.2.
186
Page 193
FX3G Series Programmable Controllers
14 Test Operation, Adjustment, Maintenance and Troubleshooting
User's Manual - Hardware Edition
14.7 Troubleshooting
11 High-Speed Counters
14.7.3 Cautions in registering keyword 1. Cautions in registering keyword
2. Caution on using a peripheral device which does not support the second keyword and customer keyword Sequence programs in which the second keyword and customer keyword are registered cannot be all-cleared using the programming tool (GX Developer whose version is earlier than Ver. 8.72A).
12 Output Wiring
The keyword limits access to the program prepared by the user from peripheral devices. Keep the keyword carefully. If you forget the keyword, you cannot operate the PLC online from the programming tool depending on the type of the programming tool and the registered keyword.
13 Wiring for Various Uses
3. Non-resettable protect function When the non-resettable protect function is set, the protect function cannot be reset.
14 Test Run, Maintenance, Troubleshooting
15 Input/Output Powered Extension Units
16 Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
187